| 1 | Note: (i) Please refer Schedule \"A\" Notes given in tender documents.(ii)The Schedule \"A\" Part-XII is not estimatedby MES and the estimated rate indicated as \"Rs. 0.00\" under Col. 5 signifies this fact only. |
| 2 | LUMPSUM/ OTHER PRE-PRICED PROVISIONAL SCHEDULES OF WORKS |
| 3 | Lump sum price worked out by the contractor for BUILDING WORKS carried forward from Pre-Priced Schedule \"A\" Part-I. |
| 4 | Lump sum price worked out by the contractor for INTERNAL WATER SUPPLYWORKS carried forward from Pre-Priced Schedule \"A\" Part-II. |
| 5 | Lump sum price worked out by the contractor for INTERNAL ELECTRIFICATION WORKS carried forward from Pre-Priced Schedule \"A\" Part-III. |
| 6 | Lump sum price worked out by the contractor for SEWAGE DISPOSALWORKS carried forward from Pre-Priced Schedule \"A\" Part-IV. |
| 7 | Lump sum price worked out by the contractor for AREA DRAINAGE WORKS carried forward from Pre-Priced Schedule \"A\" Part-V. |
| 8 | Lump sum price worked out by the contractor for EXTERNAL WATER SUPPLY WORKS carried forward from Pre-Priced Schedule \"A\" Part-VI. |
| 9 | Lump sum price worked out by the contractor for EXTERNAL ELECTRIFICATION WORKS carried forward from Pre-Priced Schedule \"A\" Part-VII. |
| 10 | Lump sum price worked out by the contractor for ROAD AND PATHWORKS carried forward from Pre-Priced Schedule \"A\" Part-VIII. |
| 11 | Lump sum price worked out by the contractor for PROTECTIVEWORKS carried forward from Pre-Priced Schedule \"A\" Part-IX. |
| 12 | Lump sum price worked out by the contractor for FENCING AND GATE WORKS carried forward from Pre-Priced Schedule \"A\" Part-X. |
| 13 | Lump sum price worked out by the contractor for SITE CLEARANCE & EARTHWORKS carried forward from Pre-Priced Schedule \"A\" Part-XI. |
| 14 | MISCELLANEOUS ITEMS OF WORKS (SCHEDULE \"A\" PART-XII)(A)EXTERNAL ELECTRIFICATION WORKS |
| 15 | Supply, installing, testing and commissioning, factory made outdoor type and tested (prototype having been CPRI type test certified),LT Panel, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars ofAmps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside,front opening type, with aprons for cable entry,with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) lock with 2 keys,internal wiring 2.5 Sqmm with PVC insulated,solid copper conductor, FRLS cables, IS-694marked of adequate size incl the provision of space to accommodate the under mentioned items. The scope of work includes the following:-(109 BDE) |
| 16 | (a) Incoming(i) MCCB 4 pole, 415 volts AC grade, 630 Amps rating and 36/45KA rupturing capacity Adjustable Thermal & Fixed Magnetic - 01 Nos (ii) Aluminium bus bar suitable for900 Amp-04 Nos(iii)Voltmeter 0-500 volts,square,144 mm,digital type, flush pattern with 3way rotary selector switch- 01 Nos(iv) Ammeter size 144 mm,square dial, digital type, flush pattern having dual range suitable for incoming capacitywith three way rotary selector switch with suitable size of LT\"s- 01 No(v) LED Indicating lamps : 01 set of three(vi) Secure 3 Phase, 1 Element, 4 Wire 440 V Digital Power Factor Meter- 01 Nos(vii) Current & Potential Transformer : 01 Nos(b) Outgoing(i) MCCB 4 pole, 415 volts AC grade,250 Amps rating and 25/26 KA rupturing capacity Adjustable Thermal & Fixed Magnetic- 04 Nos (c) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B\", old sizebricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cmabove the nearest road level.Note :(i)All out going feeders shall be connected by cable through suitable size gland plate / glands.(ii) The various feeders shall be indicated by 50 mm size lettersin synthetic enamel white paint. |
| 17 | Supply, installing, testing and commissioning, factory made outdoor type and tested (prototype having been CPRI type test certified),LT Panel, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars ofAmps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside,front opening type, with aprons for cable entry,with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) lock with 2 keys,internal wiring 2.5 Sqmm with PVC insulated,solid copper conductor, FRLS cables, IS-694marked of adequate size incl the provision of space to accommodate the under mentioned items. The scope of work includes the following:-(16 ASSAM,20 Grn ) |
