| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthingthe point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. (Make: Polycab/ Finolex/ L&T ) |
| 2 | Group A |
| 3 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface /recessed medium class PVC conduit, 2 way modular switch,modular plate, suitable GI box and earthing the point with 1.5sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.(Make:Polycab/Finolex/ L&T) |
| 4 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. (Make: Polycab/ Finolex/ L&T) |
| 5 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 6 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 7 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 8 | 2 X6sq. mm + 1 X 6 sq. mm earth wire |
| 9 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 10 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). (Make- L& T/ABB/LEGRAND /INDOASEAN) |
| 11 | Supplying and fixing suitable size GI/PVC box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.(Make- L& T/ABB/LEGRAND /INDOASEAN) |
| 12 | Supplying & fixing suitable size GI/PVC box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, “C” curve including connections, painting etc. as required. (Make- L & T/ABB/LEGRAND /INDOASEAN) |
| 13 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without\ MCB/RCCB/Isolator) (Make- L & T/ABB/LEGRAND /INDOASEAN) |
| 14 | 4 way (4 + 12), Double door |
| 15 | 8 way (4 + 24), Double door |
| 16 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Make: L&T/ABB/C&S/Legrand/Hagger/Schneider) |
| 17 | Single Pole MCB |
| 18 | FP MCB 40/63 A |
| 19 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt). Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body materialand construction as per IS : 10322 withdriver (Replaceable)as per the requirement with Driver efficiency >85%, Operating voltage AC 140 270 Volt,frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P.F.≥0.95, IP20,CRI>80, Flicker free, (flickershould be below 5 %), life time (LED, Driver & electrical circuitry), ofminimum 50000BurningHourswith70%ofinitial Lumenmaintained tilllifeends, CCT3000°K/ 4000°K / 5700°K/6500°K(AsperANSIBin), SDCM(Standard Deviation Colour Matching) <3,Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BISstandard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete inall respecti/c external connectionswith1.5sqmm FRLS/HFFR,PVCinsulatedcopper conductorsingle core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy≥105 <120lm/Watt output . LM79 & LM80 Test report andalltestingrequiredforLED fixtures as per BISshall be submitted.Shape size and CCT shall be as approved by Engineer-in Charge as per requirement. (Thermalmanagement:heatsinkofaluminiumhousing such that LED junction temperature shall not rise above 90°C). Powdercoateddiecast/Extruded aluminiumBody (Thickness > 1.20 mm) (Make: Wipro/ Philipse/CG/Polycab/) |
| 20 | 18-22 Watt |
| 21 | Brush Less Direct Current (BLDC) Fan without Remote: Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%,suitable for operation withregulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019fani/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor singlecorecableandearthingetc.asrequired.(Make: Atomberg/Usha/Crompton/Orient) |
| 22 | 1400mm,service value≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum) |
| 23 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 24 | Supplying and fixing ofDecorative Wall Light/Wall Lamp ,Bulb Base : B22 | Synthetic Finish Product Dimensions 7.3Lx 3.9W x 9.1H Centimeters (Philips) (Make: Crompton/Wipro/Philips/Polycab) |
| 25 | Supplying and fixing of 3W LED, 2 star Base ,B22 bulb.Crompton Cat No: LED3WNDFWB2SCDL (Make: Crompton/Wipro/Philips/Polycab) |
| 26 | Supplying and fixing of 9 W LED bulb, 2 star Base ,B22 bulb.Crompton Cat No: LED9WNDFWB2SCDL (Make: Crompton/Wipro/Philips/Polycab) |
| 27 | Supplying and fixing of 230VAC 1Ph. 250 mm exhaust Fanwith sweep feature. INDOASIAN Cat No: 698502 HSN CODE : 8536(Make: Usha / Crompton / Orient/INDOASIAN) |
| 28 | Supplying and fixing of 230VAC 1Ph. 300 mm exhaust Fanwith sweep feature. (Make: Usha / Crompton / Orient) |
| 29 | Providing,installation, fixing,Connecting and Testing of Calling Bell INDOASIAN Cat No: 800144 HSN CODE : 8536Make: (INDOASIAN / Crompton / Anchor) |
| 30 | Providing,installation, fixing,Connecting and Testing of Mirror Light. (Make: Wipro/ Philipse/CG/Polycab/) |
| 31 | Supply and Installation of Solarion Eclipse Round IP65 Gate Lamp (Plastic with B22 Holder) Crompton Cat No: GTLMP ECLRND-WH (Make: Philipse/ Wipro/Crompton / Polycab) |
| 32 | Supplying, installing and testing of Three phase Kwh meter with LCD display(1P LCD Meter 5-30A )L&TCat No: WR301BC4D20 (Make: L&T/Schneider/Avon Meters/Secure) |
| 33 | LED FloodLight, powdercoatedpressurediecastaluminium(Systemlumenefficacy>135 lm/Watt) Supplying,Installation,Testing&CommissioningofFloodLight, powdercoatedpressuredie castaluminium body with built in or separate driver as per the requirement with Driver efficiency >85%,Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95,IP-66,IK-10,CRI>70,undervoltageandovervoltageprotection,EMI-EMCasper CISPR-15,lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum50000 Burning Hours with 70% of initial Lumen maintained tilllife ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K/6500°K(AsperANSIBin), SDCM(Standard Deviation Colour Matching) <5, Maximumpowerconsumptionshouldnotmore than the specified rating and Fixture shall be of relevant BIS standardcompleteinallrespecti/c external connectionswith1.5sq.mmFRLS/HFFR,PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report andalltestingrequiredforLED fixtures as per BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermalmanagement:heatsinkof aluminium housing such that LED junction temperature shall not rise above 90°C). (Make: Crompton/Wipro/Philips/Polycab) |
| 34 | 50 watt |
| 35 | Supplying, installing, testing and commissioning of following capacity TPN tap off box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing rising mains complete with TPN disconnector FSU and HRC fuses,connections, earthing etc. as required. Make:L&T/ABB/C&S/Legrand/Hagger/Schneider |
| 36 | 63 A TPN |
| 37 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required |
| 38 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 39 | Supply and fixing of Polycarbonate, Rectangular, IP44Box Dimension : 250 x 250 x 155 mm for Mounting of Energy Meter Make: Sintex |