| 1 | Fabrication, assembling, Factory testing, supply, installation, site acceptance testing, and commissioning of415 V, 5 wire,3 Phase min.continous current rating of 630 A at 50 deg. Celsius, min short circuit rating of 36 kA/ 1 sec with TP+N,MCCB/ACBincomer feeder (LSIG MP Based) with minimum rating of630A,36kA, TP+N MCCB/ACB outgoing feeder (LSIG MP Based) with minimum rating of250A,25kA (5 nos) and ETP grade copper busbar (99.9% purity) including multifunction meter in allfeeders, Single front, Fixed type, Pedestal/Floor mounted, Thermoplastic Polycarbonate Enclosure min.IP65 & IK08 type Outdoor Feeder Pillar with MS Hot Dip Galvanized Canopy and double door comply with IEC-61439-1/2 as per the tender specification. (MS item,GI Flat,Insulation mat required for installation will be measured separately.) |
| 2 | Fabrication, assembling, Factory testing, supply, installation, site acceptance testing, and commissioning of415 V, , 5 wire,3 Phasemin.continous current rating of 400 A at 50 deg. Celsius, min short circuit rating of 25 kA/ 1 sec with TP+N MCCBincomer feeder(TMD Based) with minimum rating of400A,25kA,TP+N MCCB/MCB outgoing feeder (TMD Based) with minimum rating of32A,25kA (4 nos),63A,25kA (4 nos),200A,25kA(4 nos.) and ETP grade copper busbar (99.9% purity)including multifunction meter ln incomerfeeder, Single front, Fixed type, Floor mounted,indoor type, Thermoplastic Polycarbonate Enclosuremin.IP54 & IK08 type indoor panel with moving arrangement comply with IEC-61439-1/2 as per the tender specification. (MS item,GI Flat,Insulation mat required for installation will be measured separately.) |
| 3 | Fabrication, assembling, Factory testing, supply, installation, site acceptance testing, and commissioning of Internal arc ( min 85kA for 0.4 sec) tested 415 V, 3 Phase min.continous current rating of 630 A at 50 deg. Celsius, min short circuit rating of 50 kA/ 1 secwith 4P, motorised MCCB/ACBincomer feeder(LSIG MP Based) with minimum rating of630A,50kA, 4P,MCCB outgoing feeder (TM Based O/C,S/C) with minimum rating of 100A,16kA (34 nos),200 A,16 kA (4 nos) and ETP grade copper busbar (99.9% purity)including multifunction meter in incomerfeeder, Single front, fixed type, ,fully type tested,min.IP54,4B form of segregation,Pedestal/Floor mounted indoor panel comply with IEC-61439-1/2 as per the tender specification. (MS item required for installation will be measured separatly.) |
| 4 | Fabrication, assembling, Factory testing, supply, installation, site acceptance testing, and commissioning ofInternal arc ( min 85kA for 0.4 sec) tested 415 V, 3 Phase min.continous current rating of 400 A at 50 deg. Celsius, min short circuit rating of 50 kA/ 1 secwith 4P, motorised MCCBincomer feeder(LSIG MP Based) with minimum rating of400A,50kA, 4P,MCCB outgoing feeder (TM Based O/C,S/C) with minimum rating of 100A,16kA (30 nos),200 A,16 kA (3 nos)and ETP grade copper busbar (99.9% purity)including multifunction meter in incomerfeeder, Single front, fixed type, ,fully type tested,min.IP54,4B form of segregation,Pedestal/Floor mounted indoor panel comply with IEC-61439-1/2 as per the tender specification. (MS item required for installation will be measured separatly.) |
| 5 | Fabrication, assembling, Factory testing, supply, installation, site acceptance testing, and commissioning ofInternal arc ( min 85kA for 0.4 sec) tested 415 V, 3 Phase min.continous current rating of 400 A at 50 deg. Celsius, min short circuit rating of 50 kA/ 1 secwith motorised 4P MCCBincomer feeder(LSIG MP Based) with minimum rating of400A,50kA, MCCB outgoing feeder (TM Based O/C,S/C) with minimum rating of 100A,16kA (24 nos),200 A,16 kA (3 nos) and ETP grade copper busbar (99.9% purity)including multifunction meter in incomerfeeder, Single front, fixed type, ,fully type tested,min.IP54,4B form of segregation,Pedestal/Floor mounted indoor panel comply with IEC-61439-1/2 as per the tender specification. (MS item required for installation will be measured separatly.) |
