| 1 | PART-I DG SETM&L for Maintenance and servicing of standby DG Set complete including draining out of diesel from tank , cleaningthe tank thoroughlyand refilling the drained out diesel, draining out engine oil from the sump, cleaningthe sump thoroughly and refilling the sump with new engine oil to it’s required level, replacing the fuel filter, lubricating oil filter , checking & cleaning air cleaner , changing air cleaner elements, checking coolant level & make up the same ,drain the fuel filter & water separator, filling the starting batteries with electrolyte/distilled water to maintain the required specific gravity, replacing the unserviceable brass connectors for batteries, cleaning of battery terminals & applying petroleum jelly to battery terminal posts & brass connectors, including replacement ofBelts, checking of exhaust leakage, governor, breathers etc, adjust/set the same for proper functioning of DG Set, checking offuel, oil and water coolantlevel etc, adjusting and keeping the fan belts to the desired tension, tightening all the bolts and nuts to the required torque etc, cleaning the DG Set with accessories asprescribed by the manufacturer and test for satisfactory running of DG set for two hour at connected load and record shall be made in respect of RPM , oil pressure , oil temperature , coolant temperature, voltage , frequency , load current , battery charging , fuel consumption etc complete all as specified and directedfor10/20/25/30 KVA D G setof any (Make as per existing complete all as specified and directed. Note :-(a).Engine oil for refilling shall be measured and paid Separately (b).Coolant for make up shall be measured & paid separately(c).Testing will be carried out in presence of Engineer - in - charge and DHPP consumption shall be entered in PRRB.(d).The Make of Fuel filter , Oil Filter , V belt & component will be as per manufactures recommendations andrate of fuel filter, oil filter, air filter and V belt areinclusive in quoted rate.) (e).The first service of all newly installed DG sets(Make:- Greaves) shall have to be carried out through authorised agency/manufacturer representative only as per OEM recommendations. |
| 2 | Description all as per item No.1 here-in-before but for 40 KVA DG Set |
| 3 | Description all as per item No.1 here-in-before but for 50 KVA DG Set |
| 4 | Description all as per item No.1 here-in-before but for 62.5/63 KVA DG Set |
| 5 | Description all as per item No.1 here-in-before but for 100/110 KVA DG Set |
| 6 | Description all as per item No.1 here-in-before but for 125 KVA DG Set |
| 7 | Description all as per item No.1 here-in-before but for 160/180/200 KVA DG Set |
| 8 | Supply only multi-grade 15W40 lubricating oil for DG Sets as per manufacturer’s recommendation complete all as specified and directed. Make- IOC, Castrol, Hindustan Petroleum |
| 9 | Supply only coolant for radiator as per manufacturer’s recommendations complete all as specified and directed. Make- Castrol, Servo, Cumins |
| 10 | Supply & fixHose pipe set & Clips of water / coolant cooled radiator systemfor following D G set:- |
| 11 | 10/20/25/30KVA DG set |
| 12 | 40 KVA DG set |
| 13 | 50 KVA DG set |
| 14 | 62.5/63 KVA DG set |
| 15 | 100/110 KVA DG set |
| 16 | 125 KVA DG set |
| 17 | 160/180/200 KVA DG set |
| 18 | Repairs & Overhauling of radiator assembly by dismantling from engine transporting to the workshop and removing the sediments and scales, corrosion etc by means of acid, cleaning and high pressure water washing and air cleaning, gas welding / soldering with good quality material for stopping the leakage etc, re-assembling the same with new gaskets and transporting to the site, fixing to the engine with hoses, clips complete to the entire satisfaction of engineer - in - charge as required for following DG Sets. |
| 19 | 10/20/25/30KVA DG set |
| 20 | 40 KVA DG set |
| 21 | 50 KVA DG set |
| 22 | 62.5/63 KVA DG set |
| 23 | 100/110 KVA DG set |
| 24 | 125 KVA DG set |
| 25 | 160/180/200 KVA DG set |
| 26 | Dismantling the water pump of the DG Set taking out the worn out parts, refixing the water pump after replacingwith new water pump repair kit set for following DG set:- |
| 27 | 10/20/25/30KVA DG set |
| 28 | 40 KVA DG set |
| 29 | 50 KVA DG set |
| 30 | 62.5/63 KVA DG set |
| 31 | 100/110 KVA DG set |
