| 1 | Repairing and servicing (Oiling and greasing) of gang operated switch 11KV vertical/Horizontal mounted and replacement of U/S spare parts as required for smooth functioning of AB switch, testing for its proper operation, all as directed at site. Note :-(a) Oil and grease include in quoted rate. (b) Supply of spares shall be measured and paid separately. |
| 2 | (a) Supply only following items for 11KV gang operated air break switch :-Male Contact/moving contact Blade heavy duty high conductive metalcap 200/400 amp 11 KV |
| 3 | (b) Female Contact/Fix contact Jaw heavy duty high conductive metalcap 200/400 amp 11 KV |
| 4 | (c) Tinned copper flexible jumper 200/400 Amps |
| 5 | (d) Post insulator for 11 KV |
| 6 | Supply & fix in repair gang operated air break switches, triple pole, manually operated, mounted on insulators and steel frame, with operating mechanism worked from ground levelhorizontal type for rating upto 400 Amps, 11000 volts complete with GI operating pipe of heavy duty including Dismantling of existing defective HT 11 KV Gang operated air break switch complete all as directed |
| 7 | Supply & fix in repair gang operated air break switches, triple pole, manually operated, mounted on insulators and steel frame, with operating mechanism worked from ground levelvertical type for rating upto 400 Amps, 11000 volts complete with GI operating pipe of heavy duty including Dismantling of existing defective HT 11 KV Gang operated air break switch complete all as directed |
| 8 | Supply & Fix in repair drop out fuse assembly complete setof three with Insulator-06 Nos and connected accessories for 11000 V grade of 400 Amps capacityincluding taking down U/S DO fuse assembly. |
| 9 | Supply & fix in repair lightening arrestor, expulsiontype complete with all fittings, transmission class, dischargecapacity 65 Kilo amp withall connecting lead and fittings, horn gap and chocking soil suitable for maximum working pressure 11000 Volts including taking down existing U/S lightening arrestor complete all as directed |
| 10 | Supply & Fix in repair cross arms, bracings, supports, clamps and back plates fabricated from structural steel section including nuts, bolts , washers, welding, bending ( cold or hot ) drilling holes for bolts bent to any shape or size as indicated or directed inclusive two coat of alumunium paint over a coat of red oxide/zinc chromate primer includingTaking down coss arms/ clamps/Nut bolts and Angle section etc from HT Pole any size complete all as specified and directed. |
| 11 | M&L for Danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT,25x 20 cm size in repair |
| 12 | Supply & Fixin repairHT jumper existing single pole/two pole/four pole structure of transformer/over head line etc including colour code, PVC sleeves for 11 KV using winding of ACSR conductor (weasel) 11000 volts, including PG clamps, nut bolts, thimbles and washer etc including taking down Old unservicable jumper as per sitre requirement as directed by Engr-in-Charge. |
| 13 | M&L for painting of PCC pole any type/size by providing yellow and black paint with 30 cms alternate strip upto 1.2 m height from ground level including writing of pole number in synthetic enamel paint including painting to cross arm, clamps, channels etc with one coat of aluminium paint including preparation of surface all as directed by Engineer-in-Charge for the following :-HT Two pole structure |
| 14 | M&L for painting of PCC pole any type/size by providing yellow and black paint with 30 cms alternate strip upto 1.2 m height from ground level including writing of pole number in synthetic enamel paint including painting to cross arm, clamps, channels etc with one coat of aluminium paint including preparation of surface all as directed by Engineer-in-Charge for the following :-HT Four Pole structure |
| 15 | Disconnecting & Taking down old unserviceable earthing set complete |
