| 1 | Disconnecting all electric connections and taking out carefully existing unserviceable items from LT Panel/ bus bar chamber/ feeder pillar box/ electric poles/ building (any capacity, any type) for carrying out repair work at site including replacement of unserviceable/ defective screw/ nut & bolts/ washers/Lugs/ spreaders/ hinges of doors/ repair to Locks & handles/ Indication lamps/meters/cable glands/Bus Bar (copper/aluminium) etc and refixing the fittings in its original position, testing and commissioning, including removal of bushes, creapers and trimming of branches around the LT Panel/ Bus Bar Chamber/Feeder Pillar/ Electric Poles at site complete all as directed.Note:(a) Cost of minor items like nuts, bolts, washers, insulation tape, fuse wire etc is deemed to be included in the quoted rates. However, any major parts required to rectify the defect shall be measured and paid for separateely under relevant items of schedule.(b) Tools, ladder, vehiclerequired to carry out the work shall be provided by the contractor.(c) Contractor will ensure the safety of the workers employed at his own expenses. |
| 2 | Supply and fixing cable jointing kit for straight through heat shrinkable type joint with jointing material andall connected accessories suitable forXLPE armoured aluminium conductorcable 1100voltsgrade of size 3.5 core 240 to 300 sqmmincluding taking down of old existing joint complete all as directed. |
| 3 | Description all as per item No 2 here in above but cable jointing kit of size 120 to 185 sqmm |
| 4 | Description all as per item No 2 here in above but cable jointing kit of size 50 to 95 sqmm |
| 5 | Supply and fixing in replacement of digital 3 line display multifunction meter having features to measure Voltage, Amperes, power factor, active load etc complete all as directed. |
| 6 | Supply and fixing in replacementof LED indication Lamps (RYB) complete all as directed. |
| 7 | Material and labour for fabricating and fixing in replacement MS CRCA sheet of 3mm thick, the inner shell duly compartmented for each control gear, including powder coating internally and externally entire steel surfaces.All the cover shall be provided with suitable locking arrangements welded with exisiting panel complet all as specified. |
| 8 | Material and labour for fabricating and fixing in replacement aluminium bus bars of exisiting gauge/size duly connected with existing incoming/ outgoing connections complete all as specified. |
| 9 | Supply and fixing in replacement cable glands of size 10 to 16 Sqmm duly connected with existing incoming/ outgoing connections complete all as specified. |
| 10 | Supply and fixing in replacement Cable glands of size 25 to 35 Sqmmduly connected with existing incoming/ outgoing connections complete all as specified. |
| 11 | Supply and fixing in replacement Cable glands of size 50 to 70 Sqmmduly connected with existing incoming/outgoing connections complete all as specified. |
| 12 | Supply and fixing in replacement Cable glands of size 95 to 120 Sqmmduly connected with existing incoming/outgoing connections complete all as specified. |
| 13 | Supply and fixing in replacement Cable glands of size 150 to 185 Sqmmduly connected with existing incoming/outgoing connections complete all as specified. |
| 14 | Supply and fixing in replacement Cable glands of size 220 to 300 Sqmmduly connected with existing incoming/outgoing connections complete all as specified. |
| 15 | Supply and fixing in replacement Cable glands of size 400 Sqmmduly connected with existing incoming/outgoing connections complete all as specified. |
| 16 | Material and labour for painting of LT Panel/ Bus Bar Chamber/ Feeder Pillar box of any type & size by applying two coats of synthetic enamell smoke gray paint over a coat of red oxide primer surface complete all as directed. |