| 32 | 125 KVA DG set |
| 33 | 160/180/200 KVA DG set |
| 34 | Dismantling & strip opening of self starter for 12 volt/24 volt inspecting /checking the complete parts & taking out worn/unserviceable parts and making the self starter functional after replacing the new parts. Note: Replacement of new parts shall be measured and paid separately under Sch ‘A’ item No 8/9 below. |
| 35 | Supply & fixing the following items to self starter of existing make :- |
| 36 | Armature assembly 12 volt suitable for 180 AH |
| 37 | Solenoidswitch 12volts |
| 38 | Field coil 12 volts |
| 39 | Bendix penion 12 volts complete |
| 40 | Carbon brush |
| 41 | Supply & fixing the following items to self starter of existing make :- |
| 42 | Armature assembly 24 volt suitable for 180 AH |
| 43 | Solenoidswitch 24volts |
| 44 | Field coil 24 volts |
| 45 | Bendex penion 24 volts complete |
| 46 | Carbon brush |
| 47 | Supply & fix in repairFly wheel ring by removing alternator from enginefor 50KVA to 63 KVA DG set complete all as specified and directed. |
| 48 | Supply & fix in repairFly wheel ring by removing alternator from enginefor 100 KVA to 125 KVA DG set complete all as specified and directed. |
| 49 | Supply & fix in repairFly wheel ring by removing alternator from enginefor 180/200 KVA DG set complete all as specified and directed. |
| 50 | Material and labour for servicing battery charging alternators assembly of DG Set by disconnecting from engine and dismantling the battery charging alternator assembly for following DG set cleaning all accessories replacing with and includingworn out parts like carbon brush, bush/bearing , jumping leads etc, and varnishing all as directed |
| 51 | 10/20/25/30KVA DG set |
| 52 | 40 KVA DG set |
| 53 | 50 KVA DG set |
| 54 | 62.5/63 KVA DG set |
| 55 | 100/110 KVA DG set |
| 56 | 125 KVA DG set |
| 57 | 160/180/200 KVA DG set |
| 58 | Disconnecting and dismantling the fuel injector pump assembly from its original position, overhauling & servicing by cleaning / oiling, servicing of fuel injector pump assembly, removing and replacement with and including fuel injector pump repair kit & fuel pipe including calibration and refixing the same complete all as specified and directed. |
| 59 | 10/20/25/30KVA DG set |
| 60 | 40 KVA DG set |
| 61 | 50 KVA DG set |
| 62 | 62.5/63 KVA DG set |
| 63 | 100/110 KVA DG set |
| 64 | 125 KVA DG set |
| 65 | 160/180/200 KVA DG set |
| 66 | S&F in repair RPM meter of DG set complete all as specified and directed. |
| 67 | S&F in repair oil pressure Gauge on DG set complete all as specified and directed. |
| 68 | S&F in repair oil temperature Gauge on DG set complete all as specified and directed. |
| 69 | S&F in repair water temperature Gauge on DG set complete all as specified and directed. |
| 70 | Supply & fixin repairs fuel filter and Oil Filterfor following D G set:- |
| 71 | 10/20/25/30KVA DG set |
| 72 | 40 KVA DG set |
| 73 | 50 KVA DG set |
| 74 | 62.5/63 KVA DG set |
| 75 | 100/110 KVA DG set |
| 76 | 125 KVA DG set |
| 77 | 160/180/200 KVA DG set |
| 78 | Supply & fix in repairs Air filter for following D G set:- |
| 79 | (a) 10/20/25/30KVA DG set |
| 80 | (b) 40 KVA DG set |
| 81 | (c) 50 KVA DG set |
| 82 | (d) 62.5/63 KVA DG set |
| 83 | (e) 100/110 KVA DG set |
| 84 | (f) 125 KVA DG set |
| 85 | (g)160/180/200 KVA DG set |
| 86 | Supply & fix in repairs V Beltfor following D G set:- |
| 87 | (a) 10/20/25/30KVA DG set |
| 88 | (b) 40 KVA DG set |
| 89 | (d) 62.5/63 KVA DG set |
| 90 | (e) 100/110 KVA DG set |
| 91 | (f) 125 KVA DG set |
| 92 | (g)160/180/200 KVA DG set |
| 93 | S&FPVC insulated stranded copper conductor cable25 Sqmmsingle core, of 2 Mtr length, soldiered with 2 Nos gunmetal battery terminals suitable for 60-180 Ah 12 V DC battery complete all as specified and directed. Make of cable : Plaza / Finolex / Gloster/National/ Polycab |
| 94 | Dismantling asbestos rope from silencer of DG set and supply & fix asbestos rope (8/10mm thick) around silencers complete all as specified and directed. |
| 95 | M&L for preparation of old painted surface of DG Set complete (10/20/25/30KVA DG set) with fuel tank by scrapping / removing old paint / dust etc and painting with two coats of synthetic enamel paint (colour & tint as approved) including calibration of capacity and marking/writing letters as follows:-(a)Tank capacity(b)Tank cleaned on(c) Due date. |
