| 1 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 2 | 3 x 2.5 sq. mm |
| 3 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 4 | 20 mm |
| 5 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt) as required. |
| 6 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 7 | Above 35 sq. mm and upto 95 sq. mm |
| 8 | Supply of LED Flood Light with a minimum system lumen of 7000 Lumen and system wattage not exceeding72W with a nominal efficiency 90 lumen/watt .The Luminaire should be having Minimum 50000 Burning hours(L70B50). The housing should be of Single piece non-corrosive ADC12Grade high-pressure die-cast aluminumand should have corrosion resistant coating to pass Natural salt spray test of 500 Hrs with IP66 Protection. The luminaire should be capable of withstanding voltage stress of 440V for 8 Hrs , should have an auto shutdown at 325V and have an auto recovery feature , Under Voltage protection with Input Voltage Stress of 100V for 48 Hrs, PF > 0.95 and THD<10 %.The Luminaire should have a 10 KV SPD duly bolted in the Luminaire,SPD should be able to sustain a minimum 15 hits of 10KV rating i.e. Total of 45 hits across all the three modes as per IEEE 62.41.2 .The Drivers should be a potted driver not a printed circuit board without casing, mounted inside the luminaire,PF>0.95 and THD<10% . Luminaire and driver shall be separately BIS approved of same make equivalent to PhilipsBVP120 LED047 CW FLNB FG A1 PSU GR. LM80,LM79 ,Type Test certificate and Bis certificate need to be submitted. Including all necessary equipments for installation. |
| 9 | Supplying installation, testing and commissioning of free standing out door compartmentalized cubicle feeder pillar type panel suitable for 415 V, 3phase, 4 wire 50Hz AC supply system fabricatedin CRCAsheetsteelof14gaugethick, with hinged double leaf shutters with pad locking arrangement, detachable gland plates of suitable size at the bottom for cable entry, and busbar chamber with tinned copper bus bar of 100A capacity,handle, gaskets etc.withslopedroof,includingpowdercoat paintinginapprovedshade,ISMCchannelat bottom, entire panel shall have a common tinned copperearthbarofsize20mmx3mmatthe rear with1 no 100 A 4 P MCCB, 1 no 63 A 4 P RCCB, 1 no 63 A 4P MCCB, 2 no 32 A 4P MCCB, 4 no 25/20 A 4P MCCB, 1 no 20 A MCCB with digital timer, 2nosearthstud,solidconnections fromswitchgearswithrequiredsizeofcopper wire,control wiring with 1.5 sq.mm PVC insulatedcopperconductorcable,cable alleys, cable gland plates etc including indication lamps, digital type Multi function meter suitable CTs, SPD type 1&2 with back up fuse, danger notice board, LED indicator, feeder compartment lock, terminal block, PVC trunking, slotted channel, suitable connector, termination lug, copper wire if required, meter viewing glass if required etc.. Insulated copper bus bar for phase and Neutral adequate amperesize of Incomer Switch , out going switches. The panel Board should be fitted on the base frame for panel board using channels of class designation 75 including cutting,welding, drilling holes,painting two coats of synthatic enamel paint over a coat of zinc chromate paint botling the frame to the panel and to the furnished floor using required bolts and nuts making good the dameges colour washing and including providing and fixing the following switch gears etc as required.The charges for all control wiring, loading and unloading, testing and commissioning are included. The cable entry may be bottom or top as per direction of Engineer in charge, The Panel shall be Fabricated as perElectrical Inspectorate, KSEB, CPRI & other relevent codes and standards. Including proper labeling of cable entry, outgoing etc. With appropriate drawing (CAD file) and documentation for electrical inspectorate approval for load addition and energisation as required complete, including charges/ fee for application to KEI. |
| 10 | Supply and laying one number of the 8 SWG good quality bare copper wire for earthing from earth electrode to security container cabin recess of minimum 60cm below the ground for connections etc. as required. |
| 11 | Charges for removing metal enclosures with MCB & other accessories without any damage and making good the damages of the wall including painting,etc. as required. |
| 12 | Supply of suitable amount (60kg) of earthing compound (EXCEL compound or equivalent) etc. as required. |
| 13 | Supplying and fixing 130 x 180 x 77 mm or nearest size water proof rigidpolycarbonate loop in loop out weather proof box (IP 66) with detachable front cover, including supply & fixing 4 way busbar connector with base insulator, fixing 6 A SP MCB, fixing on the surface using suitable size metal screws, giving connections and other accessories as required. |
| 14 | Supply and laying one number of the 6 SWG good quality bare copper wire for earthing from earth electrode to security container cabin recess of minimum 60cm below the ground for connections etc. as required. |