| 1 | BOQ Dated Dec 2025 |
| 2 | GENERAL SUMMARY NOTE: Schedule ‘A’ Part I to X are prepriced by MES under Ser No. 1 to 10. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only. |
| 3 | Lumpsum price worked out by the contractor for “Building or Works” as listed in Schedule ‘A’Part–I |
| 4 | Lumpsum price worked out by the contractor for “Internal Water Supply” as listed in Schedule ‘A’Part–II |
| 5 | Lumpsum price worked out by the contractor for “Internal Electric Supply\" as listed in Schedule ‘A’Part–III |
| 6 | Lumpsum price worked out by the contractor for “Road / Path\" as listed in Schedule ‘A’ Part - IV . |
| 7 | Lumpsum price worked out by the contractor for \"Area Drainage\" as listed in Schedule ‘A’ Part - V . |
| 8 | Lumpsum price worked out by the contractor for “Sewage Disposal” as listed in Schedule ‘A’ Part – VI. |
| 9 | Lumpsum price worked out by the contractor for “External Water Supply” as listed in Schedule ‘A’ Part – VII |
| 10 | Lumpsum price worked out by the contractor for “External Electric Supply” as listed in Schedule ‘A’ Part –VIII |
| 11 | Lumpsum price worked out by the contractor for \"Lightning Protection” as listed in Schedule ‘A’ Part – IX |
| 12 | Lumpsum price worked out by the contractor for \"Air Conditioning” as listed in Schedule ‘A’ Part – X |
| 13 | Sch \"A\" Part - XI : BUILDINGS OR WORKSDesign and Construction of MI Room building (Double storey)in RCC M-30(Design Mix) framed construction with permanent specifications, PCC block masonry walls, ATT, PU based WPT, UPVC windows, earthquake resistance as per latest IS etc complete all as specified and as shown on drawings. |
| 14 | Design and Construction of Logistic section building (Triple storey)in RCC M-30(Design Mix) framed construction with permanent specifications, PCC block masonry walls, ATT, PU based WPT, UPVC windows, earthquake resistance as per latest IS etc complete all as specified and as shown on drawings. |
| 15 | Design and Construction of Security section building (Triple storey)in RCC M-30(Design Mix) framed construction with permanent specifications, PCC block masonry walls, ATT, PU based WPT, UPVC windows, earthquake resistance as per latest IS etc complete all as specified and as shown on drawings. |
| 16 | Design and Construction of Fire station building (Double storey)in RCC M-30(Design Mix) framed construction with permanent specifications, PCC block masonry walls, ATT, PU based WPT, UPVC windows, earthquake resistance as per latest IS etc complete all as specified and as shown on drawings. |
| 17 | Design and Construction of Repair bay for fire domestic tender building (Single storey)in RCC M-30(Design Mix) framed construction with permanent specifications, PCC block masonry walls, ATT, PU based WPT, UPVC windows, earthquake resistance as per latest IS etc complete all as specified and as shown on drawings. |
| 18 | Design and Construction of Desk NCO room for fire domestic tender building (Single storey)in RCC M-30(Design Mix) framed construction with permanent specifications, PCC block masonry walls, ATT, PU based WPT, UPVC windows, earthquake resistance as per latest IS etc complete all as specified and as shown on drawings. |
| 19 | SCHEDULE \"A\" Part- XII (FITTINGS AND FIXTURES & MISC ITEMS) |
| 20 | INTERNAL ELECTRIC SUPPLY Supply and fix LED batten tubelight with integral LED driver, plastic batten of 20watts capacity including necessary electric connections 3 core 1 sqmm insulated copper wire from ceiling rose to tube light fitting complete all as specified and as directed. |
| 21 | Supply and fix recessed mounted 2 x 2 square LED panel light 36watts, ultra modern recess mounting luminaire with high performance LEDs suitable for mounting with Armstrong / Grid ceiling complete all as specified and as directed. |
| 22 | Supply and fix decorative wall mounting, gold finish fixture with cognac hammered glass diffuser suitable for 9W LED filament lamp E27 base including suitable lamp complete all as specified and as directed. |
| 23 | Supply and fix 30Watts LED new generation energy saving and enevironment friendly long life LED building light made up of pressure die cast aluminium housing with high efficiency LED as lighting source and lens embedded PC cover having bottom opening seperate drivwe compartment with IP 66 protection and impact resistance of IK08 complete all as specified and as directed. |