| 16 | M&L for earthing complete as per electric plate No 3 of MES SSR Part-I with galvanised steel earth plate electrode 60x60cmx6.0mm thick burried directly in ground ( earth pit not less thanb 2.25 Mtr deep below ground level ) with top edge of the plate not less than 1.5 Mtr below normal ground level, connected to galvanised strip 32 x 6 mm earth lead by means of bolts, nuts, check nuts and wathers of GI or steel . Earthing strip shall be protected by galvanised iron pipe 40 mm bore light grade and connected to continous earth lead on pole/test point, Watering pipe shall be 20 mm bore GI medium grade. The unit rate quoted for earthing shall be inclusive of excavation and earth work in any type of soil, charcoal, salt, funnel, PCC pit and RCC cover complete all as specified and directed.Note :- (a) Irrespective of what is shown in drawings, the concrete pit shall be in PCC (1:3:6) type C-1 and 40 mm thick precast cover slab of RCC (1:2:4) type B-1, using 20 mm graded stone aggregate with suitable handle. (b)Item includes the cost of GI pipe for protection of earth lead /strip including earth lead upto 7.5 Mtr. (c) Earthing value should be less than 5 ohm. |
| 17 | Suppy,laying in treches/ducts connecting, jointing and testing forcable XLPE insulated screenedPVC beddedsgalvanised steel stripor wire armoured heavy dutyelectric power cable with multistranded aluminium conductor suitable for 11 KV grade of size 120 Sq mm X 3 core including taking down Old unservicable HT cable all as specified and directed. |
| 18 | Suppy,laying in treches/ducts connecting, jointing and testing forcable XLPE insulated screenedPVC beddedsgalvanised steel stripor wire armoured heavy dutyelectric power cable with multistranded aluminium conductor suitable for 11 KV grade of size 95 Sq mm X 3 core including taking down Old unservicable HT cable all as specified and directed. |
| 19 | Excavation in trenches n. exc. 1.5Mtr width n.exc 1.5 Mtr in depth for laying of cables & foundation of poles, stay assembly and getting cut in hard/dense type of soil. |
| 20 | M & L for sand cushioning to PVC under ground cable with screened and washed sand and punning to provide a required covercomplete all as specified and directed. Note :- Thickness after punning shall be considered for payment. |
| 21 | M/L for brick work with FLY ASH BRICKS as per IS-13757 (1993) burnt clay fly ash building bricks, (OLD SIZE BRICKS)with width equal to the length of the brick laid dry & flat abutted with each other with gap between adjacent bricks not exc 10 mm over UG cable for protection and complete all as specified & directed. |
| 22 | Returning, filling in including spreading levelling , watering and well ramming in layers not exc. 25cm in any type soil |
| 23 | Removing of surplus excavated soil to a distance not exc. 50m and depositing where directed at a levelnot exc 1.5 Mtr above the starting point. |
| 24 | Boring of holes under road,pavement, hard standing by trench less technology using ultra sound technique and necessary machine including HDPE pipe of 80 mm dia suitable for 0.4 mpa working pressure. |
| 25 | M/L for GI pipelight gradefor protection of HT cable fixed to walls/ poles/road crossing including clamps complete of size 80 mm bore in repair |
| 26 | Dismantling and taking out unserviceable 11 KV (Earthed) grade cable jointing kit any type/size and straight through joints any type/size all as directed |
| 27 | M&L Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armourend aluminium conductor cable of size 50-95 sqmm. Note :- Necessory excavation and earth work for removing loop included in quoted rate. |
| 28 | M&L Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armourend aluminium conductor cable of size 120-185 sqmm.Note :- Necessory excavation and earth work for removing loop included in quoted rate. |
| 29 | M&L Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120-185 sqmm.Note :-Necessory excavation and earth work for removing loop included in quoted rate. |
| 30 | M&L Cable jointing kit for 11 KV (Earthed) grade cable straight through termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120-185 sqmm.Note :- Necessory excavation and earth work included in qouted in quoted rate. |