| 96 | Description all as per item No.24 here-in-before but for 40 KVA DG Set |
| 97 | Description all as per item No.24 here-in-before but for 50 KVA DG Set |
| 98 | Description all as per item No.24 here-in-before but for 62.5/63 KVA DG Set |
| 99 | Description all as per item No.24 here-in-before but for 100/110 KVA DG Set |
| 100 | Description all as per item No.24 here-in-before but for 125 KVA DG Set |
| 101 | Description all as per item No.24 here-in-before but for 160/180/200 KVA DG Set |
| 102 | Disconnecting and taking out carefully unserviceable alternator, ofany make and any capacityof DG Sets , dismantling andstrip opening of alternator for servicing, taking outand removing old burnt out winding and rewinding of alternator with existing gauge super enamelled copper wire (Make: Finolex/Atlas / Devi Dayal) as approved by the Engineer-in-Charge with insulatingmaterial such as luminous paper, latherized paper, cotton tape, glass sleeves insulatingVarnish etc , reassembling and fixing the same in position and testing alternator assembly all as specified and directed. |
| 103 | Taking out following defective parts from Alternator ofDG sets and supply and fixing new parts including testingcomplete all as specified and directed :- |
| 104 | AVR unit complete for 40/50 KVA DG Set |
| 105 | AVR unit complete for 62.5/63 KVA DG Set |
| 106 | AVR unit complete for 110 KVA DG Set |
| 107 | AVR unit complete for 200 KVA DG Set |
| 108 | Terminal plate |
| 109 | Silicon Rectifier assemblywith metallic plate as existing covered with thin layer of selenium and insulted nut bolt , control wiring soldering complete suitable for 10KVA to 200 KVA DG Set |
| 110 | Field excitation unit three phase 415 Vcomplete suitable for 10KVA to 200 KVA DG Set |
| 111 | Flexible rubber coupling star typecapacity alternatorcomplete suitable for 10KVA to 200 KVA DG Set |
| 112 | Carbon brushes set of fourcomplete suitable for 10KVA to 200 KVA DG Set |
| 113 | Slip rings complete suitable for 10KVA to 63 KVA DG Set (Four rings) |
| 114 | Slip rings complete suitable for above 110KVA DG Set (Four rings) |
| 115 | Taking down and repair to self starter by taking out defective parts and replacement of armature, field coils, carbon bush, pinion, shocker arm, bearing complete including testing allfor complete suitable for 30/40/50/62.5/63/100/110/125/160/180/200 KVA DG Set complete all as specified and directed |
| 116 | Taking down and repair to flexible fuel pipe by taking out defective and replacement of flexible fuel pipe of 5 Mtr length including end benja nut, bolts etc complete all as specified and directed. |
| 117 | Taking down and repair to ignition switch push button by taking out defective and replacement of ignition switch push button of all type as specified and directed |
| 118 | Material and labour for reconditioning 12 V 180 AH, 25 plates Batteries including replacement with new parts such as –ve & +ve plates, PVC separators, terminal post, Acid and distilled water etc making in serviceable conditions, all as specified and directed. |
| 119 | Material and labour for reconditioning 12 Volts 150/100 AH, 17 Plate battery including replacement with new parts such as –ve & +ve plates, PVC separators, terminal post, Acid and distilled water etc making in serviceable conditions, all as specified and directed. |
| 120 | S & F in repairsbrass terminal for batteries all as directed including taking out and removing existing unserviceable terminals complete all as specified and directed. |
| 121 | PART-II AMF PANELMaintenance & Servicing ofAMF panel of any description and in any position, of 30 KVA to 63 KVA capacity DG set & opening of AMF Panel, checking AC/DC circuits, Tightening of all Power / control wiring connectionand replacement of unserviceable control wiring with 1.5 Sqmm, single core, copper conductor, flexible, PVC insulated, unsheathed cablesuitable up to 1100 volts confirming to IS-694, taking out, removing and replacement of unserviceable parts / spares / items, reassembling the panel & fixing the same in position and testing the AMF panel on full load aftercompletion of repairs complete all as specified and directed. Note : (i) The quoted rates of the contractor are deemed toinclude forfixing the serviceable parts in position and replacement of unserviceable parts with new parts.The new replaced parts shall bemeasured and paid for separately under appropriate item of Sch `A’ as `supply only ‘ but quoted rates are inclusive of replacement of small/minor parts such as nuts, bolts, washers/lugs/gasketsetc |
