| 1 | M&L for taking down/out/dismantling of existing LT over head conductor of any size/ capacity including insuator, cross arms etc complete all as specified and as directed. |
| 2 | M&L for painting of steel tubuler 11/9 mtr poles any type complete incl flat iron clamps,D clamps, Stay clamps, earth wire clamps, bracing, cross arm with two coat aluminium paint including prepration old painted surface initally & applying one coat of red oxide, applying two coat of aluminum paint over the red oxide, marking with alternate white and red strips 30 cm height 5 Nos strips with two coat of synthetic enamel paint (Ist quality of manufacturer )and also including numbering of poles with white paint are located on different locationscomplete all as specified and directed . |
| 3 | S & FMCCB,04 Pole, capacity 125 Amps with ultimate breaking capacity 25 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I in the existing panel with suitable connecting copper terminals at site complete all specified and directed. Make- Havells /L&T/Indo-Asian/Legtand/ABB |
| 4 | Supplying, laying, jointing & commissioning in replacement of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade, (Earthed) cross sectional area 300 sqmm 3.5 core as per IS 7098 Pt-II including cable connection with LT Panel/LT feeder pillar box of suitable size aluminium lugs/thimble complete all as specified and directed. |
| 5 | Supplying, laying, jointing & commissioning in replacement of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade, (Earthed) cross sectional area 240 sqmm 3.5 core as per IS 7098 Pt-IIincluding cable connection with LT Panel/LT feeder pillar box of suitable size aluminium lugs/thimble complete all as specified and directed. |
| 6 | Supply and laying1100 volts grade heavy duty cable with XLPE insulated stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel or strip and overall PVC sheathed, 50 sq mm 3.5 core ISI Marked as per IS 7098(Part 1) including connecting on LT OH line / LT panel /DB with suitable lugs, glands, binding wire etc complete all as specified and directed. |
| 7 | Supply and laying1100 volts grade heavy duty cable with XLPE insulated stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel or strip and overall PVC sheathed, 25 sq mm 4 core ISI Marked as per IS 7098(Part 1) including connecting on LT OH line / LT panel /DB with suitable lugs, glands, binding wire etc complete all as specified and directed. |
| 8 | Supply and laying1100 volts grade heavy duty cable with XLPE insulated stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel or strip and overall PVC sheathed, 16 sq mm 4 core ISI Marked as per IS 7098(Part 1) including connecting on LT OH line / LT panel /DB with suitable lugs, glands, binding wire etc complete all as specified and directed. |
| 9 | Supply and laying1100 volts grade heavy duty cable with XLPE insulated stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel or strip and overall PVC sheathed, 35 sq mm 3.5 core ISI Marked as per IS 7098(Part 1) including connecting on LT OH line / LT panel /DB with suitable lugs, glands, binding wire etc complete all as specified and directed. |
| 10 | Material and labour for Double wall corrugated HDPE pipe, ISI marked of outer dia 50mm, inner dia 38mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etcfor protection of LT cable XLPE grade 1100 volts complete all as specified and directed by Engineer-in-Charge. |
| 11 | Excavationin trenches in soft/loose soil not exc 1.5 mtrs wide and exc 1.5 mtr in depth for laying of pipe/ cables/ poles etc and getting out complete all as specified and as directed. |
| 12 | Returning filling in any type of soil including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and as directed. |
| 13 | Removing excavated soils to a distance n.exc. 50 mtr and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and as directed. |
| 14 | M&L for PCC 1:2:4 type B-1 (using 20mm graded stone aggregates) as in coping of poles etc including form work for poles all as specified and directed by Engr-in-Charge. |
| 15 | M&L for PCC 1:4:8 type D-2 (using 40mm graded stone aggregates) as in foundation filling and bed concrete for poles (bed concrete) all as specified and directed by Engr-in-Charge. |
