| 1 | M&L for following repair, serviceing and replacement of unserviceable accessories of LT Panel any make type/size includingwelding, brazing and drilling work:- (a) Tightening of all loose conectiont of cableinside the panel and welding the broken door of the panel.(b)Clean all the rusted busbar through hemry paper and fixing insulation heat shrink sleeves through out the busbar including strip connected with out going MCCB. (c) Cutthe damage insulation portion end of cable inside the panel and reconnecting its into positions after fixing the end termintion/Sleeves complete with suitable size of aluminium lugs and stainless steel nut bolts including excavation and earth work in any type for taking out the existing cable loop to fixing the end joint or reconnection in position. (d) Repair/Replacement ofburn/unserviceable voltmeter, ammeter,indication lamp contactor including control wiring of the panel between voltmeter, Ammeter and their selector switch and CTs . (e)Repair/Replacement of all burn lugs inside the panel.(f) Replaced all the GI rusted nut, bolts,and washers with made of stainless steel nuts, bolts and washers.(g) Cleanthe dust inside the panel by air blower/vaccum cleaner complete.Note : (a) The cost of nut bolts, washers, insulation tape, lugs, etc essentially required to make the panel serviceable shall be deemed to be included in the quoted rate. (b) Other spare parts/accessories shall measured and paid separatelyunder relevant items of schedule. |
| 2 | Supply only epoxy type insulator for support of busbar grade 1100 volt as per existing size. |
| 3 | Materialonly for control wiring of the panel with 1.5 sq mm multistranded, PVC insulated copper conductor 1100 Volt grade FRLS cable. |
| 4 | Supply only LED phase indicator lamp colour RED/YELLOW/GREENAC 220 Volt 50 Hz. |
| 5 | Supply only LED phase indicator lamp colour BLUE 220 Volt 50 Hz. |
| 6 | Supply only LED phase indicator lamp colour WHITE AC 220 Volt 50 Hz. |
| 7 | Supply only LED phase indicator lamp colour AMBER AC 220 Volt 50 Hz. |
| 8 | Supply only cast resin insulated type CT, Ratio 300/5Awith capable of withstanding momentary short circuitand symmetricalshort circuit for 1second. |
| 9 | Supply only cast resin insulated type CT, Ratio 400/5Awith capable of withstanding momentary short circuitand symmetricalshort circuit for 1second. |
| 10 | Supply only copper bus bar any size (5x20, 10x20, 10x25, 10x40, 10x50,10x80) mmduly insulated with heat shrink busbar insulation sleeves. |
| 11 | M&L for spray painting in existing steel surface of Panel/FPB/JB etc with two coats of synthetic enamel including one coat red oxide in rusted area after proper cleaning and prepration of old painted surfaces steel / Iron of any description with spray machine complete all as specified and directed. (Note:- Painting of panels / feeder filler boxes shall be carried out in different colour of paints as required at site and as directed. |
| 12 | M & L for repair, serviceing, release testing and comprehensive maintenance of fully automatic Air Circuit Breaker (ACB) of all LTpanel and capacitor panel. Repair/maintenance work comprisr the followings:-(a) Disconnecting the ACBfrom existing position and opening, cleaning the dust ofall contactpoints , servicing by using CRC and throughly chekingto detect the any faultthen rectifiedthe same by supplying and replacing the defect parts and after rectified the fault refitted the ACB in its position and commossioning and testing the panel . (b)Opening the panel and cleaning dust of the panel through vaccum cleaner, blower should not be usedfor cleaning. (c) After cleaning , checkingtheall cable connection,Busbar joint and tightening the loose connection and oiling all the nut Bolt of the same.(d) Cleaning and checkingthe servicibity condition ofall the relays, contactor, fuse, Indicator switch, push buttom, control wiring, connector and replacing all the burn out parts assembled the paneli.e contactor, relaywith new one. |
| 13 | Note -(i) Spare parts shall be measured and paid separately under relevant items. (ii)Minimun one ACBshall be produce to contractor for restand/ repair for one visit. Contractor will not demand all ACB repair in one visit. Visit and repair charges of electrician and helper are included in the quoted rate. no extra charges shall be paid to the contractor. |
| 14 | Supply only aux contactor MX0 31E (3NO +1NC)operating voltage 240 Volt AC |
| 15 | Supply only aux contactor MX0 31E (3NO +1NC) operating voltage 110 Volt DC |
| 16 | Supply only aux contactor MX0 22E (2NO +2NC) operating voltage 240 Volt AC |
| 17 | Supply only aux contactor MX0 22E (2NO +2NC) operating voltage 110 Volt DC |
| 18 | Supply only aux contactor MXO 40E (4NO)operating voltage 240 Volt AC |
| 19 | Supply only Panel control switch (TNC 02 NO + 02 NC) operating voltage 240 Volt AC |
| 20 | Supply only DigitalVAF meter LCD display flush mounting type of size96 mm x 96 mm (4”x4”) square dialAccuracy Cl-0.5S with Rs 485input voltage measurement range 50-520 Volt VAC (P-P) , aux supply 80-300 volt AC/DC,CT secondary site selectable 1A/5A,3 phase four wire system with inbuilt selector switch complete all as specified and directed. |
