| 1 | Comprehensive maintenance for a period of 06 (Six) months for Split ACs (Inverter and Non-Inverter) 1.5 / 2.0 TR of Make: BLUESTAR / VOLTAS / LG / O-GENERAL / DAIKIN / VIDEOCON / AMTREX / IFB / HITACHI/ CARRIER OR ANYOTHER MAKEinstalled at various location by carrying out necessary repairs , cleaning filters, adjustment of assemblies , sub-assymblies , check the level of refrigerant , arresting the leakage of any type , replacement of parts, calibration including cleaning of condenser & Evaporator coils fins with mild detergent and descaling of condenser coil for split ACs through any authorised service centre/ agencies as approved by GE,complete all as specified and as directed . |
| 2 | All as per item No 1.0 here-in-before but for Window AC of any make (Inverter and Non-Inverter Type )complete all as specified and as directed by Engr-in-charge . |
| 3 | NOTE :- (Applicable for BOQ Serial item No 1.00 and 2.00) |
| 4 | (i) The contractor shall provide the following comprehensive services arising out of wear and tear of the normal running of split /Window AC and the complete tender is to be carried out in twopart (I&II) . |
| 5 | (ii) PART-I : Preventive and corrective maintenance to be commencedimmediately after commencement of work and to be completed within six months. The Authorised service Engineer ofcertified agencies as approved by GE, shall inspect the equipment for carrying out preventive and corrective maintenence on all the units installed at site . This includes maintenance of all mechanical, electrical and electronics part/sub-assemblies . The preventive maintenence report will be as per the original equipment manufacturer\"s instruction and based on maintenance report if any parts/sub-assemblies defects found shall be replacedand as specified in particular specification . |
| 6 | (iii) PART-II : Preventive and corrective maintenance to be commenced after expiry of six months from the date of commencement of work and to be completed before completion date .The Authorised service Engineercertified agencies shall inspect the equipment for carrying out preventive and corrective maintenence on all the units installed at site . This includes maintenance of all mechanical, electrical and electronics part/sub-assemblies . The preventive maintenence report will be as per the original equipment manufacturer\"s instruction and based on maintenance report if any parts/sub-assemblies defects found shall be replacedand as specified in particular specification andin off season i,e during the lien period of winter , the authorised service Engineer ofcertified agencies shall attend the Air-conditioner units for major attentions and keep the equipment ready for use for the next summer . |
| 7 | (iv) The Authorised service Engineer ofcertified Agencies will carry out all breakdown maintenence after receving information(written or oral ) from GE (AF) Kalaikunda officials or their representatives . Theauthorised service representativewill carry out the required repairs of the unit and appraise GE , Engineer-in-charge and JE the status of the breakdown of repair at site . No payment shall be made on account of any breakdown service during comprehensive maintenance period . |
| 8 | (v)The service Engineer will be called in case of any breakdown and the same shall be attended within 24 hrs of lodging of complaint, failing which a penal recovery as specified in particular as specified in particular specification will be recovered from the outstanding dues to the contractor. |
| 9 | (vi) Cost of minor items like taflontape , metal washers, fibre/rubber washers, screws, small nuts& bolts,LPG gas for welding work,copper brazing stick,charging pipe etc shall be deemed to be inclusive of the quoted rate. |
| 10 | (vii) All other spares such as compressor , condenser, PCB , ODU fan motor , IDU motor , magnetic contact ,strainer , fan blade ,copper pipe , outdoor bracket , Insulation foam with wrapping tape , air filter , Gas charging etc shall be measured and paid separetely as a supply only under relevant item of this schedule. |
| 11 | (viii) The contractor shall maintain service reports for all visit & breakdown visits & copy of the same will be submitted to the Engineer-in-charge . |
| 12 | M&L for Shifting / re-locateof split type AC by taking outAC from MES yard or from existinglocation to the new location by taking it after taking down, closing the opening of old location withcement mortar cement mortor(1:3),white wash to match with the existing colour of the site & makingholes in brick wall at new location and fine finishing withcement mortar white wash etcto match with the existing colour ofthe site installation & commissioning after replacement of insulation of suction & discharge line,charging,electrical connection only. Note:-Existing/ new location will be inDomestic area/DDK range as per site requirement.) |