| 31 | Supply & errecting Cable path indicators for HT Cable made of CI plate fixed on MS angle iron size 40x40x5mm and 90 Cm long. and fixing in ground 60 Cm below ground level in PCC 1:3:6 type B-1 using 40mm grade stone aggregate of size 45x45x60cm . Cable path indicators shall be provided at distance of every 30 meters and at cable joints and turning of all cables and incorporated HT 11000 Volts on it.including PCC & earth work complete all as specified and directed. |
| 32 | Findout the location for faulty HT cable of any size by using HT cable fault locator for jointing the straight through termination complete all as directed by Engr-in-Charge. Note:- (i) Excavation and earth work shall be measured and paid seperately(ii) straight through termination required for replacement, shall be measured and paid under the relevant item. (iii) The contractor should rectify the defects within 24 hours from the time of information. If contractor failed to rectify the defects within 24 hours, then the recovery will be made against the contractor @ Rs.4000/- per day for delay period |
| 33 | Supply and fill unused mineral insulating oils conforming to IS 335: 2018, Type II Class (Transformer oils), Uninhibited (U), pour point -10⁰C, vacuum filtered in a laboratory, Breakdown voltage of min 70 kV at 2.5 mm gap complete all as specified and as directed. |
| 34 | M&L for dehydaration/filteration of transformer oil of existing transformer installed at site with portable plant to improve the dielectric strength not less than 50 KV , including testing of dielectric strength before and after dehydration at site. (Note : The contractor has to arrange the dehydration machine & testing kit without any cost to the Deptt. Test report to be submitted after completion of job). |
| 35 | Labour for repair to the transformer 63 KVA to 500 KVA at site by opening the topcover for carrying out repair such as replacement ofHT side busing with rods, LT side bushing and rods, gasket, tap changer etc and reassembling after carrying out required repair in the transformer complete including testing and commissioning all as directed by Engr-in-Charge. Note : (i).Replacement of U/S parts shall be measured and paid separately under respective item of Sch `A`(ii). Labour charge for Replacement of u/s parts are deemed to be included in quoted rate. |
| 36 | M&L for disconnecting, lifting, loading and transportation of unserviceable transformer indoor/outdoor type 11000/433 Volts of capacity 63 KVA to 500 KVA from site to workshop for repair/rewinding and repair to the transformer by dismantling the top cover and removing unserviceableburnt LT/HT side coil from the core, rewinding the LT and HT side core complete with same size of copper wire in HT side and copper strip from LT side with suitable insulating materials, nuts, bolts, washers, gasket set etc, heating the new transformer winding in special heat chamber for demoisturising of LT/HT coil, connecting the LT/HT coils, filling the fresh transformer oil, re-assembling the transformer, transporting/shifting back the transformer at site after repairs, re-commissioning & testing, including applying two coats of synthetic enamel paint of approved paint after preparation of all external surfaces of transformer, complete, all as specified and directed by Engineer-in-Charge. Note :- (i)Placing/ removing stand by transformer in the place of defective transformer under repair will be the responsibility of the contractor, stand by transformer will be provided by the department(ii) The quoted rates shall deemed to include for the transportation, T&P, Labours from site to workshop and workshop to back at site after repairs, cost of gasket set, nuts, bolts, washers, etc. (iii)Old oil shall be collected by the contractor or refilling otherwise for credit(iv)All other spares such as tap changer, copper wire & copper strip for rewinding, HT/LT side bushing, transformer oil & air breather assembly with silica gel shall be measured and paid for separately as “Supply only” under respective items of this Schedule. |