| 21 | Supply only XT series HMI size 4.5 inch with colour TFT display option with ethernet model, touch screephigher brightness level upto 440cd/m2 long backlight life upto 50000 hours for display, shock and vibration protection as per IEC standard, RAM 32 Mb and ROM 128 MB all as per specified and directed by Engr-in charge. complete all as specified and directed. |
| 22 | Supply only Instantaneousdifferential protection relayCAG Type CT Sec 1 amp Model No CAG34AF71A |
| 23 | Supply onlypush buttons red, green, yellow and blackwith aux contacts 1 NO and 1 NC all as specified and directed. |
| 24 | Supply only flush typemicro processor based alarm annunciator with P.B window 08 and aux voltage 110 Volt DCas persample in site in complete all as specified and directed. |
| 25 | Supply only Hooter flush type 96 x 96 mmaux voltage 110 Volt DCas persample in site in complete all as specified and directed. |
| 26 | Supply only shunt releaseforACB supply voltage 110 VDCas per sample in existing sizeall as specified and directed. |
| 27 | Supplyonly Closing releasefor ACBsupplyvoltag 240 Volt AC as per sample of existing in siteall as specified and directed by Engr-in-charge. |
| 28 | Supplyonlyunder voltage trip device forACBsupply voltage 415 Volt AC as per sample of existing in siteall as specified and directed by Engr-in-charge. |
| 29 | Supplyonlyautomatic spring charge motor operating voltage 220 Volt ACfor ACB as per sample of existing in siteall as specified and directed by Engr-in-charge. |
| 30 | Supply onlyDoor interlock of ACB as per sample of existing in siteall as specified and directed. |
| 31 | Supply and fixingrepair ofMicroprocessor SP-UW MTX3.5ECRelease suitable for Omega ACB as per sample at existing site all as specified and directed . |
| 32 | M&L for Repair, serviceing and replacement of unserviceable accessories ofLT Capacitor Panelof any makeany sizecomprises the ffollowing repair work:- (a) Tightening of all loose conectiont of cableinside the panel and welding the broken door of the panel.(b)Cutthe damage/burn portion end of cable inside the panel and reconnecting its into positions after fixing the copper lugs with suitable sizeand stainless steel nut bolts and reconnection in position. (d) Opening and checking and testing the serviceabilty ofcapacitor bankand detect any fault the same should be rectified by supplying and replacing the deffective parts with new one.(e) Repair/Replacement of all burn lugs inside the panel with copper lugs suitable size.(f) Replaced all the GI rusted nut, bolts,and washers with made of stainless steel nuts, bolts and washers.(g) Cleanthe dust inside the panel by air blower/vaccum cleaner complete.Note : (a) The cost of steelnut bolts, washers, copperlugs, etc essentially required to make the panel serviceable shall be deemed to be included in the quoted rate. (b) Other spare parts/accessories shall measured and paid separatelyunder relevant items of schedule. |
| 33 | Supply only automatic power factorcontrollerEPCOS BR 6000 12 stage operatingvoltage 240 VAC all as specified and directed |
| 34 | Supply onlyPower contactor 3phaseAC3 ratin 110A and AC1 rating 160 ampType MNX 110 with 2 NO + 2NCall as specified and directed. |
| 35 | Supply only Power contactor 3phaseAC3 rating 80A and AC1 rating 1100 ampType MNX 80 with 2 NO + 2NCall as specified and directed. |
| 36 | Supply only PVC cable 6 sq mm 4 core copper conductor FRLS multidtranded with rope insulation complete all as specified and as directed. |
| 37 | Supply and fixing Copper lugs 10 sq mmall as specified and directed. |
| 38 | Supply and fixing Copper lugs 16 sq mmall as specified and directed. |
| 39 | Supply and fixing Copper lugs 25 sq mmall as specified and directed. |
| 40 | supply and fixing in repair LTAPP box type capacitor bank capacity 25 KVAr 440 V AC 3 Ph 50 Hz all as specified and directed. |
| 41 | supply and fixing in repair LTAPP box type capacitor bank capacity 50 KVAr 440 V AC 3 Ph 50 Hz all as specified and directed. |
| 42 | Supply and fixing Under Voltage and Over Voltage Minilec Relay 415 Volt AC as per sample at existing site all as specified and directed. |
| 43 | Supply and fixing Bridge rectifire Input Voltage 240 Volt Ac all as specified and directed. |
| 44 | M&L for Repair, serviceing and replacement of unserviceable accessories ofUPS type power back up of any makeany capacity comprises the ffollowing repair work:- (a) Tightening of all loose conectiont of wirein between UPS and panel and cutthe damage/burn portion end of cable inside the panel and reconnecting its into positions after fixing the copper lugs with suitable sizeand nut bolts and reconnection in position. (b) Opening and checking and testing the serviceabilty ofBattery and detect any fault the same should be rectified by supplying and replacing the deffective parts with new one. (c) Cleanthe dust inside the panel by vaccum cleaner complete.Note : (a) The cost of nut bolts, washers, copperlugs, etc essentially required to make the panel serviceable shall be deemed to be included in the quoted rate. (b) Other spare parts/accessories shall measured and paid separatelyunder relevant items of schedule. |
