| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 2 | Group C |
| 3 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 4 | 12 way Doubledoor |
| 5 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 6 | 4 way (4 + 12), Double door |
| 7 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 8 | Single pole |
| 9 | Single pole and neutral |
| 10 | Triple pole and neutral |
| 11 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 12 | 2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 13 | 4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire |
| 14 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 15 | Supplying and fixing 12 module GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 16 | Supplying and fixing 5/6 A modular switch on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 17 | Supplying and fixing 3 pin 5/6 A modular socket outlet on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 18 | Supplying and fixing 15/16 A modular switch on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 19 | Supplying and fixing 6 pin 15/16 A modular socket outlet on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 20 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 21 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A \"C\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket outlet and complete with connections, testing and commissioning etc. as required |
| 22 | LED Streetlight fixture, powdercoatedpressurediecastaluminiumbody (System lumen efficacy≥105 <120 lm/Watt) Supplying,installation,Testing&CommissioningofStreetlightLEDfixture powdercoatedpressurediecastaluminiumbody withdriver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5KVL,N,EasperIEC61000-4-5, Driverefficiency >85%,THD< 10%asperIEC 61000-3-2,P. F.≥0.95,IP-66,IK-10,CRI>70, undervoltageandovervoltageprotection,EMIEMCAsper CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry)ofminimum 50000BurningHourswith70%ofinitial Lumenmaintained tilllife ends as per LM80 extrapolation IES TM-21-11 report,CCT 3000°K / 4000°K / 5700°K/6500°K(Asper ANSIBin),SDCM (Standard Deviation Colour Matching) <5,Maximumpowerconsumption should not more than the specified rating and Fixture shall be of relevant BIS standardcomplete inallrespecti/cexternal connectionswith1.5sq.mmFRLS/HFFR,PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120lm/Watt output .LM79 & LM80 Test report andalltestingrequiredforLED fixtures as per BISshall be submitted.Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermalmanagement:heatsinkof aluminiumhousing such that LED junction temperature shall not rise above 90°C).(72W) |
| 23 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%,suitable for operation withregulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019fani/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor singlecorecableandearthingetc.asrequired. |
| 24 | 1200mm,service value≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 25 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt).Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body materialand construction as per IS : 10322 withdriver (Replaceable)as per the requirement with Driver efficiency >85%, Operating voltage AC 140270 Volt,frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20,CRI>80, Flicker free, (flickershould be below 5 %), life time (LED, Driver & electrical circuitry), ofminimum 50000BurningHourswith70%ofinitial Lumenmaintained tilllifeends, CCT3000°K/ 4000°K / 5700°K/6500°K(AsperANSIBin), SDCM(Standard DeviationColour Matching) <3,Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BISstandard.Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete inallrespecti/c external connectionswith1.5sqmm FRLS/HFFR,PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy≥105 <120lm/Watt output . LM79 & LM80 Test report andalltestingrequiredforLED fixtures as per BISshall be submitted.Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermalmanagement:heatsinkofaluminiumhousing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminiumBody (Thickness > 1.20 mm) |
| 26 | 40 watt |
| 27 | LED Panellight 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt) ) Supplying, installation, Testing & Commissioning of Panellight 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirementwith Driver efficiency >85%, Operating voltage AC140-270 Volt,frequency50/60hz,Operatingtemprange-50Cto40 0C,internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95,IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free,(flicker should be below 5 %), life time (LED, Driver & electrical circuitry),of minimum50000 Burning Hours with , 70% of initial Lumenmaintained tilllife ends ,CCT 3000°K /4000°K /5700°K /6500°K(As perANSI Bin), SDCM(Standard Deviation Colour Matching) <3,Maximumpower consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete inallrespecti/c external connectionswith1.5sq.mm FRLS/HFFR, PVC insulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy>135lm/Watt output . LM79 & LM80 Test report andalltestingrequiredforLED fixtures as per BISshall be submitted. Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management:heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powdercoateddiecast/Extruded aluminiumBody (Thickness > 1.20 mm) |
| 28 | 40 watt |