| 24 | Supply and fix Exhaust Fan of 250 mm sweep made of PVC body with blades and frame and louvers shutter including 3 core 1.5sqmm copper conductor cable from ceiling rose to exhaust fan AC single phase, voltage 230V, 50 Hz. RPM 1200, Copper winding including writing MES NO. 2 CM height with synthetic enamel black paint etc complete in all respect etc complete all as specified and as directed. |
| 25 | Supply and fix Modular TV Socket, one module etc complete all as specified and as directed. |
| 26 | Supply and fix Modular Telephone socket, RJ-11, one module etc complete all as specified and as directed. |
| 27 | Material and labour for Telephone Wiring with unarmoured Solid annealed bare copper industrial cablein concealed of size 0.5 mm, 3 pair with PVC Conduit 25 mm diaetc complete all as specified and as directed. |
| 28 | Material and labour for TV Wiring with unarmoured coaxial cable, RG-11in concealedwith PVC Conduit 25 mm diaetc complete all as specified and as directed. |
| 29 | Material and labour for Mild steel Box for Telephone wiring including blocks, Suitable for 30 Pair etc complete in all respect all as specified and as directed. |
| 30 | Supply and fix MCB DB VTPN 4 ways with metal double door, IP 43 protection suitable for FP MCB as incommer and MCB as outgoing, 415 volt 3 phase with appropriate size copper bus bar and neutral link as required at site including cutting chases to wall for fixing of DB and making good disturbed wall / surface complete all as specified and as directed. |
| 31 | EXTERNAL WATER SUPPLYConstruction of Masonry valve chamber 1500mm x 1500mm x 750mmincluding excavation and earth work in any type of soil and 100 mm thick PCC 1:4:8 type D2 foundation, brick work in CM (1:6), plastering internal surface 15 mm tick in CM (1:4), PCC (1:3:6) type C1 coping 50mm x50mmx6 mm angle iron, 6 mm thick MS plate cover complete with locking arrangement, painting steel and iron surface with two coat of synthetic enamel paint over a coat of zinc chrome primer all as specified and as directed. |
| 32 | Supply & laying centrifugalcast (Spun) Ductile Iron Pressure Pipe 100mm dia with Spigot & Socket end, Class K-9 conforming to IS : 8329/2000 (latest revision) complete all as specified and as directed. |
| 33 | EXTERNAL ELECTRIC SUPPLYSupply, installation, testing & commissioning of HT 11 KV 3 Phase, rated voltage 12 Kv, 630A, 21kA/3sec, 50 Hz Outdoor type, extensible type, floor mounted with copper bus bars, SF6 gas Insulated, completely Manual operated, 1 Way consisting of 1 NoSwitch fuse unit and earth fault protection Relay with 250MVA rupturing capacity totally enclosed metal clad switchgear. The unit shall have front cable entry (Suitable for termination of 1R x 3C x 95 Sqmm Cable ). The unit shouldbe complete with all accessories such as Terminal boots, mechanical indications for Load break switch ON/OFF, Manometer etc including foundation as per OEM all as specified. Note: Contractor shall submit the detailed OEM drawing for approval of Engr-in-Charge. |
| 34 | Supply, installation, testing & commissioning of HT 11 KV 3 Phase, rated voltage 12 Kv, 630A, 21kA/3sec, 50 Hz Outdoor type, extensible type, floor mounted with internal copper bus bars, SF6 gas Insulated, completely Manual operated, 2 Way RMU consisting of 1 NoLoad Break Switch as Incomer & 1 No 630A VCB as Outgoing for Transformer withOverload and earth fault protection Relay with 250 MVA rupturing capacity. The unit shall have front cable entry (Suitable for termination of 1R x 3C x 95 Sqmm Cable ). RMU shouldbe complete with all accessories such as Terminal boots, mechanical indications for Load break switch ON/OFF, Manometer etc including foundation as per OEM all as specified.Note: Contractor shall submit the detailed OEM drawing for approval of Engr-in-Charge. |
| 35 | Supply, installation, testing and commissioning of Silent DG set 30 KVA, 3 phase 4 wire , 415 volts , 1500 RPM, 50 Hz power supply with power factor 0.8, coupled directly to alternator mounted on a common base frame plate complete with integral acoustic enclosure having silent features to withstand all weather conditions and for outdoor application with AMF Panel. The design of the DG set shall confirm the CPCB IV+ norm/ regulation with fuel tank, battery and standard accessories, PCC foundation siutable to mount DG set as per size recommended by OEM and the height of the plinth shall be 45cm above the ground level all as specified and directed with the following specifications. Note: Contractor shall submit the detailed OEM drawing for approval of Engr-in-Charge. |
