| 1 | S&F in repair Automatic Transfer Switch (ATS), 630 Amp, 4 Pole with controller, 415 V, 50 Hz, Open Execution, complete all as specified and as directed.Make: Havells Cat No. IHYFCDO630 or equivalent in ABB/ Siemens/ Schneider/ C&S/ Legrand/ Lauritz Knudsen Electrical & Automation (Formerly L&T). |
| 2 | S&F in repair Automatic Transfer Switch (ATS), 400 Amp, 4 Pole with controller, 415 V, 50 Hz, Open Execution, complete all as specified and as directed.Make: Havells Cat No. IHYFCDO400 or equivalent in ABB/ Siemens/ Schneider/ C&S/ Legrand/ Lauritz Knudsen Electrical & Automation (Formerly L&T). |
| 3 | S&F in repair Automatic Transfer Switch (ATS), 315 Amp, 4 Pole with controller, 415 V, 50 Hz, Open Execution, complete all as specified and as directed.Make: Havells Cat No. IHYFCDO315 or equivalent in ABB/ Siemens/ Schneider/ C&S/ Legrand/ Lauritz Knudsen Electrical & Automation (Formerly L&T). |
| 4 | S&F in repair Automatic Transfer Switch (ATS), 200 Amp, 4 Pole with controller, 415 V, 50 Hz, Open Execution, complete all as specified and as directed.Make: Havells Cat No. IHYFCDO200 or equivalent in ABB/ Siemens/ Schneider/ C&S/ Legrand/ Lauritz Knudsen Electrical & Automation (Formerly L&T). |
| 5 | S&F in repair Automatic Transfer Switch (ATS), 125 Amp, 4 Pole with controller, 415 V, 50 Hz, Open Execution, complete all as specified and as directed.Make: Havells Cat No. IHYFCDO125 or equivalent in ABB/ Siemens/ Schneider/ C&S/ Legrand/ Lauritz Knudsen Electrical & Automation (Formerly L&T). |
| 6 | S&F in repair MCCB with thermal magnetic protection unit rating 400 Amp, 4 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items andtaking down old item complete all as specified and as directed. Make: Legrand Cat Part No. 4220 07 or equivalent in makes mentioned in Appendix \"B\" here-in-after. |
| 7 | S&F in repair MCCB with thermal magnetic protection unit rating 250 Amp, 4 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items andtaking down old item complete all as specified and as directed. Make: Legrand Cat Part No. 4202 49 or equivalent in makes mentioned in Appendix \"B\" here-in-after. |
| 8 | S&F in repair MCCB with thermal magnetic protection unit rating 160 Amp, 4 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items andtaking down old item complete all as specified and as directed. Make: Legrand Cat Part No. 4200 97 or equivalent in makes mentioned in Appendix \"B\" here-in-after. |
| 9 | S&F in repair MCCB with thermal magnetic protection unit rating 100 Amp, 4 Pole, 16 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items andtaking down old item complete all as specified and as directed. Make: Legrand Cat Part No. 4200 15 or equivalent in makes mentioned in Appendix \"B\" here-in-after. |
| 10 | S&F in repairs MCB TPN 63 Amp, 415 V, 50 Hz, AC supply, 10kA, \"C\" Curve, complete all as specified and as directed. Make: Legrand Cat No. 4086 83 or equivalent in makes mentioned in Appendix \"B\" here-in-after. |
| 11 | S&F in repairs MCB SPN 32 Amp, 240 V, 50 Hz, AC supply, 10 kA, \"C\" Curve, complete all as specified and as directed.Make: Legrand Cat No. 4086 17 or equivalent in makes mentioned in Appendix \"B\" here-in-after. |
| 12 | S&F in repairs MCB SPN 40 to 63 Amp, 240 V, 50 Hz, AC supply, 10 kA, \"C\" Curve, complete all as specified and as directed. Make: Legrand Cat No. 4086 18 to 4086 20 or equivalent in makes mentioned in Appendix \"B\" here-in-after. |
| 13 | M&L for Earthing with & including galvanised mild steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than2.25 m below normal ground level) with top edge of the earth plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to & including galvanized mild steel strip 32x6 mm as earth lead, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted/welded to earth plate at one end and other end of strip connected to Panel / transformer / GOD / equipment body / test point with two Nos nuts bolts or welding with steel structure, GI earth strip encased in and including 40mm bore GI light grade pipe with all fittings from upper edges of earth plate upto 7.5 metre above ground level fixed with and including 25x3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from earth pit to top of electrode and including funnel, wire mesh, copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate and 40mm thick RCC (1:2:4 type B1) cover reinforced with 8 mm dia TMT bars reinforced at 100 mm C/C both ways and handle of 6 mm dia MS bar made to shape complete all as specified and shown in electrical plate No 3 of SSR Part-I including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exc 50m complete all as specified and as directed including dismantling & taking out old existing unserviceable earthing. |
| 14 | M&L for galvanised iron strip 32 x 6mm earth continuity conductor or main earthing lead buried in ground / fixed on wall/ Pole including taking out existing GI strip complete all as specified and as directed. |
| 15 | S&F in repair 3 Pole Power Contactor, 40 Amp AC3 rating, 2 NO + 2 NC, including necessary connections for incoming and outgoing complete all as directed.Make : L&T ‘Type ML 3’ Cat No. SS90721 or equivalent in makes mentioned in Appendix \"B\" here-in-after. |
| 16 | S&F in repair Pole assembly for ATS of 200 Amp capacity, 4 Pole, as per existing make, including testing on completion, complete all as specified & as directed. |
| 17 | S&F in repair Pole assembly for ATS of 315 Amp capacity, 4 Pole, as per existing make, including testing on completion, complete all as specified & as directed. |
| 18 | S&F in repair Pole assembly for ATS of 400 Amp capacity, 4 Pole, as per existing make, including testing on completion, complete all as specified & as directed. |
| 19 | S&F in repair Pole assembly for ATS of 630 Amp capacity, 4 Pole, as per existing make, including testing on completion, complete all as specified & as directed.Note for Srl Item No. 16 to 19 : Fixing rate of the spares including testing is deemed to be inclusive in quoted rate of this item. Unit rate quoted by the tenderer shall be deemed to include for minor spares/ extras. The decision of Accepting Officer regarding minor spares/ extras shall be final, conclusive and binding. |