| 1 | Dismantling of unserviceable worn out / weathered / damaged ACSR conductor, service feeder of any sizeand type from pole after disconnectingjumpers and insulator bindings complete all as specified and directed. |
| 2 | Dismantling cross arm of MS channel or angle section frompole anysize complete all as specified and directed. |
| 3 | Dismantling insulators of any type and any size complete all as specified and directed. |
| 4 | Dismantling stay assembly complete all as specified and directed. |
| 5 | Dismantling GI earth wire/Old Unsv Grading complete all as specified and directed. |
| 6 | Dismantling cable protection pipe 25/40/50/80 mm dia complete all as specified and directed. |
| 7 | Taking out Old Unsv Service mains/ Old Unsv UG cable any type complete all as specified and directed. |
| 8 | Supply, laying, Jointing connectingof LTUG cable XLPEinsulated,PVC bedded galvanised steel strip or wirearmoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 10 sqmm 2 core laid in trenches/ on poles / walls / in ducts / passing through pipes and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed. |
| 9 | All as per item No. 8.00 above but for 06 Sqmm 2 Core. |
| 10 | All as per item No. 8.00 above but for 16 Sqmm 4 Core. |
| 11 | All as per item No. 8.00 above but for 25 Sqmm 4 Core. |
| 12 | All as per item No. 8.00 above but for 35 Sqmm 3.5 Core. |
| 13 | All as per item No. 8.00 above but for 50 Sqmm 3.5 Core. |
| 14 | All as per item No. 8.00 above but for 70 Sqmm 3.5 Core |
| 15 | All as per item No. 8.00 above but for 95 Sqmm 3.5 Core |
| 16 | All as per item No. 8.00 above but for 120 Sqmm 3.5 Core |
| 17 | All as per item No. 8.00 above but for 150 Sqmm 3.5 Core |
| 18 | Supply and fixing in replacement ofsteel tubular swaged poles, type 410 SP 31 (Overall length 9.00 m) complete with cast iron base plate, finial taper plug, bolts, nuts screws and washers including painting two coats of black bituminous paint internally and externally up to planting depth and remaining external portion with two coats of aluminum paints over a coat of red oxide primer and writing pole Nos with white paint on black back groundcomplete all as specified and directed. |
| 19 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and directed. |
| 20 | All as per item No 19.00 but Exc 1.50 but n.exc 3.0m deep complete all as specified and directed. |
| 21 | Supply and spread sand in trenches as sand cushioning to underground cable for protection with dry fine river sand and provide required cover after punning down 18CM will be measured and paid complete all as specified and directed.Note: Thickness of sand cushion after punning down will be measured and paid. |
| 22 | Supply and laying wellburntsub class‘B’ bricks( designated 75) locally available best quality, laid dryin trenches forprotection of underground cable complete all as specified and directed. |
| 23 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm as in soils complete all as specified and directed. |
| 24 | Removing excavated materials to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5 mtr above the starting point as in soils complete all as specified and directed. |
| 25 | Supply and layingof DWC Double wall corrugated Duct Pipe as cable protection pipe in trench/wall/pole including all fittings complete all as specified and directed for the following sizes (OD X ID) :- |
| 26 | All as per item no 25.00 above but Size 40 X 32 mm |
| 27 | All as per item no 25.00 above but Size 63 X 50 mm |
| 28 | All as per item no 25.00 above but Size 75 X 63 mm |
| 29 | M&L for plain cement concrete 1:4:8 type D-2 (using 40mm graded stone aggregate) in foundation of PCC poles/struts as specified including necessary form work, complete all as specified and directed. |
| 30 | M&L for plain cement concrete 1:3:6 type C-2 (using 40mm graded stone aggregate) in foundation of stay assembly etc including necessary form work, complete all as specified and directed. |
| 31 | Supply and laying in replacement of GI tube light grade as in cable protection pipe including all fittings & taking down / taking out from trenchcomplete all as directed for the following sizes :- |