| 16 | M&L for PCC 1:3:6 type C-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete of poles including form work for poles all as specified and directed by Engr-in-Charge. |
| 17 | Supply and laying dry river sand for cable cushioning in trenches to required width at bottom and top of cable incl spreading, levelling, watering and consiolidation complete all as specified and directed. |
| 18 | Supplying and laying Pcc cable cover, size 250 x150 x 40 mm, laid flat complete all as specified and directed by Engr in charge. |
| 19 | S&F in replacement of new generation energy saving and enviromental friendly long life LED security/ street light fitting 70 Watt with pressure die cast housing, toughened glass and secondary lens optics with IP-66 ingress protection, 4 kv in built surge protection, top opening driver cover for easy maintenance, efficacy upto 120 Im/w, white colour, input voltage of 150-240 Volts (Normal rated voltage 240Volts) complete including replacement of twisted 3 core copper cable of size 1.5Sqmm dia for connecting phase, neutral and earth from junction box to LED light through copper connectors complete as specifiedand as directed.Make:- CG/Wipro/Bajaj/Havells/Phillips/Halonix |
| 20 | S&F in replacement of LED flood light 120 watt 230Volt,AC outdoor type high performance with pressure die cast housing, toughened glass and secondary lens opticswith IP-66 ingressprotection, efficacy 120 Im/W complete with driver and lamp all as specified and directed. Make:- CG/Wipro/Bajaj/Havells/Phillips/Halonix |
| 21 | S&F in replacement kiosk box for luminaires ,weather proof made out of FRP housing fire retardant, non fusing, shock & rust proof, single piece moulded andcover with hinged door, pole mounting type comprising of four pole copper connectors of 16 Amps capacity with 6 Amp MCB single pole , of minimum size 300x200x125mm,fixed on pole with MS, clamps 30 x 5mm with necessary nuts, washer and incl applying two coats of synthetic enamel paint over ared oxide primer on steel surface/clamps and embossing/painting of Danger sign of size not less than 10cms x 7.5cms with letter and conventional skull and bones in single red color on front face of kiosk box complete all as directed. The quoted rate also includes cost for material & repalcement of 4 sqmm multistranded twincore aluminium cable ISI marked from overhead conductor to junction box and replacement of 3 core copper cable of 1.5 Sqmm ISI marked from junction box to security light length as per required at site. Make-Syntex/Supreme/Hensal |
| 22 | S & F in replacement of GI brackets for fixing LED street light fitting fabricated out of GI tubing 40 mm dia, medium grade,1.2 mtr long , bend to 120 degree shape by cutting, welding and well finishing including MS clamp of flat iron of size 32 x 4 mm -02 Nos complete for steel poles / PCC pole as per site requirement with nut, bolt & washers for fixing of GI bracket complete all as specified and directed. |
| 23 | M&L for switch air break gang operated triple pole polymer type, mechanically operated mounted onHT insulators (12 insulator type) and MS steel framewith operating mechanism worked from ground level with 11 KV insulation for current rating up to 200 amps 11000 volts with locking arrangement, MS clamps, nuts, bolts and washers etc also incl drop out expulsion type fuse, single pole up to 25 Amps, 11000 volts fuse barrels, incl two coats of aluminium paint over a coat of red oxide primer on MS work complete all as specified and directed. |
| 24 | Supply and fix lightning arrestor expulsion type complete with all fittings, transmission, 11 KVclass, discharge capacity 65 KA complete all as specified and as directed |
| 25 | S & F and replacement of cross arms, bracing, supports clamps and back plates fabricated from structural steel sections incl nuts & bolts, washers, welding bending cold or hot, drilling holes for bolts in any shape or size and inclusive of one red oxide primer coat, one under coat and one finishing coat of synthetic enamel paint complete all as specified and directed |