| 122 | Descriptionall as per item No. 33 above but AMF panel of 100 KVA to 125 KVA capacity |
| 123 | Description all as per item No. 33 above but AMF panel of 200 KVA capacity |
| 124 | Supply only the following spare parts components of AMF Panels repaired under sch \"A\" item No 33, 33.01 to 33.02above complete all as specified and directed. Note :-Fixing and testing element of the following items is deemed to be included in the quoted rate by the contractor for respective schedule\"A\" item No No 33, 33.01 to 33.02above :- |
| 125 | Power Contactor fourpole AC3 rating of 325 Amps , 415 Volts |
| 126 | Power Contactor three pole AC3 rating of 115 Amps , 415Volts |
| 127 | Power Contactor three pole AC3 rating of 100 Amps , 415 Volts |
| 128 | Power Contactor four pole AC3 rating of 50 Amps , 415 Volts |
| 129 | Power Contactor single pole AC3 rating of 10 Amps , 415 Volts |
| 130 | Power Contactor three pole AC3 rating of 32 Amps , 415 Volts |
| 131 | Pla relay 12/24 Volts DC, 11pin, 2 change over, |
| 132 | Pla relay 12 Volts DC, 9 pin, 2 change over, |
| 133 | Ammeter 0-200 Amps, 96mm X 96mm, digital type with three way ON / OFF rotary type selector switch, suitable for existing CTs of class 1.0 |
| 134 | Ammeter 0-100 Amps, 96mm X 96mm, digital type with three way ON / OFF rotary type selector switch, suitable for existing CTs of class 1.0 |
| 135 | Voltmeter 0-30 Volts, 96 mm X 96mm, digital type for measuring DC supply. |
| 136 | Voltmeter 0-500 Volts, 96 mm X 96mm, digital type of accuracy class 1.0, 3 phase for measuring AC supply, with and including suitable rotary type selector switch. |
| 137 | Frequency meter 40-99.99 HZ with selector switch, 96mm X 96mm digital type. |
| 138 | Under voltage relay suitable for 3 phase 415 volts, AC supply |
| 139 | Engine starting relay with sequence timer & Master timer suitable for 12 / 24 Volts DC supply. |
| 140 | Electronic timer, type ET-100, suitable of 240 Volts, 50 Hz, AC supply, for0 -10 seconds . |
| 141 | Electronic DC timer suitable for 12/24 Volts DC supply, for 0-60 seconds. (on delay). |
| 142 | Electronic timer, suitable of 240 / 415 Volts, 50 Hz, AC supply, for0-60 seconds (OFF delay). |
| 143 | Rectifier 4 plates single phase having charging rate 15–20 Amp per minute for 12 Volts DC battery charge. |
| 144 | Selector switchfor volt meters / Ammeter. |
| 145 | Indicating lamps neontype with holderfor 12 / 24 volts DC supply |
| 146 | Battery Charging transformer 0 – 10 Amperes, 12 Volts DC tapping0-12-18-24 Volts. |
| 147 | MCB Tripel pole 240 volts 10 KA, rating 6 to 32 Amps ‘C’ series. |
| 148 | S&F in replacement of aluminium bus bar including drilling holes as required, including new GI nut, bolts and washers of shape, size & section as per site requirement to be fixed in feeder pillar box / panel board and insulation of bus bar with PVC tape and making connection with existing system using new lugs complete all as specified and directed. |
| 149 | Dismantling existing unserviceable MCCBs of any capacity and make from LT panels/ AMF Panel after disconnecting all the electrical connections all as specified and directed |
| 150 | Supply and fixing MCCB,Three Pole, 415 V all as specified and directed for following Amps & breaking capacity 25 to100 Amps, 16 KAall as specified and directed |
| 151 | Supply and fixing MCCB,Three Pole, 415 V all as specified and directed for following Amps & breaking capacity125 Amps, 16 KAall as specified and directed |
| 152 | Supply and fixing MCCB,four Pole, 415 V all as specified and directed for following Amps & breaking capacity 160 Amps, 36 KA |
| 153 | Supply and fixing MCCB,four Pole, 415 V all as specified and directed for following Amps & breaking capacity200 Amps , 36 KA |
| 154 | Disconnecting and dismantling old unserviceable change over switch of any capacity and make from any position all as specified and directed. |
| 155 | Supplying, Fixing, jointing and testing ON LOAD change over switch (open execution), 3 pole, 415 volts of current rating 400 Amps. |