| 32 | 25 mm bore |
| 33 | 40 mm bore |
| 34 | 80 mm bore |
| 35 | Material and labour for cuttingof road/ hard standingn exc 20cm widthandn exc 60cm in depth for laying ofcable protection pipe including making good the disturbed road/hard standing by providing PCC (1:2:4) type B1to match with existing surface complete all as specified and directed. |
| 36 | S&F in replacement MCCB 3 pole, 415 V, adjustable type 25 to 100 Amp with breaking capacity 16 KA complete all as specified anddirected. |
| 37 | S&F in replacement MCCB 3 pole, 415 V, adjustable type 125 Amp with breaking capacity 16 KA complete all as specified anddirected. |
| 38 | S&F in replacement MCCB 4 pole, 415 V, adjustable type 160 Amp with breaking capacity 36 KA complete all as specified anddirected. |
| 39 | S&F in replacement MCCB 4 pole, 415 V, adjustable type 200 Amp with breaking capacity 36 KA complete all as specified anddirected. |
| 40 | S&F in replacement MCCB 4 pole, 415 V, adjustable type 250 Amp with breaking capacity 36 KA complete all as specified anddirected. ((Make: Havells /HPL / Indo Asian / Hager)) |
| 41 | S&F in replacement MCCB 4 pole, 415 V, adjustable type 350 Amp with breaking capacity 36 KA complete all as specified anddirected. (Make: Havells /HPL / Indo Asian / Hager) |
| 42 | Supply and fixing, in replacementLED street light fitting70/75Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified anddirected. |
| 43 | Supply, fixing and testing in replacement Street light automatic Nature switch of capacity 3 KW single phase complete with high and low voltage and overload protection, degree of protection confirm to 1P-55 AC, SP complete with MCB and power contactor fixed on pole with 25 X 3mm MS strip clamp including provision of 6 sqmm 3 core cable for connection complete all as specified anddirected. Make - Kakatiya Energy system Model SWADEEP |
| 44 | S&F in replacement ofIP65/IP66 Thermoplastic Polycarbonate cable Junction box for street lights; size not less than 250mm x 250mm x 160 mmsuitable for cable dimensions of size10 to25 sq mm, with 25 sqmm terminal of 32 Amps rating for three phase & neutral mounted on din railwith locking arrangement fixed to PSC/Steel Poles by means of suitable size of clamps made of MS flat 20 x 4mm - 2 Nos with nut, bolts & double washers andincluding provn for fixing 01 No. single pole, MCB, 10 amps,10KA, ‘B’ series with ON/OFF flap complete all as specified and directed. |
| 45 | M&L for cleaning, scrapping, preparingof old painted steel tubular pole 9m long and applying one coat of aluminium red oxide primer and two coat of aluminium paint to pole and accessories / fittings whatever fixed on pole including marking/writing pole No on each pole with yellow SE paintwith 5cm large bold letters on black background of suitable size at a height of 2m above GL complete all as specified and directed. |
| 46 | M&L for earthing in replacement complete with galvanized iron earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to GI strip 25x4 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth wire protected by 50mm dia GI pipe medium grade and connected to pole structure/ panel board/earthing test point all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and directed.Note :- The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, protection pipe, earth strip up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II |
| 47 | S&F in replacement ofcable joining kit for grade cable for outdoor termination heat shrink type joint complete with joining material and accessories suitable for LTXLPE armoured aluminium conductor cable of size 50 sqmm to 120 sqmmcomplete all as specified and directed. |