| 26 | M&L for earthing complete with galvanised steel earth plate electrode of size 600X600X6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.50 mtr below the ground level connected to galvanised iron strip of 32 x 6 mm as earth lead by means ofbolts nuts check nuts & washers of galvanised iron or steel ,surrounded by charcoal of coke and salt,water pipe 20mm bore GI medium grade with funnel and wire mesh,and making chamber of PCC (1:4:8) type D-2 using 40 mm graded stone aggregate and coping shall be in PCC(1:3:6) type C-1 using 20 mm graded stoneaggregate, 50 mm thick cover of RCC (1:2:4) type B-1 using 20 mm graded stone aggregate, reinforced with 8 mm dia TMTbars @ 80 mm c/c boath ways including excavation and earth work and removal of surplus soil todistance n exc 50 m complete all shown in electrical plate No 3of SSR part- 2010 complete all as specified and directed.Note :-(i) The cost ofGI earth lead & G Ipipe of 7.50 mtr length for protection of GI wire and excavation work for pit shalldeemed to be included in this item. (ii)Earthing test will be carried out and if desired result not achieved and the earthing will be redone to achieve desired result without any extra payment. (iii)Charcoal dust and commonsaltupto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate. |
| 27 | Supply ,commissioningandtestingfactory madeLTfeeder pillar, outdoortypefloor mounted ,suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated The panel shall be dust and vermin proof, IP 65 class protection and made of3.15 mm CRCA MS sheet and 50x50x5mm thick angle iron base frame work,powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside,both side openingtype, with aprons for cable entry,with double door shutter and locking arrangementand consisting of the followingcomplete all as specified and directed. (a) Aluminiumbus barfour strips 600 Amps ,415 volts,fixed on epoxy insulated with panel fixed horizontally, duly insulatedwithheat shrinkable sleeves in colour code - 01 Set.Incoming:-(b) Incommer MCCB,04 Pole, 400 Amps with ultimate breaking capacity Icu- 36 KA at 415 volts , adjustable type with thermal and magnetic settings conforming to IEC 60947 Part-I/IS-13947 Part-I- 01 No(Ics=Icu=100%)Outgoing:-(c ) Out going MCCB,04 Pole, 250 Amps with ultimate breaking capacity Icu- 36 KA at 415 volts , adjustable type with thermal and magnetic settings conforming to IEC 60947 Part-I/IS-13947 Part-I- 02 Nos(Ics=Icu=100%)(Make :- Havells/L&T/schnider/ABB) (d) MCCB,04 Pole, 160 Amps with ultimate breaking capacity Icu- 36 KA at 415 volts , adjustable type with thermal and magnetic settings conforming to IEC 60947 Part-I/IS-13947 Part-I- 02 Nos(Ics=Icu=100%).(e)Spare way for MCCB 63 Amp 4 way - 01 Nos (g) Analoge type volt meter 0-500 volt- 1Set. (h) Indication lamps R,Y,BLEDtype with 3 Nos– 1 set:- |
| 28 | S&F in replacementtesting , commissioning of outdoor type bus barpanel padestal type weather proof CPRI aproovedMS cubical panelboard made of3 mm CRCA MS sheet outdoor type of size 100 cm x 80 cm x 40 cm, 4 Nos of aluminium bus bar of 300 Amp capacity with MCCB 4 pole of Capacity 200 Amp 25 KA (Ics =Icu=100%) including one coat of redoxide and two coat of enamel paint powder coated, mounted on mild steel channel of suitable size andPCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels,, aluminium bus barchanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator all as specified & directed. LTPanel board should be as per IS/IEC 61439-I: 2011 &IS/IEC 61439-2 : 2011, Type Test certificates for Short Circuit Test, Temperature Rise Test, Di-ElectricProperty Test and Degree of Protection IP-65 at minimum 4000 Amps with Breaking capacity not less than 65KA. ( The contractor should submit all Certificates before executing the job.) |
| 29 | Supply, erecting and fixing in true vertical position, steel tubular swaged pole (410 SP-31) 9.0 mtr long, complete with cast iron base plate, pole cap / finial taper plug, bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire length of pole including 2 coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole shall be provided withtwo coats of aluminium paint overone coat of red oxide primer and incl taking down existing old unserviceable poles complete all as specified and directed. (Numbering of the poles shall be done with synthetic enameled painted letter of shape & size as directed.) Note :- Excavation incl earth work and PCC foundation will be measured and paid separately. |
| 30 | S&F in replacement Factory made sheet metal enclosure (MCCB DB) of CRCA sheet 2 mm thickness suitable for fixingofMCCB 4 pole 415 volts upto 200 Amps with fixing arrangement andcable connection withglands/lugs/thimble packing etc complete all as specified and direcetd. Make- ABB/Havells/L&T/Indo asian/Seimens |