| 156 | Supplying, Fixing, jointing and testing ON LOAD change over switch (open execution), 3 pole, 415 volts of current rating 250 Amps |
| 157 | Supplying, Fixing, jointing and testing ON LOAD change over switch (open execution), 3 pole, 415 volts of current rating 100 Amps |
| 158 | S&F Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicatedsituation for loop earthing etc. as required 32x6mm galvanised iron or steel wire complete all as specified and directed. |
| 159 | Excavation in trenches in soft & loose soil not exceeding 1.5 metre deep and not exceeding 1.5 m width and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes etc.all as specified and directed including removing cable protection PCC covers/ bricks & stacking serviceable covers / bricks for reuse and disposal of unserviceable covers within 50 m all as specified and directed. Note : Excavation shall be made carefully in order to avoid damage of existing cables and protection covers |
| 160 | Returning, filling in including spreading, levelling, watering and well ramming in layers of25 cm thickafter the cables etc. are laid, jointed & tested complete all as specified and directed. |
| 161 | Removal of surplus excavated spoil not exceeding 50 Mtr distance and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 162 | Supplying & Laying Sub Class `B’ bricks old size with axis of the bricks perpendicular to the axis of the cable as in cable protection all as specified and directed. |
| 163 | Material & labour for sand filling with clean dry find sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed NOTE:- For measurement purpose punned thickness shall beconsidered as per clause 19.75 of SSR Part-I |
| 164 | Preparation of the old decorated existing external and internal steel surfaces of feeder pillar boxes/panels/ boards of any description and in any position including removal of disintegrated & deteriorated paint either by hand scrapping or by blow lamps, applying necessary filler coat and stopping as required and applying two coats of synthetic enamelled paint (grey in colour)with using spray machine on old prepared surfaces complete all as specified and directed.Note :Rates quoted by the contractor are deemed to include for writing the MES /SM No and other relevant details with paint in the pattern and style as approved by the Engineer-in-Charge |
| 165 | Disconnecting ,taking out and removing from trenches/ducts/sleeve/on pole/wall etc existing LT UG XLPE insulated,armouredcable of any description, any size/core and in any position complete all as specified and directed for the following sizes of cable :- Note: Earth work shall be measured & paid separately under respective item. |
| 166 | 50 Sqmm 3.5 Core |
| 167 | 35 Sqmm 3.5 Core |
| 168 | 25 Sqmm 3.5 Core |
| 169 | Supplying, laying, jointing & testing XLPE insulated & PVC sheathed armoured LT cable, 1100 volts grade heavy duty with aluminium conductor of the following sizes laid in trenches/pipe/fixed on the wall etc complete all as specified and directed. |
| 170 | 50 Sqmm 3.5 Core |
| 171 | Preparation of the old decorated existing external and internal steel surfaces of feeder pillar boxes/panels/ boards of any description and in any position including removal of disintegrated & deteriorated paint either by hand scrapping or by blow lamps, applying necessary filler coat and stopping as required and applying two coats of synthetic enamelled paint (grey in colour)with using spray machine on old prepared surfaces complete all as specified and directed.Note :Rates quoted by the contractor are deemed to include for writing the MES /SM No and other relevant details with paint in the pattern and style as approved by the Engineer-in-Charge |
| 172 | 25 Sqmm 3.5 Core |
| 173 | Supply, laying & fixing in replacement GI light grade pipes of size 80 mm Dia for cable protection laid in trenches/floor/roof and on the walls, with all accessories, complete all as specified and directed. |
| 174 | Supply, laying & fixing in replacement GI light grade pipes of size 50 mm Dia for cable protection laid in trenches/floor/roof and on the walls, with all accessories, complete all as specified and directed. |