| 37 | Supply of HT bushingporcelain with copper stud, nuts, bolts, washers, gasket, oil seal suitable upto100 KVA. Transformer. |
| 38 | Supply of HT bushingporcelain with copper stud, nuts, bolts, washers, gasket, oil seal suitable for 125 to500 KVA.Transformer. |
| 39 | Supply ofLT bushingporcelain with copper stud, nuts, bolts, washers, gasket, oil seal suitable upto100 KVA. Transformer. |
| 40 | Supply of LT bushingporcelain with copper stud, nuts, bolts, washers, gasket, oil seal suitable for 125 to500 KVA. Transformer. |
| 41 | Supply of Complete gasket set suitable for 63 KVA to 500 KVA transformer |
| 42 | Supply of Copper winding wire / Copper strip of required size. |
| 43 | Supply & Fix Silica gel breather of suitable size with new silica gel breather |
| 44 | M&L for spreading in layers onlyGraded coarse aggregate 40mm Nominal size |
| 45 | Writing letters or figures (Block, Roman, Italic or Indian ) not exceeding 30 cm high with synthetic enamel paint of approved colour and qualitywith thick painting so that they stand out boldly and solidly without sign of brush mark, if necessary they shall be repainted until the desired results obtained and painting surface of any description over 10cm girth or width all as directed by Engr-in-Charge as per details as under :-i) Earth result sign board / SM/MES No. |
| 46 | Painting of existing transformer of 63 KVA to 200 KVA capacity applying two coat of synthetic enamel paint of grey colour by spraypainting complete including preparation of old surfaces, removing,cleaning of oil, grease all as specified and directed by Engineer-in-Charge of following:- Note :- MES No. and SM No. on equipment with type and colour of paint all as specified and directed by Engr-in-Charge. |
| 47 | Painting of existing transformer of 250 KVA to 500 KVA capacity applying two coat of synthetic enamel paint of grey colour by spray painting complete including preparation of old surfaces, removing,cleaning of oil, grease all as specified and directed by Engineer-in-Charge of following:- Note :- MES No. and SM No. on equipment with type and colour of paint all as specified and directed by Engr-in-Charge. |
| 48 | M&L for preventive maintenance / repairing by opening and taking out the Vacuum Circuit Breaker (VCB) 11 KV 800 Amp, type VMX from panel and carry out the general maintenance such as oiling & greasing the mechanical parts, motor, gear, lever spring, operating rod, cleaning the female contacts, tightening of nuts and bolts, cleaning the male and female contact of panel, oiling the bus bar shutter, checking the AC/DC wiring, circuit including control fuses and circuit jack, on/off push button, indicating lamp, voltmeter, ammeter, PF meter, replacement of minor parts (where required) and testing after re-inserting the VCB in panel complete all as specified and as directed. The new replaced parts shall be measured and paid separately under appropriate item of Sch \"A\" as \"Supply Only\" |
| 49 | Supply only Electro mechanical Master trip relay Hand reset type Suitable for flush mounting, in temp 0 to 55°C, RH 50% to 100%, 1A & 5A CT input and auxuliary DC supply of 30/110/220 Volt complete all as specified and directed. |
| 50 | Supply only Over current and earth fault relay Suitable for flush mounting, in temp 0 to 55°C, RH 50% to 100%, 1A & 5A CT input and auxuliary DC supply of 30/110/220V with breaking capacity 2 KVA complete all as specified and directed. |
| 51 | Supply only Trip Circuit supervisionRelay as existing Make /Model complete all as specified and directed. |
| 52 | Supply only Anti Pumping Relay should not be plug in type & should have suffcient number of contact complete all as specified and directed. |
| 53 | Supply only Tripping coil having copper material through actuating device rated for Substation DCvoltage 12/ 24 /110 V ,burden value < 200 watt , Min operating Voltage of 70% for tripping and 85% for closing operation as per existing installed on site complete all as specified and directed. |