| 13 | S&F in repair Split AC indoor unit not less than 1.5 TR suitable forexisting make and model of outdoor unit asper OEMs specificationssuitable for R-22/R-32/R-410 gas, 220-240 volts, single phase, 50 Hz including taking down old u/s indoor unit and depositing the same in MES Store complete all as specified and directed by Engr-in-charge. Make of indoor unit shallbe in Voltas / Daikin / Blue star / IFB / LG / O General |
| 14 | S&F in repair Split AC outdoor unit not less than 1.5 TR suitable forexisting make and model of indoor unit asper OEMs specificationssuitable for R-22/R-32/R-410 gas, 220-240 volts, single phase, 50 Hzincluding taking down old u/s indoor unit and depositing the same in MES Store complete all as specified and directed by Engr-in-charge. Make of outdoor unit shallbe in Voltas / Daikin / Blue star / IFB /LG / O General |
| 15 | Supply only in repair Rotary compressor suitable for Split / Window AC of capacity 1.5 TR, suitable for R-22/R-32/R-410 gas , 220-240 volts, single phase, 50 Hz. as per OEMs specifications, complete all as specified and directedMAKEAs per existing OEM . |
| 16 | Supply only in repair Rotary compressor suitable for Split / Window AC of capacity 2.0 TR, suitable for R-22/R-32/R-410 gas , 220-240 volts, single phase, 50 Hz. as per OEMs specifications, complete all as specified and directedMAKEAs per existing OEM . |
| 17 | Supply only in repair Reciprocating compressor suitable forSplit / Window AC of capacity1.5TR. suitable for R-22/R-32/R-410 gas, 220-240 volts, single phase, 50 Hz. as per OEMs specifications, complete all as specified and directedMAKEAs per existing OEM. |
| 18 | Supply only in repair Reciprocating compressor suitable forSplit / Window AC of capacity2.0TR. suitable for R-22/R-32/R-410 gas, 220-240 volts, single phase, 50 Hz. as per OEMs specifications, complete all as specified and directedMAKEAs per existing OEM. |
| 19 | Supply only Inverter compressor 1.5/2.0 TR of existingmake and model as specified and as per OEM specification complete all as specified and as directed .Note : Contractor will not be allowed to take the sample of the compressor from the site for purchasing from Authorised service center , only make andmodel No of the unit will be provided . |
| 20 | Supply only in repair Magneting Relay coil for splitAC\"s 1.5/2.0 TR as per existing make , complete all as specified and directed. |
| 21 | Supply only in repair Rubber bush for indoor motor of split AC\"s 1.5/2.0 TRInverter/Non-inverter as per existing make and model , complete all as specified and directed. |
| 22 | Supply only in repair Air filter for Split / Window type AC\"s (suitable for AC of capacity 1.5/2 TR) as per OEMs specifications, complete all as specified and directed |
| 23 | Supply only in repair anti corrosive outdoor bracket for split type AC with aluminium hexagonal screws and all fittings as per existing make and model, complete all as specified and directed |
| 24 | Supply only in repair blower motor, 220-240 V, 50 HZ,30-80Watt(as per existing), 4 pole insulation class -B, IP22as per existing make and model suitable for window AC / Split AC Outdoor of any make and 1.5/2 TR capacity . Note : Contractor will not be allowed to take the sample of the PCB from the site for purchasing from Authorised service center , only model No of the unit will be provided . |
| 25 | Supply only in repair outdoor DC motor for split AC Inverter type of any make and model as specified of capacity 1.5/2.0 TR as per existing make complete all as specified and as directed .Note : Contractor will not be allowed to take the sample of the PCB from the site for purchasing from Authorised service center , only model No of the unit will be provided . |
| 26 | Supply only in repair Indoor motor (AC/DC motor) for Non-inverter type split AC of any make and model as specified of capacity 1.5/2.0 TR of existing make complete all as specified and as directed .Note : Contractor will not be allowed to take the sample of the PCB from the site for purchasing from Authorised service center , only model No of the unit will be provided . |
| 27 | Supply only in repair Indoor motor (DC motor) for Inverter type split AC of any make and model as specified of capacity 1.5/2.0 TR of existing make complete all as specified and as directed . |
| 28 | Supply onlyin repair blower/runner drum as per existing make and model as specifiedfor window /splitAC Inverter/non-inverter type of any make and model of cap 1.5/2 TRof existing make complete all as specified and as directed . |
| 29 | Supply only in repair Condenser coil copper size of 20x30 for suitable for Split type AC 1.5 /2.0 TR. including taking down of defective coil as per OEMs specifications,complete all as specified and as directed . |