| 175 | Disconnection and taking out the turbo charger assembly complete from the Engine of any make of 40 KVAto 63 KVA DG Set, strip opening of turbo charger and replacement of turbo charger repair Kit , assembling the complete part of the turbo charger and fixingto the engine and testing for satisfactory workingcomplete all as specified and directed. |
| 176 | Disconnection and taking out the turbo charger assembly complete from the Engine ofany make of 100 KVA to160 KVA DG Set , strip opening of turbo charger and replacement of turbo charger repair Kit , assembling the complete part of the turbo charger and fixing to the engine the testing for satisfactory workingcomplete all as specified and directed. |
| 177 | Disconnection and taking out the turbo charger assembly complete from the Engine ofany make of 180 KVAto 200 KVA DG Set, strip opening of turbo charger and replacement of turbo charger repair Kit , assembling the complete part of the turbo charger and fixing to the engine the testing for satisfactory workingcomplete all as specified and directed. |
| 178 | S & F in repair electronic type battery charger having capacity input voltage 220V and output voltage 12V complete all as specified and directed. |
| 179 | S&F in repair of electronic type battery charger having capacity input voltage 220V and output voltage 24V complete all as specified and directed. |
| 180 | S&F in repair of battery 12 Volt 180 AH suitable for DG Set complete all as specified and directed. Note:- OEM recommended complete with minimum warranty (36) month shall be submitted to the EIC. |
| 181 | S&F in repair of 12 Volt 150 AH suitable for DG Set complete all as specified and directed.Note:-OEM recommended complete with minimum warranty (36)month shall be submitted to the EIC. |
| 182 | S&F in repair of battery 12 Volt 120 AH suitable for DG Set complete all as specified and directed.Note:-OEM recommended complete with minimum warranty (36)month shall be submitted to the EIC. |
| 183 | S & F in repair governor control unit for electronic governor suitable for DG Sets of capacityupto 125 KVA,OEM recommended complete all as specified and directed. |
| 184 | S & F in repair governor control unit for electronic governor suitable for DG Sets of capacity 160 to200 KVA, OEM recommended complete all as specified and directed. . |
| 185 | S & F in repair DG Set Display control unit forsuitable for DG Sets of capacity 50 to125 KVA,OEM recommended complete all as specified and directed. . |
| 186 | S & F in repair DG Set Display control unit forsuitable for DG Sets of capacity 160 to200 KVA,OEM recommended complete all as specified and directed. . |
| 187 | M&L for repairing of canopy of DG set by carrying outrepairing of door with replacement of broken hinges including nuts, bolts/welding etc as per requirement, cleaning of base of foundation and painting with black paint MS channel with two coats including touching of paint at cannopy where required complete all as specified and directed. |
| 188 | M&L in replacement of complete AMF panel control wiring ofAMF panelOutdoor type by dismantling and disconnecting the existing electrical connection of the existing AMF panel ,totally enclosed, dust and vermin proof, floor mounted , including powder coated with all control wiring , panel shall have provision for termination of UG cable for incoming / outgoing and necessary gland plates including replacement of cable termination with cable glands shall be provided at bottom of the panel suitable for DG set 125 to160 KVA,415V, 3 phase 50 Hz 4 wire system includingreplacement of OEM approved Auto main supply failure monitor (AMF) control relays, voltage & current sensors, supply failure timer, restoration timer control unit incorporating automatic engine start/stop/Auto/manual/test, indicators for load/mains status, Push button for engine start/stop, 200 Amps 4 Pole Power contactors with OLR relay - 02 NosandMCCB 4 Poles 200 Amps 36 KA rating with ics=100%icu with adjustable thermal over load and magnetic short circuit releases - 2 Nos, with replacement of on load change over system of capacity 250 Amps, with replacement ofbusbar having400A rating for phase &Neutral which is duly insulated with proper colour coding , One battery charger in built for charging batteries with 24V 20A SCR Controlled Battery Charger , selector switch and DC voltmeter & Ammeter all as specified and directed by Engineer-in-charge.Note : - 1. The outdoor panel enclosure only will be taken to the workshop for powder coated painting ,welding ,denting . 2. The materials inside the Panel shall be completely replaced with new one as approved make 3. Rewiring ,fixing of spares & complete testing of AMF Panel shall be done at the site only 4. Reconnecting /restoration of the existing connection shall be the contractor\"s responsibility (5) Cost of Foundation work & cleaning the site afterinstallation included in the quoted rate . |
