| 1 | Detail of Work |
| 2 | Safe cartage of PCC/ST poles up to 8.5/11 Mtr. Long from ESC, SRE/JE store to site of work at various sites of Sarsawa Town including loading & unloading at both ends.(Dist.Up to 20 Km.) |
| 3 | Safely cartage of other complete line material (Except PCC Poles/ABC Cable/XLPE Cable) from ESC, SRE/ JE store to site of work at various sites of Sarsawa Town including loading, unloading at both ends.( Dist.App. 0 to 20 Km.) |
| 4 | Safe cartage of 11 KV XLPE Cable 3x120/3x300 sq.mm from ESC,SRE, to the site of work including loading & unloading at both ends. (Dist. Upto 20 km.) |
| 5 | Safe cartage of ABC Cable 3*95/3x120 sq.mm from ESC,SRE, to the site of work including loading & unloading at both ends. (Dist. Upto 20 km.) |
| 6 | Complete work of Laying, lifting, stringing proper sagging of 11 KV XLPE cable 3X120 sq mm of including complete etc |
| 7 | Complete work of Laying, lifting, stringing proper sagging of 11 KV XLPE cable 3x300 sq mm of including complete etc |
| 8 | Complete Work of 11 KV cable terminations kit out door & indoor of size 3X120 sq mm.(Heat Shrink Cable Box) |
| 9 | Complete work of 11 KV cable terminations kit out door & indoor of size 3x300 sq mm. (Heat Shrink Cable Box) |
| 10 | Complete work of Laying, lifting, and Stringing proper sagging ABC cable of site 3x120 sq.mm including fixing of all type clamp and connector providing all accessories |
| 11 | Erection of single support on ST/ PCC poles up to 8.5/11 Mtr Long with complete fitting of all accessories of 11 KV/LT line. complete. |
| 12 | Fixing of 11 KV stay rods by digging of pits in block of 600X600X300 mm. & with nozzling of stay wire 7/10 SWG and fitting the same on the pole |
| 13 | Providing and fixing of PRC Connector |
| 14 | Providing and Fixing of Stone Ped 300x300x75 |
| 15 | Earthing of poles by earthing rod complete. |
| 16 | Providing and fixing of All type MS Clamp for ST/ PCC poles with nuts bolts made of new MS flat iron 50x6 mm. |
| 17 | Providing and fixing of LT Clamp |
| 18 | Providing and fixing nuts & bolts of various sizes. |
| 19 | Providing and fixing Suspention clamp, Earth wire Clamp, Dead end Clamp, J-hook with clamp |
| 20 | Providing and fixing Piercing connector Diff. size. |
| 21 | Complete work of laying, lifting, Stringing, sagging jumpring & binding of ACSR Weasel Conductor for 11KV/LT Line including complete. |
| 22 | Grouitng of PCC/ ST poles with cement concreting in bolck of 600X600X1500 MM. in ratio 1:4:8 with cement, sand and brick ballast size 1\"\"x1.5\"\" with plinth. |
| 23 | Fixing of LT Distribution Box 3 Phase |
| 24 | Fixing of LT Distribution Box single Phase |
| 25 | Laying of Connecting lead as per respo specification. |
| 26 | Fabrication of Channel angle |
| 27 | Guarding work of Road crossing |
| 28 | Providing and fixing of Tripple Circuit Tail less unit 500 Amp in coming circuit connected with copper bus bar of proper ratting for 630 KVA T//F in the frame made of MS Angle 45x45x5 mm fitted with GI Nut bolts and fixing the same top of plinth/near ground level as per site requirement. |
| 29 | Safely Carriage of 11 KV Fuse Set from ESC SRE to site of work including loading and unloading at both ends. |
| 30 | Safely Carriage of 11 KV TPMO Set from ESC SRE to site of work including loading and unloading at both ends. |
| 31 | Providing & fixing of LT shackle insulator |
| 32 | Safely installation of 11 KV fuse Set |
| 33 | Safely installation of 11 KV TPMO Please Enable Macros to View BoQ information |