| 18 | (a) Incoming(i) Aluminium Busbar suitable for540 Amps - 04 Nos(ii) MCCB 4 pole, 415 volts AC grade, 500 Amps rating and 36/45KA rupturing capacity Adjustable Thermal & Fixed Magnetic - 01 Nos.(iii)Voltmeter 0-500 volts,square,144 mm,digital type, flush pattern with 3way rotary selector switch- 01 No(iii) Ammeter size 144 mm,square dial, digital type, flush pattern having dual range 500 amps with three way rotary selector switch with suitable size of LT\"s- 01 No(iv) LED Indicating lamps : 01 set of three(v) Secure 3 Phase, 1 Element, 4 Wire 440 V Digital Power Factor Meter .01 Nos(vi) Current & Potential Transformer : 01 Nos(b) Outgoing(i) MCCB 4 pole, 415 volts AC grade, 200 Amps rating and 25/26KA rupturing Adjustable Thermal & Fixed Magnetic - 04 Nos (c) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B\", old sizebricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cmabove the nearest road level.Note :(i)All out going feeders shall be connected by cable through suitable size gland plate / glands.(ii) The various feeders shall be indicated by 50 mm size lettersin synthetic enamel white paint. |
| 19 | Supply, installing, testing and commissioning, factory made outdoor typeand tested (prototype having been CPRI type test certified),LT Panel, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars ofAmps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside,front opening type, with aprons for cable entry,with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) lock with 2 keys,internal wiring 2.5 Sqmm with PVC insulated,solid copper conductor, FRLS cables, IS-694marked of adequate size incl the provision of space to accommodate the under mentioned items. The scope of work includes the following:-( Ranna Camp) |
| 20 | (a) Incoming(i) Aluminium Busbar suitable for540 Amps - 04 Nos(ii) MCCB 4 pole, 415 volts AC grade, 500 Amps rating and 36/45KA rupturing capacity Adjustable Thermal & Fixed Magnetic - 01 Nos.(iii)Voltmeter 0-500 volts,square,144 mm,digital type, flush pattern with 3way rotary selector switch- 01 No(iii) Ammeter size 144 mm,square dial, digital type, flush pattern having dual range 500 amps with three way rotary selector switch with suitable size of LT\"s- 01 No(iv) LED Indicating lamps : 01 set of three(v) Secure 3 Phase, 1 Element, 4 Wire 440 V Digital Power Factor Meter .01 Nos(vi) Current & Potential Transformer : 01 Nos(b) Outgoing(i) MCCB 4 pole, 415 volts AC grade, 200 Amps rating and 25/26KA rupturing Adjustable Thermal & Fixed Magnetic - 03 Nos (c) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B\", old sizebricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cmabove the nearest road level.Note :(i)All out going feeders shall be connected by cable through suitable size gland plate / glands.(ii) The various feeders shall be indicated by 50 mm size lettersin synthetic enamel white paint. |
| 21 | Supply, installing, testing and commissioning, factory made and tested (prototype having been CPRI type test certified),LT Panel, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars ofAmps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside,front opening type, with aprons for cable entry,with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) lock with 2 keys,internal wiring 2.5 Sqmm with PVC insulated,solid copper conductor, FRLS cables, IS-694marked of adequate size incl the provision of space to accommodate the under mentioned items. The scope of work includes the following:- (427 ASC) |
