| 1 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep and getting out in any type soil for layingof pipe lines etc, complete all as specified and directed by Engineer-in-Charge. |
| 2 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm, complete all as specified and directed by Engineer-in-Charge. |
| 3 | Removing excavated material to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 4 | Material and labour for Horizontal Directional Drilling (HDD) / trenchless boring under existing roads, pavements, and hard standings for laying pipelines, including all materials, labour, tools, tackles, plants, machinery, and skilled manpower required, without cutting or damaging the bituminous road surface. The work includes drilling holes and drawing / pushing D.I. pipes up to 150 mm diameter through the bored holes, complete in all respects, as specified and as directed by the Engineer-in-Charge. |
| 5 | Material and labour for cutting of existing bitumen road / CC road / PCC hard standing up to 15 cm depth for laying of pipe lines and making good the disturbed surfaces by providing PCC 1:2:4 type B-1 (using 20mm graded aggregate) after laying of pipes lines and returning filling of soil, complete all as specified and directed.Note:- Excavation and earth work below road / hard standing thickness shall be measured and paid under relevant items. |
| 6 | Material and labour for Cutting CI / DI pipes of size 200 mm bore dia in position for insertion of new tees, branches, etc, complete all as specified and directed by Engineer-in-Charge. |
| 7 | Supplying, laying, jointing, testing and commissioning of 100mm dia, class K-7, Ductile iron pipe (Conforming to IS: 8329-2000), Centrifugally Cast (Spun) Pressure Pipe with Socket and Spigot ends suitable for Push-on-Joint including jointing material, duly applied with Zinc Coating with finishing layer of Bitumen on external surfaces and Cement Motor Lining with Bituminous Seal Coat on internal surfaces complete all as specified and as directed by Engineer-in-Charge. |
| 8 | Material and Labour for DI fittings suitable for DI spigot and socketed pipe of size up to 200 mm bore and any type such as MJ Collar, Bends (any type, radius and angle), tapers any type (straight, bend, increasing, decreasing or double socket etc), Tee pieces (single branch, \"Y\" junction, double branch, cross etc), collars, caps and plugs etc, complete all as specified and directed by Engineer-in-Charge. |
| 9 | Supplying, laying, jointing, testing and commissioning of 100 mm dia, medium grade galvanized iron (GI) pipes conforming toIS:1239 Part-I (2004), including all fittings such as bends, tees, reducers, sockets, unions, nipples, clamps and supports, with threaded joints using approved sealing material, complete with cutting, threading, alignment, fixing in position, fixed to walls and ceilings or laid in floors complete all as specified and as directed by Engineer-in-Charge. |
| 10 | Supplying, laying, jointing, testing and commissioning of 80 mm dia, medium grade galvanized iron (GI) pipes conforming toIS:1239 Part-I (2004), including all fittings such as bends, tees, reducers, sockets, unions, nipples, clamps and supports, with threaded joints using approved sealing material, complete with cutting, threading, alignment, fixing in position, laid in trenches / fixed to walls and ceilings or laid in floors complete all as specified and as directed by Engineer-in-Charge. |
| 11 | Supply and fix Cast Iron Sluice Valve of size 200 mm nominal bore, PN 1.6, as per IS : 14846 with flanged ends, hand wheel operated, stainless steel stem including necessary packing material, GI bolts, nuts and washers etc complete all as specified and directed by Engineer-in-Charge. |
| 12 | Supply and fix Cast Iron Sluice Valve of size 100 mm nominal bore, PN 1.6, as per IS : 14846 with flanged ends, hand wheel operated, stainless steel stem including necessary packing material, GI bolts, nuts and washers etc complete all as specified and directed by Engineer-in-Charge. |
| 13 | Supply and fix Cast Iron Sluice Valve of size 80 mm nominal bore, PN 1.6, as per IS : 14846 with flanged ends, hand wheel operated, stainless steel stem including necessary packing material, GI bolts, nuts and washers etccomplete all as specified and directed by Engineer-in-Charge. |
| 14 | Supply and fix Cast Iron double orifice kinetic air valve with SS floats of size 50mm ISI marked IS:14845 Type DK in PN 1.0 flanged ends with isolating sluice valve ISI marked complete all as specified and directed by Engineer-in-Charge. |