| 17 | Material and labour for replacement of unserviceable earthing complete with galvanised steel earth plate electrode 600x600x6mm thick burried directly in ground (earth pit not less than 2.25 Mtr deep below ground level) with top edge of the plate not less than 1.5 Mtr below normal ground level, connected to galvanised earth strip 25x4 mm by means of bolts, nuts, check nuts and washers of GI or steel all as shown in electrical plate No. 3 of SSR Part-I 1991 connected to earthing test point/ transformer/ panel all as directed and testing on completion as directed including necessary excavation & earth work in any type of soil, funnel, PCC chamber (1:3:6) type C1, RCC pit cover, charcoal, salt including provision of earth lead protected by 40mm dia light grade GI pipe and 20mm dia medium grade GI Pipe for watering complete all as specified and directed.Note: (i) If the desired earth resistance is not found within permissible limit of less than 5 Ohm, earthing shall be redone by contractor without any extra cost.(ii) Cost of galvanised earth strip upto 7.5 mtr, 40mm dia light grade GI pipe and 20mm dia medium grade GI pipe for watering is included in the rate quoted for this item. |
| 18 | Description all as per item 17 above but with galvanised iron strip 32x6 mm as earthing lead and protection pipe of dia 50mm. |
| 19 | Material and labour for replacement of unserviceable earthing with maintenance free earthing with copper electrode 50mm dia thick buried directly in ground vertically to a depth not less than 2.10 mtr below ground level filled with highly conductive metalic compound mixture CCM with the permanent sealing of the both end, outer dia pipe 50mm with strip terminal 50x6 with terminal holes including one bag 25 kg of bfc compound, earth connected with copper strip 20 x 3 mm as earth lead by means of bolts, Nuts, check nuts and washers of galvanized iron and thimbles and other end of the earth wire connected to main switch board protected by galvanized iron pipe medium 40 mm bore,PVC chamber as per manufacturer instruction and testing on completion complete all as specified and directed.Note: (a) If the desired earth resistance is not found within permissible limit of less than 2 Ohm, earthing shall be redone by contractor without any extra cost.(b) Cost of copper earth strip upto 7.5 mtr, 40mm dia light grade GI pipe is included in the rate quoted for this item. thimbles and other end of the earth wire connected to main switch board protected by galvanized iron pipe medium 40 mm bore, PVC chamber as per manufacturer instruction and testing on completion. |
| 20 | Supply and fixing in replacement MCCB 415 V with adjustable thermal & adjustable magnetic setting Ics=100% Icu complete of following capacities including fixing properly with new suitable size of thimbles, nut - bolt and washers and taking down existing unserviceable of any type/ make etc complete all as specified and directed. |
| 21 | MCCB 400 Amps, 4 pole of breaking capacity 36 KA |
| 22 | MCCB 320 Amps, 4 pole of breaking capacity 36 KA |
| 23 | MCCB 250 Amps, 4 pole of breaking capacity 36 KA |
| 24 | MCCB 200 Amps, 4 pole of breaking capacity 25 KA |
| 25 | MCCB 160 Amps, 4 pole of breaking capacity 25 KA |
| 26 | MCCB 125 Amps, 4 pole of breaking capacity 25 KA |
| 27 | MCCB 100 Amps, 4 pole of breaking capacity 25 KA |
| 28 | MCCB 63 Amps, 4 pole of breaking capacity 25 KA |
| 29 | Supply and fixing in replacement Air Circuit Breaker 415 Volts, 50 Hz, manual drawout type, with thermal magnetic release setting Ics=100% Icu complete of following capacities including fixing properly with new suitable size of thimbles, nut - bolt and washers and taking down existing unserviceable of any type/ make etc etc complete all as specified and directed. |
| 30 | ACB 400 Amps, 4 pole of breaking capacity 36 KA |
| 31 | ACB 630 Amps, 4 pole of breaking capacity 50 KA |