| 189 | M&L in replacement of complete AMF panel control wiring ofAMF panelOutdoor type by dismantling and disconnecting the existing electrical connection of the existing AMF panel ,totally enclosed, dust and vermin proof, floor mounted , including powder coated with all control wiring , panel shall have provision for termination of UG cable for incoming / outgoing and necessary gland plates including replacement of cable termination with cable glands shall be provided at bottom of the panel suitable for DG set 180 to 200 KVA,415V, 3 phase 50 Hz 4 wire system includingreplacement of OEM approved Auto main supply failure monitor (AMF) control relays, voltage & current sensors, supply failure timer, restoration timer control unit incorporating automatic engine start/stop/Auto/manual/test, indicators for load/mains status, Push button for engine start/stop, 200 Amps 4 Pole Power contactors with OLR relay - 02 NosandMCCB 4 Poles 200 Amps 36 KA rating with ics=100%icu with adjustable thermal over load and magnetic short circuit releases - 2 Nos, with replacement of on load change over system of capacity 250 Amps, with replacement ofbusbar having400A rating for phase &Neutral which is duly insulated with proper colour coding , One battery charger in built for charging batteries with 24V 20A SCR Controlled Battery Charger , selector switch and DC voltmeter & Ammeter all as specified and directed by Engineer-in-charge.Note : - 1. The outdoor panel enclosure only will be taken to the workshop for powder coated painting ,welding ,denting . 2. The materials inside the Panel shall be completely replaced with new one as approved make 3. Rewiring ,fixing of spares & complete testing of AMF Panel shall be done at the site only 4. Reconnecting /restoration of the existing connection shall be the contractor\"s responsibility (5) Cost of Foundation work & cleaning the site afterinstallation included in the quoted rate . |
| 190 | DismantlingAsbestos cement (corrugated ted, semi corrugated, etc.) sheets in roof coverings complete all as specified and directed |
| 191 | S&F Pre- painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified |
| 192 | S&F Pre- painted galvalume aluminium zinc coating GI based plain steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified |
| 193 | Dismantling unframed work of timber scantlings 40 sq. cm and over in section, in any position complete all as specified and directed |
| 194 | S&F Steel work in tubular trusses including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to I. S.1161-1979 grade St.-240 complete all as specified and directed |
| 195 | Dismantling posts or struts (wood, steel or R.C.C.) any section, embedded in Concrete, brick work, masonry, etc. including taking out embedded portion and making good disturbed ground, complete all as specified and directed. |
| 196 | Excavating in post holes in soft/loose soil(or similar holes) each n exc 0.5 cum, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, watering and removing surplus soil to a distance n. exc 50 m and making good surface in hard/dense soil complete all as specified and directed |
| 197 | M&L Cement concrete type B1 1:2:4 (20mm graded aggregate ) as in foundation for Posts and Struts all as specified and as directed |
| 198 | S&F,mild steel work as in posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc, flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc, running bars, for chain link fencing including embedding in concrete and similar work conforming to Fe-290 Gde E-165complete all as specified and directed |
| 199 | M&L, two coats of synthetic enamelled paint over a coat of red oxide primer including preparation of new steel/iron surfaces exceeding 10cm width or girth. Complete all as specified and directed |