| 1 | Taking down carefully the existing aluminium/copper point wiring of any size and capacity and type by disconnecting from the either terminals complete including fittings and fixtures such as switches, sockets, ceiling rose, fanregulators, lamp holders, call bell, bell pushesany type etcby unscrewing and taken away from site, complete and make good the disturbed surface as existing, complete all as specified and directed. |
| 2 | Taking down submain wiring any type and any size and making good disturbed surface by using cement mortar, white cement, putty etc. and match with existing surfaces of walls, floors etc., complete all as specified and as directed. |
| 3 | Taking down sheet metal enclosure DBs, main switch board etc and making good distrubed surface to match with existing surface, complete all as specified and directed. |
| 4 | M & L for point wiring with 1.5 sqmm (Nominal Area) FRLS PVC insulated unsheathed multi stranded copper conductor, 1100 Volts grade, in and including concealed PVC conduit(ISI marked) with accessories such as bends, cross, elbow, tees etc. of suitable sizeincluding concealedMS pressed steel (Modular sunken box) terminal box not less than 1.6 mm thick for mounting switches, sockets, fan regulators etc and Modular cover plate as top cover (ISI marked) including continuous earth wire FRLS PVC insulated unsheathed 1.5 Sqmm (nominal area) copper multistranded conductor, 1100 Volts grade, connecting to common earth and earth dolly complete all as specified for one light point/Exhaust fan point controlled by one switch, complete all as specified and directed. Note : i)Wiring Colour code i.e. Red/Yellow/Bluefor Phase, Black for neutral and Green for earth shall be maintained.ii) Rate of cutting chases, cement plaster, white wash and making surface good as existing surface included in quoted rate.iii) Point wiring is considered for Modular Switches and sockets. Rate of Metallic Sunken box and modular sheet cover plate and other connected accessories required for modular point wiring included in quoted rate.iv) Rate of modular switch and sockets will be paid seperately under relevant item. |
| 5 | All as per item No 4 above but for 3 pin 5 Amp socket outlet on independant board with 1.5 sqmm multi stranded copper conductor 1100 volts grade FRLS PVC insulated sheathed cable with FRLS PVC 2.5 Sqmm multi standard insulated unsheathed copper wire for continuos earth on independent board, complete all as specified and directed. |
| 6 | All as per item No 4 above but for 3 pin 5 Amp socket outlet on same board with 1.5 sqmm multistranded copper conductor 1100 volts grade FRLS PVC insulated sheathed cable with FRLS PVC 2.5 Sqmm multi standard insulated unsheathed copper wire for continuos earth on independent board, complete all as specified and directed. |
| 7 | All as per item No 4 above but for one light point controlled by two way switches, complete all as specified and directed. |
| 8 | All as per item No 4 above butfor 3 pin 15 Amp socket otlet on independant board with 2.5 Sqmm multistranded copper conductor 1100 volts grade FRLS PVC insulated sheathed cable with FRLS PVC 2.5 Sqmm multi standard insulated unsheathed copper wire for continuos earth on independent board, complete all as specified and directed. |
| 9 | M & L for point wiring with 1.5 sqmm (Nominal Area) FRLS PVC insulated unsheathed multi stranded copper conductor, 1100 Volts grade, in and including PVC casing caping(ISI marked) with accessories such as bends, cross, elbow, tees etc. of suitable sizeincluding PVC junction box /MS pressed steel cadmium plated terminal box not less than 1.6 mm thick for mounting switches, sockets, fan regulators etc and 3 mm thick laminated hylam sheet top cover (ISI marked) including continuous earth wire FRLS PVC insulated unsheathed 1.5 Sqmm (nominal area) copper multistranded conductor, 1100 Volts grade, connecting to common earth and earth dolly complete all as specified for one light point/ fan pointcontrolled by one switch, complete all as specified and directed.Note : i) Wiring Colour code i.e. Red/Yellow/Bluefor Phase, Black for neutral and Green for earth shall be maintained.ii) Rate of casing&caping included in quoted rate.iii) Point wiring is considered for Modular Switches and sockets. Rate of Metallic Sunken box and modular sheet cover plate and other connected accessories required for modular point wiring included in quoted rate.iv) Rate of modular switch and sockets will be paid seperately under relevant item. |
| 10 | All as per item No 9 above but for 3 pin 5 amps socket outlet on same board with 1.5 sqmm PVC copper conductor (FRLS) cable and PVC insulated, unsheathed 1.5 sqmm stranded copper conductor cable as continous earth wire, complete all as specified and directed. |
| 11 | All as per item No 8 above but for 3 pin 5 amps socket outlet on independent board with 1.5 sqmm PVC copper conductor (FRLS) cable and PVC insulated, unsheathed 1.5 sqmm stranded copper conductor cable as continous earth wire, complete all as specified and directed. |
