| 1 | Supply, install testing and commissioning in repair factory madeout door typeLT panel board of size not less than 1.5 mtr X 1.2mtr X 0.60 mtr, 440 volts , 3 phase , 4 wire system with powder coating providedto make it dust /vermin proof manufactured by CPRI approved manufacturer. The panel shall be made with 3.15 mm thick CRCA sheet for outer shell and inner shell made out of 1.6 mm thick CRCA sheet, double door with front openable with locking arrangement, provision of threaded earthing stud at bottom, inner shell be compartmentalized, front openable single door system lockable. Inner shell completely vermin proof and to accommodate incoming/outgoing ACB\"s, MCCBs, MCBs, and TPN aluminium bus and extension links. Aluminium bus bar of capacity 1200 Amps- 4Nos,including neutral duly insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size/rating of epoxy resininsulator all housed in suitable bus bar chamber.All control wires shall be as per the OEM recommendations and shall be properly bunched, tied, ferrulled for proper indentification and crimped with adequate size of lugs andprovision and fixing of Voltmeter,Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps completealong with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable size of cable glands etc. Computer cut shelf adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The panel shall consists of following accessories complete all as specified and directed:-Location :- Near 400KVA Transformer Aundh Camp. |
| 2 | Note : (i) Electrical connection from switchgear to bus bar would be through copper strips of suitable size.(ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size.(iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminumlugs of suitable rating incommensurate with that of switchgear.(iv)Cable glands would be provided for incoming & out going cables in panels.(v)The cost of fixing of the panel on suitable PCC (1:3:6) type C-1 (using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item.(vi)The panel is to be fixed with Angle Iron Frame of size 65mm x 65mm x 6mm with bottam of panel having minimum 60cm height from existing ground/floor level.(vii) The operation of all MCCBs should be of Rotary handle type, the cost of rotory handles is deemed to be included in the quoted cost. |
| 3 | Aluminium bus bar strips with proper colour code -04 No, 1200 A capacity, insulator, nuts bolts etc complete. |
| 4 | Indicator Lamp-01 Set (Set of three) |
| 5 | IncommerACB 630 Amps Manual draw out type , 50 KA 4 pole 415 volts - 01 NosMake :- Legrand cat no -DMXS106N3MD4N /Havells |
| 6 | Outgoing, MCCB 4P320 amp with thermal magnetic release , 415V, 36 KA- 01 No (for APFC panel) Make Legrand cat no-4220 06 /Havells |
| 7 | Outgoing, MCCB 4P200 amp with thermal magnetic release , 415V, 36 KA- 03 No (for Feeder panel) Make Legrand cat no-4202 48 /Havells |
| 8 | Outgoing, MCCB 4P250 amp with thermal magnetic release , 415V, 36 KA- 01 No (for Feeder panel) Make Legrand cat no-4202 49 /Havells |
| 9 | Outgoing, MCCB 4P125 amp with thermal magnetic release , 415V, 25 KA- 01 No (for Feeder panels of Md accn) Make Legrand cat no-4200 56 /Havells |
| 10 | Outgoing, MCCB 4P63 amp with thermal magnetic release , 415V, 25 KA- 01 No (for Street light panel) Make Legrand cat no-4200 53 /Havells |
| 11 | Digital Voltmeter 0 to 500 Vand Digital Amps meter0 to 1000A.with selector switich Make-Legrand/Minilac |
| 12 | Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles. |
| 13 | Supply, install testing and commissioning in repair factory madeout door typeLT panel board of size not less than 1.2 mtr X 1mtr X 0.300 mtr, 440 volts , 3 phase , 4 wire system with powder coating providedto make it dust /vermin proof, manufactured by CPRI approved manufacturer. The panel shall be made with 3.15 mm thick CRCA sheet for outer shell and inner shell made out of 1.6 mm thick CRCAsheet, double door with front openable with locking arrangement, provision of threaded earthing stud at bottom, inner shell be compartmentalized, front openable single door system lockable. Inner shell completely vermin proof and to accommodate incoming/outgoing MCCBs, MCBs, and TPN aluminium bus and extension links. Aluminium bus bar of capacity 400 Amps- 4Nos,including neutral duly insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size/rating of epoxy resininsulator all housed in suitable bus bar chamber.All control wires shall be as per the OEM recommendations and shall be properly bunched, tied, ferrulled for proper indentification and crimped with adequate size of lugs andprovision and fixing of Voltmeter,Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps completealong with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable size of cable glands etc. Computer cut shelf adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The panel shall consists of following accessories complete all as specified and directed:- |
