| 1 | Turbine, Generators and Accessories |
| 2 | Turbine Generator units 3.0 MW,10 % COL, 1000 RPM, 135 m head, 0.8 p.f. 6.6 kV complete with auxiliary equipment such as Governor, LPcompressed air system, AVR, excitation system LA/VT panels etc. including one spare Runner |
| 3 | Unit Control Boards (TACP) |
| 4 | Cooling water system comprising of Pump-Motor and filter sets, valves, piping etc. |
| 5 | Drainage and dewatering systems |
| 6 | Compressed air system including pipes and valves |
| 7 | Supervisory control and data acquisition system (Automatic PLCbased control system) |
| 8 | Optical Fiber Communication System |
| 9 | Control & protection panels |
| 10 | Penstock valve (MIV 850 mm dia) |
| 11 | Mandatory Spares for Turbine, Generator and Accessories |
| 12 | Turbine Generator complete with auxiliary equipment such as Governor, LP compressed air system, AVR, excitation system LA/VT panels etc. including one spare runner, Compressed air system including pipes and valves. |
| 13 | OPU Turbine Oil |
| 14 | Items to be supplied and essential for Generator. |
| 15 | Transformer Oil. |
| 16 | Cooling water system comprising of Pump-motor and filter sets, valves, piping, etc. |
| 17 | Dewatering systems. |
| 18 | Supervisory Control and DATA Acquisition System (Automatic PLC based control system) |
| 19 | Optical Fibre Communication system |
| 20 | Control & Protection panels |
| 21 | Penstock valve (MIV 850 mm dia) |
| 22 | Auxiliary Electrical Equipment forPower Station |
| 23 | Step up transformers (Rating 6.6/33 kV,5MVA,ONAN, 3 phase oils filled type) with all accessories, oil, |
| 24 | Transformer Oil purifier (500 LPH) with pipes etc. |
| 25 | Station Service transformer (Rating 6.6/0.433 kV, 200 kVA, 3 phase oil filledtype) |
| 26 | LTAC board for power supply to PH and outdoor switchyard complete |
| 27 | DC batteries, battery charging equipment, D.C. distribution board with DCswitchgear (Rating 24 V, 500 AH) |
| 28 | Diesel generating set 160 kVA 415 VoltsAMF |
| 29 | Power and Control Cables |
| 30 | Cable racks and accessories |
| 31 | Ground mat and earthing for PH andswitchyard including transformers |
| 32 | Illumination of power house andswitchyard |
| 33 | 6.6 kV switchgear panels |
| 34 | 11KV Switchgear panel comprisingCircuit breaker, protection, metering CTand PT Etc. |
| 35 | Internal communication system and CCTVsurveillance system |
| 36 | Auxiliary Mechanical Equipment and Services for Power Station |
| 37 | Electrical overhead traveling crane for PH (cap.25/5T) withmanual operation |
| 38 | Firefighting equipment withhydrant pipes, pumps, valves etc. |
| 39 | Air conditioning, ventilation andheating equipment |
| 40 | MANDATORY SAPRES FOR AUXILIARY ELECTRICAL EQUIPMENT AND SERVICESFOR POWER STATION |
| 41 | Transformer Oil Purifier (500 LPH) with pipes etc. |
| 42 | Power and Control Cables |
| 43 | Internal communication system and CCTV surveillance system |
| 44 | Spares for Electrical overhead travelling crane for PH (cap 25/5 T) |
| 45 | Firefighting equipment with hydrant pipes, pumps, valves etc. |
| 46 | Air Conditioning, ventilation and heating equipment |
| 47 | MANDATORY SPARES AUXILIARY FOR MECHANICAL EQUIPMENT FOR POWER Station |
| 48 | Spares for Electrical overhead travelling crane for PH (cap 25/5 T) |
| 49 | Firefighting equipment with hydrant pipes, pumps, valves etc. |
| 50 | Air Conditioning, ventilation and heating equipment |
| 51 | Tools and Plants |
| 52 | Torque wrenches |
| 53 | Spanners of different sizes |
| 54 | HT,LT Megger5 Kv and 500 Volts |
| 55 | Tong Tester |
| 56 | Switchyard Equipment and Auxiliary Equipment & Services for Switchyard |
| 57 | Vacuum Circuit breaker |
| 58 | Isolator with earthing blade |
| 59 | Isolator without earthing blades |
| 60 | Current Transformers |
| 61 | Potential Transformers |
| 62 | Lightning Arrestors |
| 63 | Bus Conductor, clamps/connectors hardwares and insulators |
| 64 | Main and Auxiliary structures (MT) |
| 65 | Fencing and security |
| 66 | Lightning protection of power houseand switchyard |
| 67 | Civil works including foundations,trenches, water tank for fire protection,spreading of boulder/ ballast for safetyagainst electric fault, drainage, railtracks etc. |
| 68 | Mandatory Spares for Switchyard Equipments |
| 69 | Vaccum Circuit Breaker |
| 70 | Isolator with Earthing Blades |