| 12 | All as per item No 9 above but for 3 pin 15 amps socket outlet on independent board with 2.5 sqmm PVC copper conductor (FRLS) cable and PVC insulated, unsheathed 2.5 sqmm stranded copper conductor cable as continous earth wire, complete all as specified and directed. |
| 13 | S&F Modular Switchone way 6 Amp, one module 230 Volts, complete all as specified and directed. |
| 14 | S&F Modular Switchone way 16 Amp, one module 230 Volts, complete all as specified and directed. |
| 15 | S&F Modular Switchtwo way 10 Amp, one module 230 Volts, complete all as specified and directed. |
| 16 | S&F Modular socket 6 Amp 3 Pin, two module 230 Volts, complete all as specified and directed. |
| 17 | S&F Modular socket 6/16 Amp 3 Pin, two module 230 Volts, complete all as specified and directed. |
| 18 | Supply and fix Switch piano6 A SP 230 Volts single pole one way, complete all as specified and directed. |
| 19 | Supply and fix Socke outlet flush type 5 pin 6 Amp, complete all as specified and directed. |
| 20 | Supply and fix bell push piano flush type 5 Amp single pole one way, complete all as specified and directed. |
| 21 | S&F Switch piano flush type single pole one way 16 A SP 230 Volts, complete all as specified and directed. |
| 22 | S&F Switch Socket multipurpose 2 in 1, 3/5 pin 6 and 16 Amps flush type, complete all as specified and directed. |
| 23 | S&F Ceiling rose surface type 3 terminals 65x50mm, complete all as specified and directed. |
| 24 | S&F Bell electric, Ding Dong AC 230 Volts, single pole, complete all as specified and directed. |
| 25 | S&F Switch Socket combination 5 in 1, 6 Amps Flush type universal, complete all as specified and directed. |
| 26 | S&F Switch Socket combination piano type 5 in 1, 6 & 16 Amps Flush type universal, complete all as specified and directed. |
| 27 | S&F in box type switch Socket combination 2 in 1, 3 pin, 6 Amps flush type, complete all as specified and directed. |
| 28 | S&F box type Switch Socket combination outlet 2 in 1, 3/5 pin 6 Amps & 16 Amp Flush type, complete all as specified and directed. |
| 29 | Supply and Fixing in repair the sheet metal enclosure with socket plugtop with MCB of a two pin and earth plug and a socket complete with one double pole MCB of 20 Amps rated, complete all as specified and directed. |
| 30 | S & F in repairs 3mm thick backelite sheet (hylam) as sheet cover with PVC Box of size 8\"x10\" for fixing switches, sockets & regulator etc, complete all as specified and directed. |
| 31 | S & F in repairs 3mm thick backelite sheet (hylam) as sheet cover with PVC Box of size 7\"x4\" for fixing switches, sockets & regulator etc, complete all as specified and directed. |
| 32 | S & F in repairs 3mm thick backelite sheet (hylam) as sheet cover with PVC Box of size 4\"x4\" for fixing switches, sockets & regulator etc, complete all as specified and directed. |
| 33 | Supply and fix modular cover plate with frame, 3 module including all As per existing make, complete all as specified and as directed by Engr-in- Charge. |
| 34 | Supply and fix modular cover plate with frame, 4 module including all As per existing make, complete all as specified and as directed by Engr-in- Charge. |
| 35 | Supply and fix modular cover plate with frame, 6 module including all As per existing make, complete all as specified and as directed by Engr-in- Charge. |
| 36 | Supply and fix modular cover plate with frame, 8 module including all As per existing make, complete all as specified and as directed by Engr-in- Charge. |
| 37 | M & L forLED tube light fitting 20 watt, 6000 K, 220 volt, decoarative type complete with driver, holders, and LED tube of 20 watt complete with all accessories internally pre wired battenincluding connecting up with three core twisted flexible copper conductor cable ofsuitable size from ceiling rose to connector of light fitting including mounted on PVC square block, complete all as specified and diercted. |
| 38 | Supply and fixing security light 45 Watt New generation energy saving and environmental friendly long life LED Bldg security light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having Top Opening seperate toughtned glass/verminproof driver compartment, SPDs with IP66 protectionconnecting with PVC insulated three core flexible copper conductor of suitable size from ceiling rose to fitting including bracket of size 32 mm dia length 1.2 mtr along with clamps, complete all as specified and directed by Engr - in - Charge. |
| 39 | Supply and fixing in replacement PVC insulated copper (Flexible) conductor PVC sheathed 3 core 2.50 sqmm universal colour code complete all as specified and directed. |