| 22 | (a) Incoming(i)Aluminium Busbar suitable for 300 Amps - 04 Nos(i) MCCB 4 pole, 415 volts AC grade, 200 Amps rating and 36/38KA rupturing capacityAdjustable Thermal & Fixed Magnetic- 01 Nos.(ii)Voltmeter 0-500 volts,square,144 mm,digital type, flush pattern with 3way rotary selector switch- 01 No(iii) Ammeter size 144 mm,square dial, digital type, flush pattern having dual range 200 amps with three way rotary selector switch with suitable size of LT\"s- 01 No(iv) LED Indicating lamps : 01 set of three(vi) Secure 3 Phase, 1 Element, 4 Wire 440 V Digital Power Factor Meter .01 Nos(viii) Current & Potential Transformer : 01 Nos(b) Outgoing(i) MCCB 4 pole, 415 volts AC grade, 80 Amps rating and 25/26KA rupturing capacity Adjustable Thermal & Fixed Magnetic - 03 Nos (c) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B\", old sizebricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cmabove the nearest road level.Note :(i)All out going feeders shall be connected by cable through suitable size gland plate / glands.(ii) The various feeders shall be indicated by 50 mm size lettersin synthetic enamel white paint. |
| 23 | Supply, installing, testing and commissioning, factory made and tested (prototype having been CPRI type test certified),LT Panel, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars ofAmps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside,front opening type, with aprons for cable entry,with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) lock with 2 keys,internal wiring 2.5 Sqmm with PVC insulated,solid copper conductor, FRLS cables, IS-694marked of adequate size incl the provision of space to accommodate the under mentioned items. The scope of work includes the following:-(Tammam,906 Fd) |
| 24 | (a) Incoming(i) Aluminium Busbar suitable for 500 Amps - 04 Nos(i) MCCB 4 pole, 415 volts AC grade, 400 Amps rating and 36/45KA rupturing capacity Adjustable Thermal & Fixed Magnetic - 01 Nos.(ii)Voltmeter 0-500 volts,square,144 mm,digital type, flush pattern with 3way rotary selector switch- 01 No(iii) Ammeter size 144 mm,square dial, digital type, flush pattern having dual range 400 amps with three way rotary selector switch with suitable size of LT\"s- 01 No(iv) LED Indicating lamps : 01 set of three(vi) Secure 3 Phase, 1 Element, 4 Wire 440 V Digital Power Factor Meter .01 Nos(viii) Current & Potential Transformer : 01 Nos(b) Outgoing(i) MCCB 4 pole, 415 volts AC grade, 160 Amps rating and 25/26KA rupturing capacity Adjustable Thermal & Fixed Magnetic - 03 Nos .(c) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B\", old sizebricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cmabove the nearest road level.Note :(i)All out going feeders shall be connected by cable through suitable size gland plate / glands.(ii) The various feeders shall be indicated by 50 mm size lettersin synthetic enamel white paint. |
| 25 | Supply and fixing ofFRP looping box of size 155x210x95 mm (HWD) with fuse/6 amps MCB provision and suitable connector for single phase connections loop in and out 10 to 16 sqmm 2 core aluminium armoured cable branch out 1.5 sqmm single core copper pvc insulated cable enclosed in thermoplastic /polycarbonate enclosure which should be shock proof safe IP 66/67 thermoplastic metric size glands ,GI clamps made out of GI flat of size 25mmX 3mm channel including making connections, takng down of old FRP box complete all as specified and directed. |
| 26 | Supply and fixing of LT overhead lines on 9 meter steel poles with XLPE insulated AB cable 3-core X 50 sq mm + 1-core x 35 sq mmincl necessary hanging arrengement all as specified & directed. |
| 27 | Supply and fixing of LT overhead lines on 9 meter steel poles with XLPE insulated AB cable 3-core X 70 sq mm + 1-core x 50 sq mmincl necessary hanging arrengementall as specified & directed. |
| 28 | Shifting of good conditioning DG Set of various capacity and size from exisiting location to Near sub stn of cantt area/Unit area with proper safety to using hydro/JCB/crane etc and disconecting the cable and earth conections , fixing, testing, commisioning and checking the supply etc complete all as specified and directed. |