| 32 | Supply and fixing in replacement off load change over switch, four pole 415 volts, 50 Hz side handle operated in sheet metal enclosure, powder coated weather proof conforming to IEC 13947-3 inclduing taking out old unserviceable one of following capacities: |
| 33 | 63 Amps, 4 pole. |
| 34 | 100 Amps, 4 pole. |
| 35 | 200 Amps, 4 pole. |
| 36 | Supply, Installation, commissioning & testing of factory made CPRI approved, LT switch gear panel board, IP-54 (outdoor type), 415 volts, 50 Hz, AC supply, three phase and neutral (4 wire), 400 Amps aluminium busbars 4 pole, duly insulated with heat shrinkable sleeve as per colour code supported on epoxy insulatators, having independent compartment for insulated busbar, incoming feeder & each outgoing feeder i.e. cubicle type, made out of 3.00 mm thick CRCA sheet and 2mm thick inner enclosure CRCA sheet, rigid mild steel angle iron frame of 50x50x6mm with 900mm long extended legs grouting in PCC 1:3:6 type C2 block of size 1000x300x600mm, duly epoxy powder coated internally & externally with approved shade, rubber gasket, hinged front & back openable doors with proper locking arrangements for dust and vermin proof, complete including suitable size cable alley, lugs, cable glands, common earth bar of GI strip 32x6mm at bottom and making connections with MCCB spreaders/wiring with suitable size of single core PVC copper conductor cable, locking arrangements 65mm size and lock with keys, earth work and excavation comprising the following:Incoming :- (a)MCCB 250 Amps 4P, 35KA, Adjustable thermal & fixed magnetic setting, Ics=100% of Icu with spreader link - 01 Nos.,Meter set : Digital voltmeter,Ammeter + CT : 400/5, RYB indicating Lamp LED type 240 V, MCB SP 6A, 400 Amp Alluminium Bus Bar Outgoing :-(a) MCCB 100 Amp FP, 25 KA, Adj tharmal & fixed magnetic setting,Ics=100% of Icu with spreader link- 02 Nos.(b) MCCB 63 Amp FP,16 KA, Adj tharmal & fixed magnetic setting, Ics=100% of Icu with spreader link - 02 Nos. |
| 37 | Description all as per item No 23 here-in before but with following switch gears :Incoming :- (a)400 Amps 4P, 35KA , Adjustable tharmal & fixed magnetic setting, Ics=100% of Icu with spreader link - 01 Nos.(b)Meter set : Digital voltmeter, Ammeter + CT : 400/5, RYB Indicating Lamp LED type 240 V, MCB SP 6A, 600 Amp Alluminium Bus BarOutgoing :-(a) MCCB 250 Amp FP,25 KA,,Adj tharmal & fixed magnetic setting,Ics=100% of Icu with spreader link- 01 Nos.(b) MCCB 160 Amp FP,25 KA,,Adj tharmal & fixed magnetic setting,Ics=100% of Icu with spreader link- 02 Nos.(c) MCCB 100 Amp FP,16 KA,Adj tharmal & fixed magnetic setting, Ics=100% of Icu with spreader link - 02 Nos. |
| 38 | Description all as per item No 23 here-in before but with following switch gears :Incoming :- (a)400 Amps 4P, 35KA , Adjustable tharmal & fixed magnetic setting, Ics=100% of Icu with spreader link - 01 Nos.(b)Meter set : Digital voltmeter, Ammeter + CT : 400/5, RYB Indicating Lamp LED type 240 V, MCB SP 6A, 600 Amp Alluminium Bus BarOutgoing :-(a) MCCB 250 Amp FP,25 KA,,Adj tharmal & fixed magnetic setting,Ics=100% of Icu with spreader link- 01 Nos.(b) MCCB 160 Amp FP,25 KA,,Adj tharmal & fixed magnetic setting,Ics=100% of Icu with spreader link- 05 Nos.(c) MCCB 100 Amp FP,16 KA,Adj tharmal & fixed magnetic setting, Ics=100% of Icu with spreader link - 02 Nos. |
| 39 | Excavation in trenches in any type of soil not exc. 1.5 mtr wide and not exc. 1.5 mtr in depth for laying of cable, foundation etcand getting out complete all as directed. |
| 40 | Material and labour for sand cushioning & covering of UG cable using crushed metal sand in trenches for cable protection complete all as directed. |
| 41 | Material & labour for sub class B bricks well burnt of size 23 x 11.5 x 7.5 cm for protection of UG cable laid dry flat over the cable width wise across the length of the cable and abutting each other with gap less than 10mm between the adjacent bricks in trenches complete all as directed. |