| 6 | Shifting,site acceptance testing, and commissioning of415 V, 3 Phase 630/800A Power panel (approx 1000Kg). (MS item will be measured separately) |
| 7 | Shifting,site acceptance testing, and commissioning of415 V, 3 Phase 250A Power panel (approx 500Kg). (MS item will be measured separetely) |
| 8 | Loading, Transportation, Unloading at site, installation, Testing and Commissioning of one number PVC/XLPE insulated & sheathed Copper/Aluminium Conductor, armoured power Cables of following sizes in excavated trenches direct in ground including excavation, sand cushioning, protective covering with chamber burnt/cement bricks on sides & top, refilling the trench and providing RCC route indicator etc as required..(Note: Cable will be issued free of cost by the department)Size:-3/3.5/4Core X above 240 & up to 400 sqmm(Note:Height of installation may vary from 3 m to 14 m) |
| 9 | Loading, Transportation, Unloading at site, installation, Testing and Commissioning of1100 Volts Grade PVC/XLPE/HRPVC insulated, Stranded Copper/Aluminium conductor cables of following sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification (Note: Cable will be issued free of cost by the department).Size:-3/3.5/4core X Upto 120 sqmm(Note:Height of installation may vary from 3 m to 14 m) |
| 10 | Loading, Transportation, Unloading at site, installation, Testing and Commissioning of1100 Volts Grade PVC/XLPE/HRPVC insulated, Stranded Copper/Aluminium conductor cables of following sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification (Note: Cable will be issued free of cost by the department).Size:-3/3.5/4Core X above 240 & up to 400 sqmm(Note:Height of installation may vary from 3 m to 14 m) |
| 11 | End Termination ofAluminium/copper Conductor PVC/XLPE Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium/copper crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.Size:-3/3.5/4Core Xup to 35 sqmm(Note:Height of installation may vary from 3 m to 14 m) |
| 12 | End Termination ofAluminium/copper Conductor PVC/XLPE Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium/copper crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.). 3/3.5/4Core X above50 Sqmm & up to 120 Sqmm |
| 13 | End Termination ofAluminium/copper Conductor PVC/XLPE Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium/copper crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.)3/3.5/4Core X above240 Sqmm & up to 400 Sqmm |
| 14 | Supply, installation, testing and commissioning of the following Raychem make Heat Shrinkable Cable Straight Through Jointing Kits (Crimping type) for 3.5 Core Aluminium Conductor, 1.1 kV (E), PVC/XLPE insulated cables of following sizes as specified. Excavation will be measured separately .Size:3.5 Core x 400 Sq. mm |
| 15 | Supply, installation, testing and commissioning of various types of LED Luminaries with colour temperature range from 5700 - 6500K,input voltage range 1ph,50Hz±3%,230V±10%,50,000 average operating hoursSurface mounted/Suspended,LED outdoor flood type fixtures of Min. initial lumen output of 14000 lumen , Min.lumen efficacy of 140 lumen/watt, Max power consumption of 100 W,IP66 or above, complete with all fixtures & erection accessories in MS Embedded Parts/Brick masonry or RCC walls/RCC ceiling/column/beam/False ceiling/any civilstructures with required number and suitable sizes of anchor fasteners, SS rope, bolts and nuts with washers etc., along with necessary Scaffolding arrangement, safety measures etc., as per the detailed specifications, drawings and as directed by the Engineer-In-Charge.(Note:5 year Manufacturer warranty shall be provided for all supplied fixtures ) |
| 16 | Supply, Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade 3C*2.5sq.mm HRPVC insulated & FRLS Multicore round sheathed Bright Annalead Copper conductor Heavy Duty Industrial grade Flexible cables in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification. |
| 17 | Supply, fabrication and installation of 25 X 6 mm GI flat size of Hot dip Galvanised GI Flats in Built in trenches on walls, poles, RCC Concrete and through embedded pipes as per the detailed specification. No cutting or drilling permitted after galvanisation.(Note:Height of installation may vary from 3 m to 14 m) |