| 45 | Supply only of CS7-12 chloride safepower , SMF typesealed Lead acid Battery capacity 12 Volt 7 Ah used for UPS backupalll as specified and directed. |
| 46 | Supply onlyEatonBussman series170M1565D high speed square body fuse 690 V (IEC) 63A 700 Volt AC , Combination fuse indication indicatorblade endall as specified and directed. |
| 47 | Supply and fixing in repair ofPLC (Programmable Logic Controller) Series SIMATIC S7 200 SMARTforDG Synchronisation Panel/Main power supply synchronisation panel all as specified and directed. |
| 48 | M&L for PLC programming and updation of softwareof DG Synchronisation Panel andMain power supply synchronisation panel all as specified and directed. |
| 49 | Supply and fixing in repair of Battery charger Mahamai 24 VDC 16 Amp all as specified and directed. |
| 50 | M&L earthing complete with galvanised steel earth plate electrode 60×60cm×6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron 25x4mm earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.3 connected to earthing test point including testing on completion including watering GI pipe 20mm bore medium grade, 15mm bore light grade GI pipe for protection of earth lead including provision ofconcrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 54 cm x 54 cm x 5 cm including 8mm dia TMT bars both ways @ 15cm centre to centre with one handle for lifting made out of8mm dia MS bar, funnel & wire mesh, excavation and earth work in any type of soil complete including dismantling existing all as specified & directed. |
| 51 | S&F in repairsMCCB 160 Amps, 4 Pole, 415 V, adjustable type, with breaking capacity 36 KA, Ics=100 % ICU including spreader terminals & connected accessories both ends complete all as specified and directed. |
| 52 | S&F in repairsMCCB 200 Amps, 4 Pole, 415 V, adjustable type, with breaking capacity 36 KA,Ics=100 % ICU including spreader terminals & connected accessories both ends complete all as specified and directed. |
| 53 | S&F in repairsMCCB 250 Amps, 4 Pole, 415 V, Adjustable type, with breaking capacity 36 KA, 100 % ICUincluding spreader terminals & connected accessories both ends complete all as specified and directed. |
| 54 | S&F in repairsMCCB 320 Amps, 4 Pole, 415 V, adjustable type, with breaking capacity 36 KA, Ics=100% ICU including spreader terminals & connected accessories both ends complete all as specified and directed. |
| 55 | S&F in repairsMCCB 600 Amps, 4 Pole, 415 V, adjustable type, with breaking capacity 50 KA, Ics=100% ICU including spreader terminals & connected accessories both ends complete all as specified and directed. |
| 56 | Taking out old unserviceable under ground cable of any size and any position from trenches, floors and wall and segrate the serviceable portion cable for reuse complete all as specified and directed. |
| 57 | Supply and laying XLPE insulated armoured (under ground) heavy duty electic cable with stranded aluminim conductor 1100 volts grade of crossectionalarea150 Sqmm 3.5core laid in trenches/ducts/through pipes/in floor road/along the pole etc all as specified & directed by Engr-in-charge. Note : (a) Excavation earth work, brick protection and cushioning shall be measured & paid separately. |
| 58 | Excavation in trenches in soft loose soil including cutting road surfaces n.exc 1.5 mtr wide and n.exc. 1.5 mtr in depth for poles, stay, cable, pipe etc getting out all as specified. |
| 59 | Returning, filling in, including spreading, leveling,watering and well ramming in layers each n.exc 25 cm thick in soft loose soil all as specified. |
| 60 | Removal of excavated soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 61 | Supply and lay brick common burnt sub class \"B\" old size (compressive strength not less than 75 kg per sqcm) for protection of cable laid in trenches for under ground cable all as specified. |
| 62 | M & L for Sand cushioning trenches using fine sand to under ground cable, laid in two layers 15cm before laying the cable & 8cm after laying the cable complete all as specified and directed. |
| 63 | Labour for drillinghole under the road with the help of bocki / by manual or by machinefor crossing GI tubingofsize 100 mm pipefor cable protection all as specified and directed. |
| 64 | Supply and fixingin repairfor cable protection GI tubinglight grade fixedalong the pole/wall/under road of size 80 mm bore with necessary clamps, nut and bolts all as specified and directed by Engineer -in-Charge. Note : Cost of Clamps,nut and bolt for fixing of pole/walli included in quoted rate, |
| 65 | (Note : The Scope of Work contained in \"Sch of Credit\" amounting to Rs. 53,050.00 The Quoted sum shall be arrived at after deducting the amount of “Sch of Credit” from the total amount of the ‘BoQ’ |