| 30 | Supply only in repair Condenser coil copper size of 26x32 for suitable for Split type AC 1.5 /2.0 TR. including taking down of defective coil as per OEMs specifications,complete all as specified and as directed . |
| 31 | Supply only in repair Condenser coil copper size of 22x32 for suitable for Split type AC 1.5 /2.0 TR. including taking down of defective coil as per OEMs specifications,complete all as specified and as directed . |
| 32 | Supply only in repair Condenser coil copper for suitable for Window type AC 1.5 /2.0 TR. as per OEMs specifications, complete all as specified and as directed . |
| 33 | Supply only in repair Fan Blade suitable for Window AC type AC 1.5 /2.0 TR as per OEMs specifications,complete all as specified and as directed . |
| 34 | Supply only in repair Fan Blade suitable for Split type AC outdoor 1.5 /2.0 TR as per OEMs specifications,complete all as specified and as directed . |
| 35 | Supply onlyin repair PCB KIT with remote for inverter typeSplit AC indoor / outdoor unit 2.0 TR suitable forexisting make and modelof Split AC suitable for R-22/R-32/R-410 gas, 220-240 volts, single phase, 50 Hz including taking down old u/s PCB Kitasper OEMs specifications complete all as specified and directed by Engr-in-charge. Note : Contractor will not be allowed to take the sample of the PCB from the site for purchasing from Authorised service center , only make and model No of the unit will be provided. |
| 36 | Supply onlyin repair PCB KIT with remote for inverter typeSplit AC indoor / outdoor unit 1.5 TR suitable forexisting make and modelof Split AC suitable for R-22/R-32/R-410 gas, 220-240 volts, single phase, 50 Hz including taking down old u/s PCB Kitasper OEMs specifications complete all as specified and directed by Engr-in-charge.Note : Contractor will not be allowed to take the sample of the PCB from the site for purchasing from Authorised service center , only make and model No of the unit will be provided . |
| 37 | Supply only in repair Remotesuitable for split type AC 1.5/2 TR indoor unit as per OEMs specifications |
| 38 | Supply and fixing in replacement of Printed Circuit Board suitable for 1.5/2.0 TR CapacitySplit Unit Air Conditioners Non-inverter typeincluding remote as per existing make and model complete all as directed by Engr in charge . MAKEAs per existing OEM |
| 39 | Supply and fixing in replacement of Printed Circuit Board suitable for 1.5/2.0 TR CapacitywinmdowAir Conditioners including remote as per existing make and model complete all as directed by Engr in charge . MAKEAs per existing OEM |
| 40 | Supply only in repair Copper refrigerent piping size 1/4\" suitable for Split AC of any type of capacity 1.5/2.0 TR complete all as specified and as directed . |
| 41 | Supply only in repair Copper refrigerent piping size 1/2\"suitable for Split AC of any type of capacity 1.5/2.0 TR complete all as specified and as directed . |
| 42 | Supply only in repair Copper refrigerent piping size 5/8\"suitable for Split AC of any type of capacity 1.5/2.0 TR complete all as specified and as directed . |
| 43 | Supply only in repair Copper refrigerent piping size 3/8\"suitable for Split AC of any type of capacity 1.5/2.0 TR complete all as specified and as directed . |
| 44 | Supply only in repair Capillary tube suitable for cooling appliances asper OEMs specifications. |
| 45 | Supply only in repair temperature sensor suitable for Split AC Inverter/Non-inverter type of any make and model of existing make complete all as specified and as directed . |
| 46 | Supply only in repair Nitrile Rubber insulation for AC pipe of size 5/8\" , 1/2\", 1/4\",3/8\" along with self adhesive white monsoon proof wrapping tape 48mm width for insulation of ACcomplete all as specified and directed . Note : 1 RM of Nitrile Rubber Insulation and 1 RM of Monsoon proof wrapping tape together shall measured as one unit ( i,e1 RM ) for payment purpose . |
| 47 | Supply only in repair Flare Nut of any size (upto 1 inch) asper existing make and model of Split AC complete all as specified and directed |
| 48 | Supply only in repairDead Nut copper/brass of various size for Split AC of existing make and model complete all as specified. |
| 49 | Supply only in repair Strainer (capillary)two way/single way/three wayas per existing make and model complete all as specified and as directed . |
| 50 | Supply only in repair Capacitor aluminium body 45 Mfd 450 V AC 50 HZ as per OEMs specifications, complete.Make - GC/Universal/Havells/Epcos/Tibcon |
| 51 | Supply only in repair Capacitor aluminium body 45 Mfd+6 450 V AC 50 HZ as per OEMs specifications, complete.Make - GC/Universal/Havells/Epcos/Tibcon |