| 18 | Supply and installation of8 SWG copper wires in built in trench as per the detailed specification |
| 19 | Supply and installation of 230 mm Dia. 2 Mtrs Long, NP 2 Class Hume Pipes at a depth of 1200 mm including supply of Collars and fixing them with1:1 cement mortar and curing, including cutting for crossing of existing road and excavation of all types of soil, backfilling, normalisation of road etc complete as directed by Engineer-in-Charge. |
| 20 | Supply installation and testing of Maintenance free earthing system (1x10 feet x 5/8inch copper bonded steel rod, 22 kg Ground Enhancing Material (GEM) ) as per IS: 3043 including RCC Chamber and RCC cover slab as per detailed specification |
| 21 | Supply installation of 2.0 mm thickness, Max useable voltage 3.3kV, AC Proof voltage 10kV for 3 minutes, AC dielectric strength 30kV RMS Insulating Mat confirming to IS:15652 |
| 22 | Excavation of soil including refilling with excavated earth and disposing surplus earth at places as directed with in a lead of 10 Mtrs. and initial lift upto 1.5 Mtrs. including neat banking as per detailed specification. |
| 23 | Supply,Fabrication and installation of GI supports for cable trays and painted supports for other application on wall/slabs/ floor/other civil structureswhich includes MS Brackets, Supports, Frame work, Clamps, Base Channels, sheets etc., fabricated out of angle / Channel / Rods etc., The rate quoted shall include the cost of fabrication / welding, cleaning andgalvanisingincluding supply of required, fasteners, nuts, washers,caterpins etc., (Note:Height of installation may vary from 3 m to 14 m) |
| 24 | Supply, installation including end termination with existing wiring, testing and commissioning of recess, box (2 ft x 2 ft) type, low bay LED indoor fixtures of Min. initial lumen output of 3600 lumen, Min.lumen efficacy of 110 lumen/watt,Max power consumption of 34 Wwith colour temperature range from 5700 - 6500K,input voltage range 1ph,50Hz±3%,230V±10%,50,000 average operating hoursas follows, complete with all fixtures & erection accessories in False ceiling/any civilstructures with required number and suitable sizes of anchor fasteners, SS rope, bolts and nuts with washers etc., along with necessary Scaffolding arrangement, safety measures etc., as per the detailed specifications, drawings and as directed by the Engineer-In-Charge.(Note:5 year Manufacturer warranty shall be provided for all supplied fixtures) (Note: Height of false ceiling is 3 to 5 mtr and distance between false ceiling and true ceiling of room is varies from 2 mtr to 10 mtr) |
| 25 | Supply, installation, testing and commissioning of 600mm dia Industrial wall Mounting /pedestalFans as per the detailed specification |
| 26 | Installation of upto 6 sqmm of 1100V grade FRLS insulated copper conductor wires existing concealed/ Exposed PVC / ERW/Flo-coated Metal conduits as per the detailed scope of work including supply and installation of spacer and clamp wherever required(Note:installation height upto 12 m) |
| 27 | Wiring for Light/Sensor/Fan Points with 2 Runs of 1.5 Sq.mm copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm copper wire for Earth from MCB Distribution Board to Primary light/sensor/fan point through Control Switch Box including 10Amps modular switch(Note: Average length per run considered is 30 mtr and installation height upto 12 m) |
| 28 | Supply, installation, testing and commissioning of the 32A 3P+N+E-FP Tempra plug and socket DBs with FP 20A-32A MCBof Metal Clad Socket in sheet steel enclosure with Plugs and Socket as per the detailed specification. (MS item will be measured separately). |
| 29 | Supply, installation, testing and commissioning of the 16A 2P+E-DP Tempra plug and socket DBs with DP 16A MCB of Metal Clad Socket in sheet steel enclosure with Plugs and Socket as per the detailed specification. (MS item will be measured separately). |