| 29 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies,shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion)less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperaturerise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR,PVC insulated copper conductor single core cable and earthing etc. as required |
| 30 | 1200mm, service value ≥ 6.0 CM/Min/Watt, airdelivery 210 CM/Min (Minimum |
| 31 | Supplying , installation, testing and commissioning of 35 Watt LED 5700K Post top Lanthern made up of pressure die cast aluminium housing of new generation, energy saving, environmental friendly, long life astheticatly design symmetrical light distribution spun aluminium landscape luminaire with high power LEDs as light source with IP 65,IK 07, avg life- 50000 hours with lumen efficacy of >140 lm/W, System efficacy of > 70 lm/W,colour temp 5700 K,THD( %) < 10 and fixing on pole with suitable clamps and nut bolts including giving connection testing etcat site of required |
| 32 | Automatic Power Factor Correction (APFC) System Supply, Installation, testing and commissioning of Automatic Power Factor Correction (APFC) panel, indoor type floor mounted free standing totally enclosed, extendable, IP 42, of following capacity for 3 phase, 415 V + 10 %, 50 Hz AC System for Ambient temperature -5°C to +40°C, fabricated in compartmentalised designed made of CRCA sheet steel of 2.0mm thick for framework & covers, 3 mm thick for gland plate i/c cleaning & finishing completewith 9 tank process for powder coated of approved shade ( RAL 7032-Siemens Gray or as approved by Engineer-in-Charge), having front section (switch gear and control accessories) and rear section capacitorand reactor, front and rear access, having suitable current carrying capacity, extensible TPN Aluminium alloy bus bar of high conductivity, DMC/SMC bus bar supports, bottom base channel of MS Section, fabrication shall be done in transportable section, entire panel shall have common copper earth bar ofminimum size of 25mm x 5mm with 2 nos. earth studs, the earth terminals provided on the body of capacitor bank shall also be bonded to the maincapacitor panel earth bus with 2 nos. 8 SWG or 6 SWG GI earth wires/ equivalent size of copper conductor cable, forced ventilation for maintainingtemperature rise not more than 5°C from ambient, interconnections, connections with 14% detuned reactor and heavy duty 525 V ISI marked Impregnated MPP(Metalized Polypropylene) Capacitor (IS 13340Part -1 & 2) APFC Panel shall be in compliance with IS :16636 & CPWD Specifications etc. as per below details. (50KVAR) |
| 33 | (A) IncomersSuitable capacity MCCB Microprocessor base withO/C, S/C, E/L release of TPN 50KA breaking capacity(Ics=Icu), ON, OFF, Trip, R, Y, B - LED IndicatingLamp set along with required Instruments andaccessories with extended rotary handle and doorinterlocking arrangement. Current rating of the Incomer in ampere shall be APFC Panel rating in KVAR x 1.4 x 1.5 or Nearest higher standards rating. |
| 34 | (B) Instruments & Indicationsi) 3-Phase current sensing APFC microprocessorrelay/controller , advance 8/12 stages (8 stages forcapacity below 100 KVAR and 12 stages 100 KVAR &above) with Communication Ethernet/RS485/SNMPport open protocol for BMS integration as perapproved by Engineering in charge and havingdisplay of Phase wise V, A, PF, Cos-Phi, Kw, KVA,KVAR, THD-V , THD-I, harmonics up to 31 level. 3nos of dual core CT\"s accuracy class 1, 15VA atincomer of PCC Panel for APFC relay. ii) Auto Manual Selector switch, auxiliary contactorswith timer for delay in manual mode.iii) Digital Multi function meter with LED Display for V,A, PF, KW, KVA, KVAR, THD-V & I, Frequency.iv) Suitable rating control transformer shall be providedfor control and indication circuit.v) All components like control transformer, meter, relayand indicating lamp shall be protected by usingsuitable rating individual MCB\"s.vi) Wiring of the control circuit shall be done by using2.5 sq mm, FRLS/HFFR 1100 V grade, PVC insulatedmulti stranded copper control wire. |
| 35 | C) Bus Bars 1.3 Amp per Sq.mm,TPN, Electrolyticgrade Aluminium bus bar of capacity 1.25 times ofincomer rating as per CPWD specification. |
| 36 | (D) Outgoings (APFC Section) Selection of thecapacitors combinations shall be for continuousrating and each capacitor bank shall have suitablecapacity Heavy Duty ISI Marked Capacitor, capacitorduty contactor,the capacitor shall be mounted onchannel with base of perforated M S Powder coatedsheet, connections inter connections etc. and otherfeatures as per CPWD Specifications and relevant ISCode having following: i) Capacitor bank ratings & stages shall be as per thetechnical specifications sheet of NIT. |
| 37 | (ii) Capacitor will be MPP self healing type withdischarge resistor, pressure release mechanism.(iii) Since Capacitor Voltage is 525 Volts, thus higherKVAR has to be considered to get rated output at 415Volts.iv) 14% Detuned Reactor of class H insulation &150% linearity in series with Capacitor.(Note: Technical specifications sheet for selection ofthe capacitors combinations shall be provided by theNIT Approving Authority with due consideration ofnumber of capacitors i.e. 1 KVAR, 2 KVAR, 3 KVAR, 5KVAR, 10 KVAR.....for smooth correction). |
| 38 | Credit Items |
| 39 | Dismantled Metal scrap |