| 52 | Supply only in repair Capacitor aluminium body 50 Mfd450 V AC 50 HZ as per OEMs specifications, complete.Make - GC/Universal/Havells/Epcos/Tibcon |
| 53 | Supply only in repair Capacitor aluminium body 36 Mfd450 V AC 50 HZ as per OEMs specifications, complete.Make - GC/Universal/Havells/Epcos/Tibcon |
| 54 | Supply only in repair Capacitor aluminium body 4 Mfd±5% 440 V AC 50 HZ as per OEMs specifications, complete.Make - GC/Universal/Havells/Epcos/Tibcon |
| 55 | Supply only in repair Capacitor aluminium body1.5 Mfdrectangular type,±5% 440 V AC 50 HZ as per OEMs specifications, complete.Make - GC/Universal/Havells/Epcos/Tibcon |
| 56 | Supply only in repair Capacitor of capacity 3.15mfd,±5% 220V,AC as per OEMs specifications, complete.Make - GC/Universal/Havells/Epcos/Tibcon |
| 57 | Supply only in repair Capacitor of capacity 2mfd,±5% 220V ,AC as per OEMs specifications, complete.Make - GC/Universal/Havells/Epcos/Tibcon |
| 58 | Supply only in repairflexible PVC heavy duty with wire meshas per sample Water drain pipe suitableupto 20mm for Split AC complete all as specified and directed. Make - AS per sample and ISI Specification. |
| 59 | Supply & charging R-134A gasto maintain the required cooling effect as and when required in the Water cooler/Refrigerator charging (Charging costing including in this item.) Note: The gas should bein a cane sealed packed of 500/1000 gm |
| 60 | Supply & charging R-600a Iso-butane gasto maintain the required cooling effect as and when required in the Water cooler/Refrigerator charging (Charging costing including in this item.)Note: The gas should bein a cane sealed packed of 500/1000 gm |
| 61 | Supply & charging R-22to maintain the required cooling effect as and when required in the Water cooler/Refrigerator charging . Note : (i) Rate for Charging shall deemed to be included in the unit quoted rate . (ii) Refrigerant brought by the contractorin sealed cylinder shall have to submit test report from any authorised Govt Lab .No sealed refrigerant cylinder shall be accepted without test report . |
| 62 | Supply & charging R-32to maintain the required cooling effect as and when required in the Water cooler/Refrigerator charging. Note : (i) Rate for Charging shall deemed to be included in the unit quoted rate . (ii) Refrigerant brought by the contractorin sealed packed cane of 500/1000 gm andshall have to submit test report from any authorised Govt Lab . No sealed refrigerant cylinder shall be accepted without test report . |
| 63 | Supply & charging R-410to maintain the required cooling effect as and when required in the Water cooler/Refrigerator charging .Note : (i) Rate for Charging shall deemed to be included in the unit quoted rate . (ii) Refrigerant brought by the contractorin sealed packed cane of 500/1000 gm andshall have to submit test report from any authorised Govt Lab .No sealed refrigerant cylinder shall be accepted without test report . |
| 64 | Supply only for Non return valve for charging gas including taking down complete all as specified and directed by Engr -in-Charge Make : As per sample |
| 65 | S & F in repair single pole and neutral enclosure with two pin and earth,plugand socket , suitable for single phase 240 V,complete with one single pole MCB of capacity 20 amps having `C` charactristic, breaking capacity 10 KA, including industial plug top, complete all as specified and as directed. |
| 66 | S&F16/20 Amp three pin top metal clad suitable for industrial socket including taking down of defective top complete all as specified and directed. |
| 67 | Material and labour in repair for sub main wiring wth 2 runs of 4 sq. mm. (Phase & Neutral ) and one run of 4 Sq. mm. for earth contunity conductor PVC insulated unsheathed FRLSH grade cable with copper conductors multi stranded 1100 V grade confirming to IS-694 drawn through and including surface PVC casing caping ofsize not less than 20 mm , with accessories all as specified and as directed by Engineer -in-charge. NOTE:- (a) 2 runs of 4 Sq.mm. + 1 run of 4 Sq.mm. cable for earth + 1 run of casing caping shall be measured as one unit leangth |
| 68 | S&F in repair PVC insulated PVC sheathed 2.5 sqmm Size 3 corecopper cablecomplete all as specfied and directed . |
| 69 | S&F in repair PVC insulated PVC sheathed 2.5 sqmm Size 4 corecopper cablecomplete all as specfied and directed . |
| 70 | Supply & fixing in repair Condenser coil suitable for Refrigerator of any make and capacityasper OEMs specifications |
| 71 | S&F in repair Cooling coil with door and frame suitable for Refrigerator of any make and capacity asper OEMs specifications |
| 72 | S&F in repair Thermostat switches suitable for Refrigerator of any make and capacityasper OEMs specifications |
| 73 | S&F in repair Gasket set complete suitable for Refrigerator of any make and capacityasper OEMs specifications. |
