| 1 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for foundation etc for laying of cables, erection of poles, struts/ stays etc not exceeding 10 sqm on plan and getting out in soft loose soil completeall as specified and directed. |
| 2 | Returning, filling in, including spreading leveling watering and well ramming inlayers not exceeding 25 cm in any type of soil completeall as specified and directed. |
| 3 | Removing excavated materials to a distance not exceeding 50 m and depositing where directed, at a level not exceeding 1.5 m above the starting pointcompleteall as specified and directed. |
| 4 | M & L for sand filling in trenches for cushioning of LT cables punning after filling complete as specified and as directed.Note: Punned thickness shall only be measured and paid |
| 5 | Supply and lay un-reinforced precast concrete cable cover , class , LV , Type Iflat size 250 x 150x 40 mm laid dry in treches over under ground cables completeall as specified and directed. |
| 6 | S & FGI pipe,light grade, of size 40 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed. |
| 7 | S & FGI pipe,light grade, of size 50 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed. |
| 8 | Dismantaling of any type and size ACSR conductor complete all as specified and directed. |
| 9 | Dismantaling of stay assemblyincluding demolation of concrete etccomplete all as specified and directed. |
| 10 | Dismantaling of insulator any size and any typecomplete all as specified and directed. |
| 11 | Dismantaling of cross arm of MS chanel or angle sections any type any size etc complete all as specified and directed. |
| 12 | Disconnecting, taking out, removing old existing unserviceable LT cable overhead service cable of any size etc completeall as specified and directed. |
| 13 | Supplying ,Laying , jointing and testingXLPE insulated, armoured, heavy duty, LT aluminum conductor cable1100 volts grade of size 4 core 16 Sqmm laid in trenches/ducts, floors, fixed to walls etc completeall as specified and directed. |
| 14 | Supplying ,Laying , jointing and testingXLPE insulated, armoured, heavy duty, LT aluminum conductor cable1100 volts grade of size 2 core 10 Sqmm laid in trenches/ducts, floors, fixed to walls etc completeall as specified and directed |
| 15 | Supplying ,Laying , jointing and testingXLPE insulated, armoured, heavy duty, LT aluminum conductor cable1100 volts grade of size 4 core 25 Sqmm laid in trenches/ducts, floors, fixed to walls etc completeall as specified and directed. |
| 16 | Supplying ,Laying , jointing and testingXLPE insulated, armoured, heavy duty, LT aluminum conductor cable1100 volts grade of size 3.5 core 35 Sqmm laid in trenches/ducts, floors, fixed to walls etc completeall as specified and directed. |
| 17 | Supplying ,Laying , jointing and testingXLPE insulated, armoured, heavy duty, LT aluminum conductor cable1100 volts grade of size 3.5 core 70 Sqmm laid in trenches/ducts, floors, fixed to walls etc completeall as specified and directed. |
| 18 | Supplying ,Laying , jointing and testingXLPE insulated, armoured, heavy duty, LT aluminum conductor cable1100 volts grade of size 3.5 core 95 Sqmm laid in trenches/ducts, floors, fixed to walls etc completeall as specified and directed. |
| 19 | Supplying ,Laying , jointing and testingXLPE insulated, armoured, heavy duty, LT aluminum conductor cable1100 volts grade of size 3.5 core 150 Sqmm laid in trenches/ducts, floors, fixed to walls etc completeall as specified and directed. |
| 20 | Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type(KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following :-Main LT panel near cook house transformer Incoming(a) AluminiumBus bar, 525A Amps TPN -01 set(b) MCCB 4 Pole thermal magnetic release 415 volts 350 A 36 KA-01(c)Digital Ammemeter 0 to 200 Amps with CT coils and selector switch - 01 No(d) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)(e)Digital voltmeter 0 to 500V with selector switch - 01No(f) Digital Multifunctional meter - 01 NoOutgoing(a) MCCB 4 Pole thermal magnetic release 415 volts 160A 36 KA-01(b) MCCB 4 Pole thermal magnetic release 415 volts 100 A 36 KA-02(c) MCCB 4 Pole thermal magnetic release 415 volts 63 A 36 KA-03(d) Automatic timer panel of capacity 5KW |
| 21 | Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type(KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following (LT Panel-1 near OR line )Incoming(a) AluminiumBus bar, 240 Amps TPN -01 set(b) MCCB 4 Pole thermal magnetic release 415 volts 160 A 35 KA-01 (c)Digital Ammemeter 0 to 200 Amps with CT coils and selector switch - 01 No(d) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three) (e) Digital volmaeter 0 to 500V with selctor swithch-01 No(f) Digital Miltifunctional meter -01 NoOutgoing(a) MCCB 4 Pole thermal adjustable magnetic release 415 volts 63A -5(b) 240VSPN 32A -8 |
| 22 | Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type(KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following :-(LT Panel-2Near BN store)Incoming (a) AluminiumBus bar, 150 Amps TPN -01 set(b) MCCB 4 Pole thermal magnetic release 415 volts 100 A 35 KA-01 (c) Digital Ammemeter 0 to 200 Amps with CT coils and selector switch - 01 No(d) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)(e)Digital voltmeter 0 to 500V with selector switch - 01No(f) Digital Multifunctional meter - 01 NoOutgoing(a) MCCB 4 Pole thermal adjustable magnetic release 415 volts 63A -03 Nos(c) 240V SPN 32A-4 |