| 54 | Supply only Closing coil having copper material through actuating device rated for Substation DCvoltage 12/ 24 /110 V ,burden value < 200 watt,, Min operating Voltage of 70% for tripping and 85% for closing operation as per existing installed on site complete all as specified and directed. |
| 55 | Supply only Resin cast/Dry type Potential transformer having 3 phase,Ratio 11000/√3V / 110√3V,vector group Star/Star with neutral earthed, burden/class: 100VA/0.5, Fixed type with HRC fuse protection,with IS: 3156-1992 complete all as specified and directed. |
| 56 | Supply only Resin cast, Dual ratio, Indoor type Current Transformer for breakers having ratio 100-50/5-5A, Burden value 15VA both for protection & metering core, Short-time circuting rating 25kA for 3 sec , Protection Core 5P10 complete all as specified and directed. |
| 57 | Supply only HT vaccum interrupted assembly bottle with flex connection suitable for VMX type VCB 800 Amps capacity for RYB phases complete all as specified and as directed. |
| 58 | Supply only Spring charging motor operated on Power 150-250 Watts ,220 V AC/DC supply having insulation Class B type complete all as specified and directed. |
| 59 | Supply only PT/VT fuse 11/12 KV,breaking capacity 45 kA, rating 3.15 Amp complete all as specified and directed. |
| 60 | Supply only Power pack fuse 1 to 5 Amp complete all as specified and directed. |
| 61 | Supply only HRC fuse link type NSD type rating 02 Amps to 10 Amps, Rated voltage 550 Volt, breaking capacity 80 KA as per IS 13703 latest complete all as specified and directed. |
| 62 | Supply only HRC fuse link type NSD type rating 16 Amps to 32 Amps, Rated voltage 550 Volt, breaking capacity 80 KA as per IS 13703 latest complete all as specified and directed. |
| 63 | Supply only Fuse fitting (front+back+busbar) for LV BS(NSD) type of FuseFA 20 Amps, Rated voltage 500 V as per IS 13703 latest complete all as specified and directed. |
| 64 | Supply only Space Heaters Thermostat having temp range 25-85°C complete all as specified and directed. |
| 65 | Supply only Auxillary switchfor suitable for 11 KV breaker complete all as specified and directed. |
| 66 | Supply only Local Remote Selector Switch complete all as specified and directed. |
| 67 | Supply only Breaker control Switch Three position : Trip, close and neutral control switch with one trip and one close 32 Amp for operation of VCB complete all as specified and directed. |
| 68 | Supply only Standard push button, flush round head 22 mm diaand required number of N/O & N/C self returning contacts without locking arrangements for Emergency Trip functionsbracket assembly complete all as specified and directed. |
| 69 | Supply only Emergency stop push button switches, Flush round Head 22 mm diaand required number of N/O & N/C self returning contacts without locking arrangements for Emergency Trip functionsbracket assembly complete all as specified and directed. |
| 70 | Supply only Claster LED type Indicating lamps with built resistor holder and coloured lens with rating 30/110/220 Volt DC complete all as specified and directed. |
| 71 | Supply only Digital Ammeter 96x96 mm AC 3 Phase (inbuilt selector switch),Auxillary supply 230 Volt AC, 3 line display having range 5-5000 Amp complete all as specified and directed. |
| 72 | Supply only Digital AC voltmeter 96x96mm AC Range 0-15 KV, Accuracy 1.0 PTR 11KV/110 Volt, Auxillary supply 230 Volt AC, 3 line display complete all as specified and directed. |
| 73 | M&L for testing and adjusting the following relay including checking and rectifying the tripping circuit complete, Calibration of relay for 11 KV VCB panel at various places at Alwar Mil Stn complete all as specified and directed.(a) Trip circuit supervision Relay(b) Master TripRelay, 24 DC(c) Over current & earth fault relay(d) Intelligent Panel Meter(e) Ammeter & VoltmeterNote:- (i) The tripping system of relays are to be calibrated with MRS, Alwar.(ii) The testing instrument whatever required to test the relays will be arranged by the contractor at his own cost.(iii) The test shall be provided fromauthorized agency. |