| 36 | (a) ENGINE: Diesel engine of suitable capacity to match the 30 KVA alternator under NTP conditions with provision of 10% overload for 1 hour in every 12 hours running. The engine shall consist of following: (i) Fly wheel (ii) Radiator, Air to Air after cooler, pusher fan & fan drive arrangement. (iii) Dry type air cleaner with restriction indicator (iv) Fuel injection system (v) Radiator fan (blower type) with guard (vi) Gear driven water pump (vii) Fuel filter (viii) 12 V DC electrical starting system (ix) Exhaust silencer heavy duty residential type (x) First fill of lubricating oil (xi) Sensors for oil pressure, coolant temperature & level.(b) Control panel: The control panel with microprocessor based DG Set controller for engine and alternator parameter in one console including complete internal wiring and shall confirm dust proof & vemin proof. The control panel consists of the following parts: (a) Auto start control module with Auto Mains Failure control module as per latest version. (b) MCCB of adequate rating. (c) Indiacting lamps for DG ON, Mains ON, Load on DG, Load on Mains etc.(d) Key switch (e) Set of current transformers and MCBs (f) Controller shall monitor and display the engine speed, oil pressure, coolant temperature, frequency, voltage, current, power factor and fuel level, battery voltage and modules for comprehensive engine and alternator protection, display the array of warning, electrical trip and shutdown alarm. The controller shall provide a record of most recent fault conditions. Fault history stored in the control non volatile memory. (g) Emergency stop : Annuciated whenever an emergency stop signal is received.(c) Alternator: Alternator self excited, self regulated brushless single bearing alternator 415 Volts +/- 2.5% AC 3 Phase 4 wire 50 Hz coupled to engine with consisting of following parameters. (i) Type : Self excited self regulated with automatic voltage regulator (ii) Rating 30 KVA at 0.8 PF lagging. (iii) Speed : 1500 RPM (iv) Connection: Star conenction (v) Ventilation: Self Ventilated. (vi) Insulation: Class \"H\" (d) AMF Panel : The AMF Panel outdoor type suitable for 30 KVA DG set factory fabricated, floor mounted, front operated, totally enclosed dust and vermin proof with suitable Incomer and Outgoing MCCBs 4 pole type, CTs, Indicating lamps LED(RYB) for Incoming/Outgoing, Illuminating push buttons with elements LED type with NO/NC, Digital MFM3 phase 415 V AC - 01 Each, battery charger of suitable capacity, AMF controller 12V DC - 01 Each, Aux relay/coil voltage of suitable capacity complete. |
| 37 | Note:- The cost of PCC platform as recommended by the OEM and the expenses for cost of testing of DG Sets shall deemed to be inclusive of quoted rate. Make: KirloskarGreen/ Jackson / Powerica / Greaves Cotton or any other make specified in particular specifications |
| 38 | Supply, installation, commissioning and testing of LT Feeder Pillar Box outdoor, double door type made out of CRCA Sheet of 3.15 mm thick with powder coated painting framesuitable size for fixing the I/C & O/G MCCB mentioned below made out of angle iron 45 x 45 x 6 mm and four numbers of 300 Amps aluminum strips / bars duly insulated on insulators - 4 Nos / suitable size Bakelite sheet, free space between MCCBs / busbar and other connection items should be provided, the space between ground to panel should be 60 cm with PCC foundation for LT Panel as required, LT panel should be provided with necessary locking arrangement, danger notice sticker, cable glands, internal wiring with FRLS copper wires of suitable size and comprising and including the following: Note: Contractor shall submit the detailed OEM drawing for approval of Engr-in-Charge. |
| 39 | (A) Main Incoming(i) MCCB conforming TPN (4 pole), 200 Amps, 415 volts, 50 Hz, rupturing capacity 36 KA - 01 No.(ii) LED Multifunctional Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (iii)LED indicating lamps with colour Red, Yellow, Blue (03 Lights) - 01 Set(iv) 5 Step APFC Relay with ultra hevay duty capacitor of rating 20 kVAR-01 No., 05 kVAR-03 Nos along with necesaary harmonic filters, Duty Contactors, control switch gears etc - 1 Set(B) Main Outgoing(i) MCCB TPN (4 pole), 100 Amps, 415 volts, 50 Hz, rupturing capacity 25 KA - 03 Nos.(ii) MCCB TPN (4 pole), 63 Amps, 415 volts, 50 Hz, rupturing capacity 25 KA - 01 No. (iii) MCCB TPN (4 pole), 40 Amps, 415 volts, 50 Hz, rupturing capacity 25 KA - 02 Nos. (iv) MCB TPN 6-32 Amps, 10 kA, C Curve - 02 Nos (v)Street light timer with contacts 3 Ph - 01 Nos (Digital) |