| 74 | S&F in repair Chiller tray suitable for Refrigerator of any make and capacity:Make - as per sample. Make - as per sample and ISI Specification. |
| 75 | S&F in repair Potential relay suitable for Refrigerator of any make and capacityasper OEMs specifications |
| 76 | S&F in repair Drier suitable for Refrigerator of any make and capacity asper OEMs specifications |
| 77 | S&F in repair Bulb thread/pin type suitable for Refrigerator of any make and capacity of any make and capacityasper OEMs specifications |
| 78 | S&F in repair Bi-Metal with timer suitable for Double door Refrigerator of any make and capacityasper OEMs specifications |
| 79 | S&F in repair Grills for keeping products suitable for Refrigerator of any make and capacityasper OEMs specifications |
| 80 | S&F in repair Compressor suitable for refrigerator 1/8 asper OEMs specifications through any Authorised Service Centre Engineers / Certified Agencies as approved by GE, complete all as specified and directed |
| 81 | S&F in repair Compressor suitable for refrigerator 1/6 asper OEMs specifications throughAuthorised Service Centre Engineers / Certified Agencies as approved by GE, complete all as specified and directed. |
| 82 | S&F Tray for keeping products suitable for Refrigerator of any make and capacity including taking down of defective tray per OEMs specifications through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies as approved by GE, complete all as specified and directed. |
| 83 | Supply & fix in repair CondensorMotor suitable for Deep freezer of any make and capacity asper OEMs specifications |
| 84 | Supply & fix in repair Compressor suitable for Deep freezer asper OEMs specifications |
| 85 | S&F in repair overload protector relay for water cooler / refrigerator of any capacity and make asper OEMs specifications |
| 86 | M&L for repair of PCB Kit for Water Cooler/ Refrigerator/ Deepfreezor of any capacity and make asper OEMs specifications complete all as specfied and directed |
| 87 | S&F Compressor for water cooler as per sample including taking down of defective compressor of any make and capacityinstalled at various locations through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies as approved by GE, includingrefixing the same at the location where directed including making/connecting of water and electric connectioncomplete all as specified and dierected. |
| 88 | Supply & fixing in repairPotential relays suitable for Water cooler of any make and capacity as per OEMs specifications, |
| 89 | S&F in repair motorassemblyof 220-240 V, 50 HZ,30-80Watt(as per existing), 4 pole insulation class -B, IP22ofas per sample suitable for suitable for Water cooler of any make .(Contractor shall provide the new motor as per OEMs specifications, in which it has to be fixed, Make ofwater cooler : Voltas/Bluestar/Shriram/Videocon or any make. Before procurement he will take the approval from Engr-in-Charge for make and model. |
| 90 | S&F in repair Door Gasket suitable for Water cooler of of any make and capacity as per OEMs specifications |
| 91 | S&F in repair Thermostat switch complete suitable for Water cooler / refrigerator of any make and capacity as per OEMs specifications, |
| 92 | S&F in repair Drain pipe for suitable for Water cooler of any make and capacity as per OEMs specifications. |
| 93 | S&F in repair Chromium plated L type/push type self closing tap of stainless steel of any make and capacity as per OEMs specifications, |
| 94 | Supply and fix in replacementVoltage stabilizer for automatic operation , single phase naturally air cooled indoor type & designed for input variation between 170 V to 260 V with output voltage stabilized at 230 V with accuracy of ±2.5% and of capacity 5 KVA with all accessories including taking down old U/S and depositing to MES storecomplete all as specified and directed by Engr-in-charge . |
| 95 | M&L in repair for earthing complete with GI earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly in ground vertical position, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5Mtr below ground level.The earth plate to be connetced with galvanised iron earthing stripof size 32 mm x 6 mm by means of nuts, bolts, chcek nuts and washers made of galvanised iron or steelearthing stripto be protected by galvanised iron pipe 40 mm bore (medium grade) up to ground level and there after with40mm dia HDPE pipe up to test point. Earthing shall be include withproviding funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) up to 90 cm all around earth platefurther filled with60 cm thick Tibba sand Earthing shall also be include for providingconcrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work all as spcified and directed. |