| 74 | Supply and fixing in replacement of battery backed power pack having input 110 or 230V AC, output 24/110/220 Volt DC and continous load 100 VA as per IEC 60947-1 & IEC 61000-4/5 complete all as specified and directed. |
| 75 | Providing the areacleaning, upkeeping and maintaining of MES installations / campus/ outside the periphery of transformer platform/ two poles structure/ four pole structures by surface dressing or trimming of natural ground to remove small inequalities not exceeding 15 cm deep (including removing vegetation / shrubs / brush wood / under-growth) including carrying away the rubbish to a distance of not exceeding 50 m away complete all as specified and as directed. The Appx area of installationkept clean all as under .(1) MRS 33/11 KV - 1000 Sqm(2) 4 pole Sub Stn- 150 Sqm(3) 42 ADSR S/S (02 Nos)- 500 Sqm(4) Vet Area S/S- 300 Sqm(5) New Md S/S - 300 Sqm(6) Map JCO/ORS/Offrs S/S ( 07 Nos)- 800 Sqm(7) 18 Arty Bde S/S- 100 Sqm(8) Gen Set Room S/S (02 Nos)- 300 Sqm(9) JCO/ORs Md S/S (08 Nos)- 1200 Sqm(10) 36 ORs Stn (02 Nos)- 400 Sqm(11) 15 GNDR- 100 Sqm(12) Swimming Pool - 100 Sqm(13) 74 Fd Regt- 200 Sqm(14) Amn Dump (02 Nos) - 250 Sqm(15) 19 JAT- 200 Sqm(16) Maj & Cap S/S (03 Nos)- 400 Sqm(17) Children School S/S- 200 Sqm(18) 322 Md Regt S/S- 200 Sqm(19) Offr Mess S/S- 150 Sqm(20) 318 Fd Hos S/S- 100 Sqm(21) 820 FD Wk Shop S/S- 150 Sqm(22) Auditorium S/S- 100 Sqm(23) JCO /ORsS/S (02 Nos) - 200 Sqm(24) SWCCR S/S- 100 Sqm(25) Block 159/210 S/S (02 Nos)- 300 Sqm(26) Baccha S/S- 100 SqmNote: - The contractor shall clean, upkeep and maintain the premises during the contract period and the payment shall be made monthly each job basis. contractor provide the required T & P for cleaning the installation. |
| 76 | S&F glow sign board of white polished transparent acrylic cover of minimum 2mm thick, unbreakable, heat resistive etc including M&L of steel fabrication of angles and supports of thickness not less than 2mm thick (thickness shall be variable upto 5mm as per site conditions) rectangular box type of size minimum 180cm x 90cm x 20cm thick, computerised letter of blue colour of size 30cm high and 3 to 5cm width or small as per site requirement having glue on backside to stick permanently, including all kind of securing, welding, assembling with proper allignment and height with fine look, including PCC, cement work, excavation if required, LED tube light fittings 1x 20Watt(6 NOS), including light point 2.5 sqmm (up to 15 m length as required)and switch independent one way 15Ampsuitable for exposing at all weathers including taking down of old UNSV sign board etc completeall as specified and as directed by Engineer-in-Charge. |
| 77 | S&F glow sign board of white polished transparent acrylic cover of minimum 2mm thick, unbreakable, heat resistive etc including M&L of steel fabrication of angles and supports of thickness not less than 2mm thick (thickness shall be variable upto 5mm as per site conditions) rectangular box type of size minimum 400cm x 60cm x 20cm thick, computerised letter of blue colour of size 30cm high and 3 to 5cm width or small as per site requirement having glue on backside to stick permanently, including all kind of securing, welding, assembling with proper allignment and height with fine look, PCC(up to 1 cum), cement work,putti and paint excavation if required, LED tube light fittings 1x 20Watt(10 NOS), including light point 2.5sqmm and switch independent one way 15Amp up to 15 m length as reuired all as specified suitable for exposing at all weathers including taking down of old UNSV sign board etc completeall as specified and as directed by Engineer-in-Charge. |
| 78 | M&L for painting aluminium coat over Steel tubular pole and cross arms any size and height including preparration of metallic surface with sand papers and applying one coat of metallic primer before applyingtwo coat of aluminium paint all as specified and as directed by Engineer-in-Charge |
| 79 | S & F Silver plates ( Installations details/ TF datails/Equipment Details/ MES /SM NO ) as directed by engr in chargecomplete all as specified and as directed. |