| 48 | Design, supplying, installing, testing and commissioning LT Outdoor type, double door IP - 65 type panel board factory fabricated cubicaltype weather andvermin proof with locking arrangement made out of MS CRCA sheet 3.15 mm thick suitable size of channel for base complete with aluminium bus bar inside sepreate chamberand compartmentalised cabinet for housing andmounting MCCBs,metering eqpt prewired with suitble size of copper conductor and duly powder coated and panel board fixed on angle iron frame which is made out of 50 x 50 x 6 mm thick angle iron duly marked the incoming & alloutgoing controls and comprising with the following duly CPRI Approved-Incomer- Incomer - MCCB 4P 320A 36kA-1No, Out going:-MCCB 4P 200A 25kA-2No,MCCB 4P 160A 25kA -01 Nos, MCCB 4P 100A 25kA -01 Nos, MCB TPN 63 A, 10 KA-01 No, 04 Nosmain aluminum bus bar. Bus Bar shall be of 1.5 times of Incomer , all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint. Microprocessor based threephase phase electronic 01 No.Digital Ammeter (0-300) with ASS-1No, Current transformer of rating 300/5A-1No, Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1, PCC foundation complete all as specified and directed. |
| 49 | Design, supplying, installing, testing and commissioning LT Outdoor type, double door IP - 65 type panel board factory fabricated cubicaltype weather andvermin proof with locking arrangement made out of MS CRCA sheet 3.15 mm thick suitable size of channel for base complete with aluminium bus bar inside sepreate chamberand compartmentalised cabinet for housing andmounting MCCBs,metering eqpt prewired with suitble size of copper conductor and duly powder coated and panel board fixed on angle iron frame which is made out of 50 x 50 x 6 mm thick angle iron duly marked the incoming & alloutgoing controls and comprising with the following duly CPRI ApprovedIncomer - MCCB 4P 250A 36kA-1No, Out going:-MCCB 4P 200A 25kA-1No,MCCB 4P 160A 25kA -01 Nos, MCB TPN 63 A, 10 KA-01 No, 04 Nosmain aluminum bus bar. Bus Bar shall be of 400A , all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint. Microprocessor based threephase phase electronic 01 No.Digital Ammeter (0-300) with ASS-1No, Current transformer of rating 300/5A-1No, Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1, PCC foundation complete all as specified and directed. |
| 50 | Design, supplying, installing, testing and commissioning LT Outdoor type, double door IP - 65 type panel board factory fabricated cubicaltype weather andvermin proof with locking arrangement made out of MS CRCA sheet 3.15 mm thick suitable size of channel for base complete with aluminium bus bar inside sepreate chamberand compartmentalised cabinet for housing andmounting MCCBs,metering eqpt prewired with suitble size of copper conductor and duly powder coated and panel board fixed on angle iron frame which is made out of 50 x 50 x 6 mm thick angle iron duly marked the incoming & alloutgoing controls and comprising with the following duly CPRI ApprovedIncomer - MCCB 4P 200A 36kA-1No, Out going:-MCCB 4P 160A 25kA-1No,MCCB 4P 100A 25kA -01 Nos, MCB TPN 63 A, 10 KA-01 No, 04 Nosmain aluminum bus bar. Bus Bar shall be of 400A , all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint. Microprocessor based threephase phase electronic 01 No.Digital Ammeter (0-300) with ASS-1No, Current transformer of rating 300/5A-1No, Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1, PCC foundation complete all as specified and directed. |
| 51 | Design, supplying, installing, testing and commissioning LT Outdoor type, double door IP - 65 type panel board factory fabricated cubicaltype weather andvermin proof with locking arrangement made out of MS CRCA sheet 3.15 mm thick suitable size of channel for base complete with aluminium bus bar inside sepreate chamberand compartmentalised cabinet for housing andmounting MCCBs,metering eqpt prewired with suitble size of copper conductor and duly powder coated and panel board fixed on angle iron frame which is made out of 50 x 50 x 6 mm thick angle iron duly marked the incoming & alloutgoing controls and comprising with the following duly CPRI Approved-Incomer- MCCB 4P 250A 36kA-1No, Out going:-MCCB 4P 100A 25kA-1No, , MCB TPN 63 A, 10 KA-01 No, 04 Nosmain aluminum bus bar. Bus Bar shall be of 1.5 times of Incomer , all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint. Microprocessor based threephase phase electronic 01 No.Digital Ammeter (0-300) with ASS-1No, Current transformer of rating 300/5A-1No, Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1, PCC foundation complete all as specified and directed. |
| 52 | Total in Figures |
| 53 | Quoted Amount in Words |