| 42 | Returning, filling in including spreading levelling watering and well ramming in layers not exceeding 25 cm in soil complete all as directed. |
| 43 | Removing of excavated soil to a distance n exc 50 mtr and deposited where directed at a level not exc 1.5 mtr above the starting point complete all as directed. |
| 44 | Material and labour for cutting chases in hard standing road/path/drain etc for passing cables/pipes etc size of cutting 100mm wide and 300mm deep and removing the excavated materials and disposal at 50 metre distance and making good to the cutting after the pipe and cables are laid with PCC 1:3:6 type C-1 using 20mm graded stone aggregates complete all as specified and directed.Note:- (a) Cost of GI/ HDPE pipe shall be measured and paid separately under relevant items. |
| 45 | Material & labour for cement concrete (1:4:8) type D-2 (using 40 mm graded crushed stone aggregate) as in foundations and mass concrete for foundations of poles etc complete all as directed. |
| 46 | Material & labour for cement concrete (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) for coping of poles including necessary from work for finishing exposed faces of concrete smooth and even using extra cement complete all as directed. |
| 47 | Taking out carefully LT cable of any size or type or make from ground/ poles/ pipes etc and testing for serviceability and laying the same serviceable LT cables under ground/ on poles/ through pipes etc at same or any other location and testing after connections complete all as directed.Note:- (a) Item to be measured only when cable is found serviceble for reuse.(b) Necessary excavation, sand cushioning, cable protection covers, returning, removal etc shall be measured and paid separately under relevant items. |
| 48 | Material and labour for laying, jointing and testing of undergroundXLPE insulated & PVC sheathed, armoured heavy duty multistranded electric cable with aluminium conductor, 1100 volts grade in trenches/ ducts/ along poles/ through pipe/ under road/ PCC etc and connecting with new aluminium lugs including taking out existing unserviceable of any size/ type complete for the following cables of cross sectional area all as directed: Notes:(a)Excavation, returning, removal, sand cushioning, cable protection covers, GI protection pipe etc shall be measured and paid separately.(b)Any damage done during cable excavation to the existing UG infra like UG pipelines, UG electric cables, OFC etc shall be repaired by the contractor at their own expenses.(c)Cost of T&P required for handling/ laying of cable is deemed to be included in the rate quoted by the contractor. |
| 49 | 10.0 Sqmm, 4 core. |
| 50 | 16.0 Sqmm, 4 core. |
| 51 | 25.0 Sqmm, 4 core. |
| 52 | 35.0 Sqmm, 4 core. |
| 53 | 50.0 Sqmm, 3.5 core. |
| 54 | 70.0 Sqmm, 3.5 core. |
| 55 | 95.0 Sqmm, 3.5 core. |
| 56 | 120.0 Sqmm, 3.5 core. |
| 57 | 150.0 Sqmm, 3.5 core. |
| 58 | 185.0 Sqmm, 3.5 core. |
| 59 | 240.0 Sqmm, 3.5 core. |
| 60 | 300.0 Sqmm, 3.5 core. |
| 61 | Supply & Laying of High density polyethylene pipes (HDPE) of pressure rating PN 6 sizelaid in trenches/ fixed to poles/ wall/ laid in floor for the protection of UG cable for following bore of pipes: |
| 62 | size 50 mm |
| 63 | size 80 mm |
| 64 | size 100 mm |
| 65 | Supplying, errecting and fixing of steel tubular swaged poles, type 410-SP-31, 9.00 metre long, complete with cast iron base plate, heat resistance finial taper plug, bolts, nuts and screws as specified including painting withtwo coats of synthetic enamalled paint over one coat of red oxide primer and 06 Nos bands/straps with white and red colour (30cm wide each) epoxy heat resistant paint at a distance 30cm from plinth block and numbering of poles with black synthetic enamel paint in 2.5 cm height including taking out existing unserviceable pole of any type/ height/ make etc complete all as specified and directed.Notes: 1. Excavation, returning, removal, PCC for foundation and coping etc shall be measured and paid separately.2. Any damage done during erection of pole to the existing UG infra like UG pipelines, UG electric cables, OFC etc shall be repaired by the contractor at their own expenses.3. Cost of T&P required for transporting/ handling/ erection etc of pole is deemed to be included in the rate quoted by the contractor. |