| 15 | Supply and fix Vertical installation, Ball type Foot Valve of size 100 mm nominal bore, with flanged end, CI body and cover, Synthetic Nitrile Rubber Coated Ball, Leaded Tin Bronze Seat, CI Strainer, Carbon Steel fasteners, enamel/epoxy painted complete all as specified and directed by Engineer-in-Charge. |
| 16 | Supply and fix Cast Iron Y type strainer of size 100mm nominal bore, PN 16, Shell Test Pressure - 24 Kg/cm2g, S.S-304 Perforated Sheet Screen dia 3mm, Flanged Ends to BS 10 Table \"F\" including gasket, nuts, bolts, washers etc. complete all as specified and directed. |
| 17 | Supply and fix Horizontal installation, Ball type Non Return Valve (NRV) of size 80 mm nominal bore, PN 1.6 with both ends flanged, CI body and cover, Synthetic Nitrile Rubber Coated Ball, Leaded Tin Bronze Seat and Carbon Steel fasteners, enamel/epoxy painted complete all as specified and directed by Engineer-in-Charge. |
| 18 | Supply, installation, connecting, testing and commissioning of centrifugal pump set suitable for delivering 900 LPM at 45 m total head, complete with CI casing, bronze impeller, stainless steel shaft with renewable shaft sleeve, gland packing type sealing arrangement with lantern ring, and renewable wearing rings, designed for continuous operation; complete with suitably rated AC 3-phase, 415 V ±10%, 50 Hz TEFC squirrel-cage induction motor, IE2 efficiency, NFLP, IP55 protection, Class ‘F’ insulation, mounted on MS fabricated common base frame; direct-coupled through flexible Lovejoy/Fenner type coupling with coupling guard; including foundation bolts, base plate, alignment, grouting, pressure gauge, vacuum gauge, all standard fittings and accessories, and all materials, labour and incidental works required to complete the pump set in all respects in accordance with relevant IS/BS standards for landscaping water sprinkler system including painting with approved colour shade and to the satisfaction of the Engineer-in-Charge. Note : Make and specification of pump sets complete with accessories shall be submitted in duplicate for approval of GE through Engineer-in-Charge before placing order for procurement. |
| 19 | Design, fabricate, supply, installation, testing and commissioning of Indoor Type cubicle panel board compartmentalized suitable for 3 phase 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory having modern fabrication facilities, made out of CRCA sheet steel of 2mm thick with front and rear openable doors with locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-43 degree of protection and including provision of 50mmx50mmx6mm angle iron base frame of suitable size for floor mounting the panel board with a minimum ground clearance of 300mm above FFL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer\"s name plate shall be riveted on panel board. The size of panel board shall be suitable for accommodating and including provision of following switchgear, control gear and accessories including internal wiring with suitable gauge of copper cables complete all as specified and directed:-Note: The Contractor shall submit set of all drawings of the L.T. panel and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations. |
| 20 | (Item No 19.00 Contd--)(i) Bus bar: TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeve insulation mounted on insulators for main bus bar and Continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.(ii) Incomer: (a) MCCB, 63 A, 4 Pole, 25 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal - magnetic release - 01 No(b) Digital Voltmeter with selector switch - 01 Set.(c) Digital Ammeter with selector switch & suitable ratio of CT\"s - 01 set(d) LED Pilot light indication lamps for R,Y,B phases - 01 Set of 03(iii) Outgoing:- (a) Motor Protection Circuit Breaker (MPCB), rotary type with extended ROM for panel mounting, 25 Amps, 3 Pole, 100 KA, with short circuit & overload protection along with FASD starter suitable for up to 15 HP, 3 ph, 415 V, 50 HZ, AC motor including single phasing preventor and LED pilot light indication lamps to indicate motor ON & OFF position - 02 Sets(b)MCB TPN 32 Amps, 10 KA, \"C\" curve - 02 Nos.(c)MCB SPN 32 Amps, 10 KA, \"C\" curve - 02 Nos. |