| 40 | Supply, installation, commissioning and testing of LT Feeder Pillar Box out door, double door type made out of CRCA Sheet of 3.15 mm thick with powder coated painting frame suitable size for fixing the I/C & O/G MCCBs mentioned below made out of angle iron 45 x 45 x 6 mm and four numbers of 200 Amps aluminum strips / bars duly insulated on insulators - 4 Nos / suitable size Bakelite sheet, free space between MCCBs / busbar and other connection items should be provided, the space between ground to panel should be 60 cm with PCC foundation for LT Panel, LT panel should be provided with necessary locking arrangement, danger notice sticker, cable glands, internal wiring with FRLS copper wires of suitable size and comprising and including the following:- Note: Contractor shall submit the detailed OEM drawing for approval of Engr-in-Charge. |
| 41 | (A) Main Incoming(i) MCCB TPN (4 pole), 100 Amps, 415 volts, 50 Hz, rupturing capacity 25 KA - 01 No.(iii) LED Multifucntional Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (iv)LED indicating lamps with colour Red, Yellow, Blue, Mains On, Standby On (05 Lights) - 01 Set(B) Main Outgoing(i) MCCB TPN (4 pole), 63 Amps, 415 volts, 50 Hz, rupturing capacity 16 KA - 01 No. (ii) MCB FP 32 Amps, 16 kA, C Curve - 01 Nos |
| 42 | Supply and fix smart intergrated all in one solar street light of 24 Watt, 5700 K with High efficiency Mono crystalline solar PV Module, Lithium Ferro Phosphate battery with in build BMS technology, High Efficacy LED, MPPT solar charge controller and Aluminium Extruded body & is specially programmed to automatically control the dimming and brightness of light, which increases the backup time complete all as specified and as directed. |
| 43 | M&L for Hot dip galvanized Octagonal pole of 5 mtr height of bottom size 130 mm and top 70 mm dia with base plate size 220 x 220x12 mm, foundation bolts, Hot dip galvanized, single Arm suitable for fixing of All in one Solar Street light fitting of 24 Watt including necessary clamps, nuts, bolts and earth work, foundation suitable for wind pressure of 100 Km/Hour complete all as specified and as directed. Note: Technical drawing for pole and installation shall be submitted for prior apporval of Engr-in-Charge. |
| 44 | Supply and fix street light brackets made of 25 mm dia G.I. Pipe light grade in shape and including suitable size of reducer to fix the LED street light of capacity 45W and angle as directed not exceeding 1.5 mtrs in length fixed to pole with suitable size of M.S. flat iron clamps, 2 Nos, M.S nut & bolt with cup washers including dismantling old rusted/unserviceable bracket withits rusted clamps and nut bolts complete all as specified and as directed. |
| 45 | Supply and fix loop in-out junction box with non mettalic FRP junction box suitable of size (Appx 350 x 250 x 150) with connector 4 way and including one MCB SP 6 A, 230V alongwith 2 Nos \"C\" Clamps and back clamp made up of 20x3 flat iron and fixing on pole with necessary nuts bolts, washers, 2 Nos PVC cable glands of size not exc 4 core 25 sqmm, Cable lugs as required complete all as specified and as directed. |
| 46 | AIR CONDITIONINGSupply and install 1.5 Ton inverter type hi wall split units indoor and outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with 5 star rating and EER 5.2 and Outdoor condenser coilmade of Copper, outdoor fixed on wall/chajjafirmly byusing set ofbrackets, bolts, nuts washers etc. Including making of hole for liquid, discharge copper pipes anddrain pipe. Liquid copper pipe line and dischagecopper pipe line should be firmly insulated complete all as specified and as directed. |
| 47 | Supply and install 2 Ton inverter type hi wall split units indoor and outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with 5 star rating and EER 5.2 and Outdoor condesor coilmade of Copper, outdoor fixed on wall/chajjafirmly byusing set ofbrackets, bolts, nuts washers etc. Including making of hole for liquid, discharge copper pipes anddrain pipe making good as existing. Liquid copper pipe line and dischagecopper pipe line should be firmly insulated complete all as specified and as directed. |
| 48 | Supply and fix copper wounded Voltage stabilizer 5.0 KVA Capacity for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 270 V with output voltage stabilized at 230 V with accuracy of ± 2.5% complete all as specified and as directed. |