| 66 | Supply and fixing of cross arms, bracing, supports, clamps and back plates fabricated from structural steel section (flat iron/ angle iron/ MS sheet) including back plate, MS boxes made out of MS sheet, clamps or D clamps made out of MS flat iron made to shape including nuts, bolts, washers, welding, bending hot or cold, drilling holes for bolt in any size or shape as directed inclusive of two coats of aluminium paint over a coat of red oxide primer including taking out existing unserviceable of any size/ type etc complete all as specified and directed. |
| 67 | Material and labour for stay assembly complete comprising of 20 mm dia galvanised stay rod 180 cm long, MS galvanised stay plate size 300 x 300 x 6 mm thick for stay pole as shown in electric plate No 1 of SSR part-I for HT poles including taking down existing unserviceable of any type/ make etc complete all as specified and directed.Note: Excavation, concrete, loop type insulator and stay clamp will be measured and paid seprately. |
| 68 | Supply and fixing of loop type insulator vitreous procelain, white, brown or green, large size with overall dimensions 65 x 90 mm, clearence of hole 16 mm etc including taking down existing unserviceable of any type/ make etc complete all as specified and directed. |
| 69 | Supply and fixing of danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nutsfor LT of size 20 x 15 cm including taking down existing unserviceable of any type/ size etc complete all as specified and directed. |
| 70 | Dismantling carefully existing steel poles/ struts/ PCC poles of any size/ type for reuse including necessary excavation, demolition of concrete, shifting to a location as directed and removing the old concrete/ PCC rubbish etc complete all as directed. Note -Item to be measured only when pole is found serviceble for reuse at same or any other location. |
| 71 | Labour only for fixing/ erecting only of steel/ PCC poles of any length and type retrieved fromdemolition/ dismantling of item No 40 here in above ofincludingloading, shifting,unloading and erection in true vertical position complete all as directed. |
| 72 | Supply and fixing of post top lantern LED type of 20 Wattcapacity 230 volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp from pole of any height/ pillar/ bldg wall etc CCT not less than 5700K, IP 65 complete including taking down existing unserviceable light fittings all as directed. |
| 73 | Supply and fixing of Integral LED Street Light Luminaire comprising of pressure die cast aluminum housing heat resistant toughened glass with frame IP-65/66 protection road way luminaries with high power LED 90 wattwith Efficacy 110 Lm/W,CCT :5700 K with potted5KV internal and 10 KV external inbuilt surge protectionincluding taking down existing unserviceable light fittings all as directed. |
| 74 | Material and labour for painting of steel pole 09 meter height after preparing the surface by scrapping old paint with sand paper with two coat of aluminium paint over a coat of red oxide primer incuding making 5 nos of alternative strips of black and yellow paint of 30 cm width & numbering of pole as per existing complete all as directed. |
| 75 | Supply and fixing of timer astronomical digital type and necessary connection complete including taking out existing timer complete all as specified and directed |
| 76 | NOTE:- Amount of credit ofRs. 218695.00 for retrieved materials is mentioned in Schedule of Credit Page No25 of tender documents in pdf form which will be deducted offline while acceptance of tender. |