| 71 | Isolator withoutEarthing Blades |
| 72 | Current Transformers |
| 73 | Potential Transformers . |
| 74 | Lightning Arresters. |
| 75 | Bus Conductor, clamps/connectors hardwares and insulators |
| 76 | Main and Auxiliary Structures (MT) |
| 77 | XLPE Power Cables6.6 kV Aluminum Conductor Armored XLPE |
| 78 | Generator Line to LA/VT and switchgear panels.6.6 kV, 2R x 1C x 400 sq mm aluminum conductor armored XLPE cables to be laid separately with 50 mm gap on steel racks. |
| 79 | Switchgear panels to LV side of step-up transformer6.6 kV 2RX3C X 400 sq mm aluminum conductor armored XLPE cables to be laid separately with 50 mm gap on steel racks. |
| 80 | Switchgear panels to HV side of station auxiliarytransformer6.6 kV 1RX3C X 185 sq mm aluminum conductor Armored XLPE cables to be laid separately on steel racks. |
| 81 | Generator Neutral grounding6.6 kV 2RX1C X 400 sq mm aluminum conductor Armored XLPE cables to be laid on steel racks. |
| 82 | 1.1 kV aluminum conductor armored XLPE cables |
| 83 | Station auxiliary transformer to station service board1.1kV 3.5Cx300 sq mm aluminum conductorarmored XLPE cables to be laid separately on steel racks. |
| 84 | DG SET to station service board1.1 kV 2R x 3.5C x185 Sqmm aluminum conductor armored XLPE cables to be laid separately on steel racks. |
| 85 | MANDATORY SPARES OF XLPE CABLES |
| 86 | 6.6kVAluminumConductorArmoredXLPE Cablesi) Generator Line to LA/VT and switchgear panels 6.6 kV, 2R x 1C x 400 sq mm aluminum conductor armored XLPE cables to be laid separately with 50 mm gap on steel racks |
| 87 | Switchgear panels to LV side of step-up transformer i) 6.6 kV 2RX3C X 400 sq mm aluminum conductor armored XLPE cables to be laid separately with 50 mm gap on steel racks. |
| 88 | Switchgear panels to HV side of station auxiliary transformer i) 6.6 kV 1RX3C X 185 sq mm aluminum conductor Armored XLPE cables to be laid separately on steel racks |
| 89 | Generator Neutral groundingArmored XLPE cables to be laid on steel racksi) 6.6 kV 2RX1C X 400 sq mm aluminum conductor |
| 90 | 1.1 kV aluminum conductor armored XLPE cablesi)Stationauxiliarytransformertostationservice boardii) 1.1kV 3.5Cx300 sq mm aluminum conductor armored XLPE cables to be laid separately on steel racks |
| 91 | DG SET to station service boardi)1.1 kV 2R x 3.5C x185 Sqmm aluminum conductor armored XLPE cables to be laid separately on steel racks |
| 92 | 33kV TRANSMISSION LINE |
| 93 | Construction of 33 kV Single circuit transmissionline on towers including Survey, Peg marking,Excavation, Casting of foundations, Stub setting,curing, back filling, erection tightening of towers,hoisting of insulators & hard wares, paying ofearth wire, conductors, stringing and their finalsagging, terminating and connecting at the gridsubstation on 33 KV terminal gantry. |
| 94 | Testing and Commissioning of transmission lineafter completion of construction works with allprecautions, maintaining the necessary clearances,tree cuttings and compensation of crop etc. to theaffected habitats for complete line |
| 95 | OPGW for Communication with both endtermination at Power House and at Shallang 33 KVSubstation |
| 96 | MANDATORY SPARES FOR 33KV Transmission line |
| 97 | Conductors and Insulators |
| 98 | OPGW for Communication |
| 99 | 33/11 kv Grid Sub-Station Grid Sub-station equipment for 33 kVbay connection |
| 100 | Vacuum Circuit breaker |
| 101 | Isolator with earthing blade |
| 102 | Isolator without earthing blades |
| 103 | Current Transformers |
| 104 | Potential Transformers |
| 105 | Lightning Arrestors |
| 106 | Bus Conductor, clamps/ connectorshardwares and insulators |
| 107 | Main and auxiliary structures |
| 108 | Fire protection system |
| 109 | Optical Fiber Communication System |
| 110 | Control/ Relay Panel, cables and earthing etc. |
| 111 | MANDATORY SPARES FOR 33/11 KV Grid Sub-Station |
| 112 | Vaccum Circuit Breaker |
| 113 | Isolator with Earthing Switch |
| 114 | Isolator withoutEarthing Switch |
| 115 | Current Transformers |
| 116 | Potential Transformers |
| 117 | Lightning Arresters |
| 118 | Bus Conductors, Clamps/ Connectors hardwares and insulators |
| 119 | Main and Auxiliary structures |
| 120 | Fire Protection Syatem |
| 121 | Optical Fibre Communication System |
| 122 | Control/Relay Panel, cables and earthing etc. |