| 21 | Supply, laying, connecting, testing & commissioning of PVC insulated and PVC Round Sheathed, Multicore Annealed Bare Copper Conductor (flexible) industrial cable of size 4 sqmm, 3 core for Voltage Grade 1100 Volts, Conforming to IS 694:2010 complete laid in duct / cable tray / drawn through pipes etc including provision of lugs, glands, nuts, bolts & washers etc for connecting in LT panel/ motor terminal plate and testing on completion all as specified and directed. |
| 22 | Material & Labour for earthing complete with galvanized iron earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to 25 x 4 mm GI strip as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth wire protected by 40mm dia GI pipe medium grade and connected to Motor / panel board / earthing test point all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and directed. Note :- The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, protection pipe, earth strip up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II. |
| 23 | Supply, installation, jointing, testing, and commissioning of uPVC Schedule 40 pipes and fittings of size 50 mm (2\"), manufactured from unplasticized polyvinyl chloride (uPVC) in accordance with ASTM D1785 (pipes) and ASTM D2467 (fittings). Fittings shall include all necessary elbows, tees, reducers, couplings, unions, adapters, end caps, and specials to complete the installation. Jointing shall be carried out using approved solvent cement and primer or threaded connections with PTFE tape, strictly in accordance with the manufacturer’s recommendations. The quoted rate shall include all accessories, supports, clamps, cutting, wastage, alignment, cleaning, pressure testing, and making good, complete in all respects and to the approval of the Engineer-in-Charge. |
| 24 | Supply and fix uPVC ball valve of size 50 mm (2\") complete all as specified and directed by Engineer-in-Charge. |
| 25 | Supply and fix uPVC ball valve of size 20 mm (3/4\") complete all as specified and directed by Engineer-in-Charge. |
| 26 | Supply and fix uPVC female threaded adapter brass of size 20 mm (3/4\") complete all as specified and directed by Engineer-in-Charge. |
| 27 | Supply, installation, testing and commissioning of heavy-duty gunmetal full-circle impact type water sprinkler ISI marked conforming to IS:12232 (Part-I), suitable for 20 mm (3/4\") male threaded water inlet connection, operating at a pressure range of 2 to 4 kg/cm², with a discharge capacity of 20 to 40 LPM and an effective wetted radius of 12 to 16 meters. The sprinkler shall be complete with stainless steel retraction spring to ensure uniform rotation speed, protection cap, well-balanced swing arm for smooth and uniform rotation, stainless steel spindle and fulcrum pin, and hydrodynamically designed brass dual nozzles with precision inner profile for accurate jet formation and extended throw radius. The item shall include all accessories, fittings, labour, and incidental works required for proper functioning, complete in all respects, as specified and as directed by the Engineer-in-Charge. |
| 28 | Material and labour for constructing valve chamber of internal dimensions 1mtr x1mtr x1.2 meters with 100 mm thick PCC(1:4:8 )type D-2for foundation, brickwallsbuilt in cementmortar(1:4 ), PCC1:2:4 type B1for coping , rendering in cementmortar1:4, 10 mm thick internally and on exposed surfaces externally up to15 cmaboveGL. BottomPCCfloor of the pit should be minimum 30 cms below the bottom surface of Air release valve flange to provide sufficient working space. The Air release valve and other fittings should be housed in center of the pit, the vertices of the pit should be in right angle and champhered .The top cover of the pit shall be made out of 3mm MS sheet with angle iron frame made out of MS angle 50mm x 50 mm x 6 mm with MS hinges two Nos, and locking arrangements duly painted with two coats of water resistant synthetic enameled paint over one coat of red oxide primer complete all as specified and directed by Engineer-in-Charge. |
| 29 | Material and labour for brick masonry with sub class B bricks, straight or curved on plan exc 6mmean radius in cement mortar 1:6 complete as in thrust / support blocks for water pipe lines complete all as specified and directed by Engineer-in-Charge. |
| 30 | Material and labour forrendering 10mm thick cement plaster 1:6 on fair faces of brick work or concrete surfaces finished even and smooth (with out using extra cement) complete all as specified and directed by Engineer-in-Charge. |
| 31 | Material and Labour for PCC 1:2:4 type B1 using 20mm graded stone aggregate with necessary form work etc complete all as specified and directed by Engineer-in-Charge. |