| 40 | S&F Heat Resistant Flame Retardant HRFR PVC Insulated Industrial Cables,1.5 Sqmm Single Core HRFR PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, in all required colour coding 1100 Volt Conforming to IS 694 incomplete all as specified and directed.Note: (a) Insulation test ofwiring to be carried out on completion of work.(b) Proper colour coding is to bemaintained .(Ph-Red, N-Black,Earth- Green)(c) Cutting chases for sub main wiring concealed PVC rigid conduit shall be deemed to be included in the quoted rate of item |
| 41 | S&F Heat Resistant Flame Retardant HRFR PVC Insulated Industrial Cables,2.5 Sqmm Single Core HRFR PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, in all required colour coding, 1100 Volt Conforming to IS 694 incomplete all as specified and directed. Note: (a) Insulation test ofwiring to be carried out on completion of work.(b) Proper colour coding is to bemaintained .(Ph-Red, N-Black,Earth- Green)(c) Cutting chases for sub main wiring concealed PVC rigid conduit shall be deemed to be included in the quoted rate of item. |
| 42 | M & L for sub main wiring withtwo single core PVC insulated unsheathed, 1100 Volts grade, (FRLS) copper cable 4 sqmm stranded conductor and and drawing through and including rigid PVC non metalic surface casing caping with accessories such as junction boxes, bends, tees etc. including continuous earth wire PVC insulated unsheathed 1100 volts grade,cable 4 sqmm copperconductor and connected to common earth dolly, complete all as specified and directed, including taking down old submain wiring.Note :-(i) One run of PVC conduit, two runs of cable (Phase + Neutral) and one run of earth wire shall be measured and paid as one unit. |
| 43 | M & L for sub main wiring withtwo single core PVC insulated unsheathed, 1100 Volts grade, (FRLS) copper cable 6 sqmm stranded conductor and drawing through and including rigid PVC non metalic conduit 20mm dia 1.8mm thick medium duty (ISI Marked) with conduit accessories such as junction boxes, bends, tees etc. including continuous earth wire PVC insulated unsheathed 1100 volts grade,cable 6 sqmm copperconductor and connected to common earth dolly, complete all as specified and directed, including taking down old submain wiring.Note :-(i) One run of PVC casing caping,two runs of cable (Phase + Neutral) and one run of earth wire shall be measured and paid as one unit. |
| 44 | Supply and fix in repair LED Bulb 12 watt, Cool/warm white 6500k / 3000K, suitable for base B22/ E27, 230 volts, complete all as specified and directed. |
| 45 | M&L for providing the MCB DB of sheet metal enclosure double door type, single pole and neutral 12 way with 200 Amp rated bus bar 240V andgrouted in walls with PCC 1:2:4 type B1 using 20mm graded stone aggregate, complete all as specified and directed. |
| 46 | M&L for providing the MCB DB of sheet metal enclosure double door type, single pole and neutral 8 way with 200 Amp rated bus bar 240V andgrouted in walls with PCC 1:2:4 type B1 using 20mm graded stone aggregate, complete all as specified and directed. |
| 47 | M&L for providing the MCB DB of sheet metal enclosure double door type, single pole and neutral 4 way with 200 Amp rated bus bar 240V andgrouted in walls with PCC 1:2:4 type B1 using 20mm graded stone aggregate, complete all as specified and directed. |
| 48 | S & F MCB, TPN,32 Amp to 63 A capacity, 415 V, 10 KA, C series including taking down old MCB TPN, complete all as specified and directed.Note: The connection to the MCBs shall be done through thimble/ lugs do not direct wire shall be connected to MCBs. |
| 49 | Supply and fix SPN 240V 32 Amps to 40 Amp, 10 KA, C series,including taking down old unsv MCB SPN, complete all as specified and directed.Note : The connection to the MCBs shall be done through thimble/ lugs do not direct wire shall be connected to MCBs. |
| 50 | Supply and fixMCB, SP 5 to 32 Amps, 10 KA, C Series including taking down old unsv MCB SP, complete all as specified and directed.Note : The connection to the MCBs shall be done through thimble/ lugs do not direct wire shall be connected to MCBs. |
| 51 | Supply and fixing in repair MCB Protected socket (Modular AC box) 3 Module with MCB SP ofcapacity 25 Amp and power socket for geyser, complete all as specified and directed by Engr - in - Charge. |
| 52 | Supply and fixing in replacement LED light fitting mirror type with high output diffuser 2 feet ,10 watt, 6000 K, 220 volts, AC decorative type with extruded polycarbonate having efficiency 120 lumens /watt warm white with driver holder including connecting up with three core flexible copper conductor cable of suitable size, complete all as specified and directed. |