| 31 | Taking down carefully service connectionto be measured seperately ) removing materials for keeping in safe custody or for taking credit (credit for above items should be made as per conditions seperatly) and making good disturbed surface of walls floors etc all as specified and directed. |
| 32 | Taking down carefullyexisting wooden board , Main switch, MCB TPN boxes with MCBs, sheet metal boxes, cut out, etc of any size anycapacity fromboards completeall as specified and as directed. |
| 33 | M&L, sub main wiringwith two single core PVC insulated unsheathed FRLSH confirming to IS 694:2010, multi stranded copper conductor (ISI marked with valid CML No), cable 1100 Volt grade, 6 sqmm size drawn in and includingnon metallic rigid PVC concealed conduit medium grade (ISI marked with valid CML No) not less than 20 mm dia with all fitting & fixing accessories including one run single core PVC insulated unsheathed 6 Sqmm FRLSH confirming to IS 14930 (Part-I) 2001, copper conductor (ISI marked with valid CML No) colour code as a earth continuity and connected upto DB complete all as specified and directed.(NOTE: (i) Two run of single core PVC cable with one run of earth conductor and conduit shall be measured as one unit and the quoted rates shall be deemed to be inclusive for cutting chasesin wall/pillars/columns etc. including taking out old sub main wiring any type of any description for concealing the conduits to required depth & making good the disturbed surface in cement mortar 1:4 including finishing the surface with putty to match with the existing surface. |
| 34 | S&F TPN DB-DPX 125 MCCB DBs 4 way Double door with provision for DPX 125 MCCB andas incomer and SP/TP MCBs as out going no of modules DPX 125+12, concealed Complete all as specified and as directed. Make:- ABB / Havells / HPL / L&T |
| 35 | Supply and fix MCCB having breaking capacity of of 16 KA 415V, 4 pole having rating capacity of 63 Amp 100% ICU complete all as specified and as directed.Make:- ABB / Havells / HPL / L&T |
| 36 | Supply and fix MCCB having breaking capacity of of 16 KA 415V, 4 pole having rating capacity of 100 Amp 100% ICU complete all as specified and as directed.Make:- ABB / Havells / HPL / L&T |
| 37 | S&F MCB double pole and neutral 40 Amp/63 Amp 240 V ,10KA , \"C\" series, complete all as specified and as directed with copper lugs, Make:- ABB / Havells / HPL / L&T |
| 38 | S&F MCB single pole 40 to 63 Amps 240 V,10KA, \"C\" series,complete all as specified and as directed.Make:- ABB / Havells / HPL / L&T |
| 39 | S&F MCB single pole 6 to 32 Amps 240 V,10KA, \"C\" series,complete all as specified and as directed.Make:- ABB / Havells / HPL / L&T |
| 40 | M&L pipe galvanised iron of size 40 mm dia, light grade ISI marked, complete with fittings laid in trenches/ fixed with poles etc as protection to cables complete as ditrected by Engineer in Charge |
| 41 | M&L for earthing completewith galvanisedsteelearth plateelectrode of size 600 mm x 600 mm x 6 mm thickweithing not less than 17.5 Kg buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below ground level, connected to galvanized earth lead wire 4.00 mm dia by means of bolts nuts check nuts & washers of galvanized iron or steel , procteded by GI pipe 15 mm bore( light grade)and watering pipe 20 mm bore GI pipe(light grade) andchamber of pcc 1:4:8 type D2 using 40 mm graded stone aggregate and coping shall be in PCC 1:3:6 type C1 using 20mm graded stone agg.50 mm thick cover of RCC 1:2:4 type B1 using 20 mm graded stone agg. reinforced with 8 mm dia MS tor bar @ 80 mm c/c both ways including excvation and earth work and removal of surplus soil complete all as shown in electrical plate no 3 of SSR PT 1, 2009 with charcoal dust and saltcomplete and earth leadconnected to earthing test point (up to main switches, DBs) completeall as specified &testing on completion. NOTE:-(I)item includes the cost of 7.5 mtr length GI pipe for protection for GI earth wire. (ii) item rates includes the cost of 7.5 mtr earth lead GI earth wire. (iii)PCC pit shall be provided at least 500mm away from the pit and not on the earth pit itself and the extra costof additional length of watering pipe,bends,elbow etc shall be deemed included in the unit rate. |