| 23 | Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type(KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following :-(LT panel-3 MT area )Incoming(a) AluminiumBus bar, 150 Amps TPN -01 set(b) MCCB 4 Pole thermal magnetic release 415 volts 100 A 35 KA-01(c) Digital Ammemeter 0 to 200 Amps with CT coils and selector switch - 01 No(d) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)(e)Digital voltmeter 0 to 500V with selector switch - 01 No (f) Digital Multifunctional meter - 01 NoOutgoing(a) MCCB 4 Pole thermalmagnetic release 415 volts 63A 1 Nos(b) 240VSPN 32A -10 |
| 24 | Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type(KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following :-(Main LT panel near JCO Mess)Incoming (a) Copper Bus bar, 400 Amps TPN -01 set(b) MCCB 4 Pole thermal magnetic release 415 volts 250 A 35 KA-01 (c) Digital Ammemeter 0 to 200 Amps with CT coils and selector switch - 01 No(d) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)(e)Digital voltmeter 0 to 500V with selector switch - 01No(f) Digital Multifunctional meter - 01 NoOutgoing(a) MCCB 4 Pole thermal adjustable magnetic release 415 volts 100A 16-2 Nos(b)MCCB 4 Pole thermal adjustable mangnetic release 415 volts 63 A 16 KA-5(c)Automatic timer panel of capacity 5KW |
| 25 | Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type(KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following :-(LP panel near new old cook house)Incoming(a) Aluminium Bus bar, 150 Amps TPN -01 set(b) MCCB 4 Pole thermal magnetic release 415 volts100A 35 KA-01 (c) Digital Ammemeter 0 to 200 Amps with CT coils and selector switch - 01 No(d) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)(e)Digital voltmeter 0 to 500V with selector switch - 01No(f) Digital Multifunctional meter - 01 NoOutigoing(a) 240VSPN 32A -15(b) MCCB 4 Pole thermal adjustable magnetic release 415 volts63A 16KA -2 nos |
| 26 | Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type(KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following :-(LP panel near QRT bathroom)Incoming(a) Aluminium Bus bar, 100 Amps TPN -01 set(b) MCCB 4 Pole thermal magnetic release 415 volts 63A 16 KA-01 (c) Digital Ammemeter 0 to 200 Amps with CT coils and selector switch - 01 No(d) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three) (e)Digital voltmeter 0 to 500V with selecter switch -01 No(f) Digital Multifunctional meter - 01 NoOutgoing(a)240V SPN 32A-5 |
| 27 | Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type(KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following :-(LP panel RP agte )Incoming(a) Aluminium Bus bar, 100 Amps TPN -01 set(b) MCCB 4 Pole thermal magnetic release 415 volts 63A 16 KA-01 (c) Digital Ammemeter 0 to 200 Amps with CT coils and selector switch - 01 No(d) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)(e)Digital voltmeter 0 to 500V with selector switch - 01No(f) Digital Multifunctional meter - 01 NoOutgoing(a) 240VSPN 32A -4(b) MCCB 4 Pole thermal adjustable magnetic release 415 volts 63A 16KA2 no |
| 28 | Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type(KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following :-(Qtr Guard & CMP)Incoming(a) Aluminium Bus bar, 150 Amps TPN -01 set(b) MCCB 4 Pole thermal magnetic release 415 volts100A 35 KA-01(c) Digital Ammemeter 0 to 200 Amps with CT coils and selector switch - 01 No(d) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)(e)Digital voltmeter 0 to 500V with selector switch - 01No(f) Digital Multifunctional meter - 01 NoOutgoing(a) MCCB 4 Pole thermal adjustable magnetic release 415 volts 63A 16KA -2 nos(b) 240VSPN 32A -1 |
| 29 | M&L , earthing complete for machinary / Equipment installed at power house / sub station with galavanised steel earth plate electrode of size 60 cmx 60 cmx 6 mm thick buried directly in ground ( earth pit not less then 2.25 m deep below the normal ground level ) with top edge of the earth plate not less then 1.5m below normal Ground level connected galvanised earth strip 32X6 mm by means of bolts, nuts, washerws and check nutsall shown in electrical plate No.5 of SSR Part- I connected to main board / disribution board complete .Earthing GI lead and GI protection pipe 15 mm dia light grade upto 7.5 m from earth pit connecting to machinary/ equipment, testing point, all as specified and testing on completeall as specified and directed. |
| 30 | Note :- (i) The unit rate shall also included for earth work in hard /dense soil , PCC type C-I (1:3:6) chamber , PCC 1:2:4 type B-I cover 50 mm thick reinforced with 8 mm dia TMT bars,150 mm c/c both ways, funnelwith watering pipe 20 mm dia medium graded , GI protection pipe light grade 15 mm dia and wire mesh complete in addition to items No. 1(a) to (e) of preamble (notes) under sub heading earthing specified on SI page No. 389 of SSR Part - II. |
| 31 | (ii) Earthing strip and GI protection pipe beyond 7.5 mtrs will be measured and paid separatelly if required under appropriate Schedule. |
| 32 | (iii)Earthing shall be tested as specified incasul 19.137 of SSP PART - I 2009 , to the entire satisfication of Engr-in-Charge. (ii) On teting after complataion of earthing,if the desired earth resistance is not obatined the earthing wiil be re done by thecontractor at his on risk and cost to the entire satisfaction of the Engr - in - charge. |
| 33 | NOTE APPLICABLE FOR ALL ITEMS :- If rate quoted for similar/identical items in same part of Sch ‘A’ is at variance, the lowest rate quoted shall only be considered for payment to the contractor. |