| 53 | M & L for earthing complete with galvanised steel earth plate electrode, 600mm x 600mm x 6mm thick, buried directly in theground (earth pit not less than 2.25m deep below normal (ground level) with top edge of the plate not less than 1.50m below ground level connected to galvanised iron strip 25×4mm as earthing lead by means of bolts, nuts and washers of GIup to test point, GI tubing 40mm bore light grade protection pipe, GI watering pipe 20mm bore medium grade with funnel and wire mesh, charcoal and salt, 40mm thick pre-cast RCC (1:2:4) type B-0 (Nominal mix) cover reinforced with XPM (weighing n.less than 4 Kg/Sqm) with suitable steel handle, and angle iron 40X40X3mm frame and chamber of PCC (1:3:6) type C-0 (including earth work in any type of soil, removal of surplus soil to a distance n.exc.50m) and connecting, testing on completion, all as shown on electric plate No. 03 of SSR-2009 Part-I, complete all as directed.Notes: 1.Earth Strip & protection pipes length upto & including 7.50 metre is included in the quoted rate.2.Soil should be free from stone, boulders, aggregate, gravels etc. |
| 54 | M&L for PVC casing & caping of size (20x12) mm ISI marked suitable for electrical wiring, complete all as specified and directed. |
| 55 | M&L for PVC casing & caping of size (26x16) mm ISI marked suitable for electrical wiring, complete all as specified and directed. |
| 56 | Supply and fix high speed fan step regulator, stepped type, complete all as specified and directed by Engr-in- Charge. |
| 57 | Taking down ceiling fan of 1200mm sweep, any make from existing position of any height by disconnecting electrical connections and removing of old burnt winding wiring any type, cleaning stator complete for burnt wiring, carbon residue and rewinding of stator winding ofceiling fan of 1200mm sweep with superior quality super enameled winding copper wire of existing specification, gauge and weight with superior quality insulation for satisfactory functioning fan in presence of JE incharge complete all as required at site and directed by Engr - in - Charge. |
| 58 | M&L for painting one coat of synthetic enamel paint (white) using spray machine painting on the surface of ceiling fan of 1200mm sweep (including blade) complete after preparation of surface i.ecleaning, washing of surfaces filling cavities with filler, cleaning dust and writing MES No., complete all as specified and directed by Engr-in-Charge. |
| 59 | Supply and fixing ball bearing of existing number suitable for ceiling fan 1200mm sweep of approved makes including necessary greasing, complete all as specified and directed.Make : NBC/ SKF/FAG |
| 60 | Supply and fixing blade of 1200mm sweep of ceiling fan, complete all as specified and directed. |
| 61 | Supply and fixing top and bottom canopy of plastic with steel screw suitable for rod for fan of 1200/ 1400mm sweep, complete all as specified and directed. |
| 62 | Supply and fixing down rod 15mm bore, 300mm long fixed one end with mild steel U clamp, nut, lockable bolt, rubber reel, lock pin and other end having threaded/ drilled hole end, suitable nut, bolt, split pin and check nut or aluminium clamp duly white painted suitable for all size and makes of ceiling fan, complete all as specified and directed. |
| 63 | Hanging only ceiling fan of any make/size, checking serviceability of safety pins, clamps, rubber bushes, nut bolts, canopy and electric connections including provision of three core twisted flexible copper conductor cable of suitable size from ceiling rose to fan, complete all as specified and as directed by Enge-In-Charge. |
| 64 | Dismantling exhaust fan 300mm/600mm sweep, removing of old burnt winding wiring and rewinding of the same with super super enameled winding copper wire of existing specification, gauge and weight with superior quality insulation for satisfactory functioning fan in presence of JE incharge, complete all as directed by Engr-in-Charge. |
| 65 | Supply and fixing blades for metal body exhuast fan upto 300mm/600mm sweep including removing existing blades, complete all as specified and directed. |
| 66 | Supply and fixing of motor of plastic body exhaust fan of 200/250mm sweep as per existing sample, complete all as specified and directed by Engr-in-Charge. |
| 67 | Fixing only exhaust fan of any make/size, checking serviceability nuts, bolts and electric connections including provision of three core twisted flexible copper conductor cable of suitable size from ceiling rose to fan, complete all as specified and as directed by Enge-In-Charge. |
| 68 | Supply and fing in replacement of condenser 2.5 mfd including necessary connection, complete all as specified and directed. MAKE- USHA/Havells/Epcos/BAJAJ |
| 69 | Supply and replacement of heating elements 1.5KW/2.0KW/3.0KWISI marked triangular base/square base suitable for water heater of any type including connection with suitable cable, complete all as specified and directed by Engineer-in-Charge. Make:-Theeta/Racold/Airex |
| 70 | S&F in repair for thermostat switch and capillary thermostat switch (as per sample exist on ground of make recold/venus geyser) of geyser 230V, (adjustable range bewteen 0 degree to 90 degree centigrade temp range), ISI marked as per existing thermostat suitable for hot water storage heater of 15/ 25/ 35 / 50 Litre capacity, complete all as specified and as directed. |
| 71 | Supply and fix Plug top 3 Pin type of rating 16 Amp, 230 volts, complete all as specified and directed. |