| 14 | Note : (i) Electrical connection from switchgear to bus bar would be through copper cable of suitable size.(ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size.(iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminumlugs of suitable rating incommensurate with that of switchgear.(iv)Cable glands would be provided for incoming & out going cables in panels.(v)The cost of fixing of the panel on suitable PCC (1:3:6) type C-1 (using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item.(vi)The panel is to be fixed with Angle Iron Frame of size 50mm x 50mm x 6mm with bottam of panel having minimum 60cm height from existing ground/floor level. |
| 15 | Aluminium bus bar strips with proper colour code -04 No, 400 A capacity, insulator, nuts bolts etc complete. |
| 16 | Indicator Lamp-01 Set (Set of three) |
| 17 | Incomer MCCB 4P200 amp with thermal magnetic release , 415V, 36 KA- 01 NoMake Legrand cat no-4220 49 /Havells |
| 18 | Outgoing, MCCB 4P40 amp with thermal magnetic release , 415V, 16 KA- 03 No (for Distribution panel) Make Legrand cat no-4200 52/Havells |
| 19 | Outgoing, MCCB 4P63 amp with thermal magnetic release , 415V, 25 KA- 03 No (for Distribution panel) Make Legrand cat no-4200 53 /Havells |
| 20 | Digital Voltmeter 0 to 500 Vand Digital Ampmeter0 to 400A.with selector switich Make-Legrand/Minilac |
| 21 | Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles. |
| 22 | Supply, install testing and commissioning in repair factory madeout door typeLT panel board of size not less than 1.5 mtr X 1.2mtr X 0.450 mtr, 440 volts , 3 phase, 4 wire system with powder coating providedto make it dust /vermin proof, manufactured by CPRI approved manufacturer. The panel shall be made with 3.15 mm thick CRCA sheet for outer shell and inner shell made out of 1.6 mm thick CRCAsheet, double door with front openable with locking arrangement, provision of threaded earthing stud at bottom, inner shell be compartmentalized, front openable single door system lockable. Inner shell completely vermin proof and to accommodate incoming/outgoing MCCBs, MCBs, and TPN aluminium bus and extension links. Aluminium bus bar of capacity 400 Amps- 4Nos,including neutral duly insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size/rating of epoxy resininsulator all housed in suitable bus bar chamber.All control wires shall be as per the OEM recommendations and shall be properly bunched, tied, ferrulled for proper indentification and crimped with adequate size of lugs andprovision and fixing of Voltmeter,Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps completealong with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable size of cable glands etc. Computer cut shelf adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The panel shall consists of following accessories complete all as specified and directed:- |
| 23 | Note : (i) Electrical connection from switchgear to bus bar would be through copper cable of suitable size.(ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size.(iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminumlugs of suitable rating incommensurate with that of switchgear.(iv)Cable glands would be provided for incoming & out going cables in panels.(v)The cost of fixing of the panel on suitable PCC (1:3:6) type C-1 (using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item.(vi)The panel is to be fixed with Angle Iron Frame of size 50mm x 50mm x 6mm with bottam of panel having minimum 60cm height from existing ground/floor level. |
| 24 | Aluminium bus bar strips with proper colour code -04 No, 400 A capacity, insulator, nuts bolts etc complete. |
| 25 | Indicator Lamp-01 Set (Set of three) |
| 26 | Incomer MCCB 4P200 amp with thermal magnetic release , 415V, 36 KA- 01 NoMake Legrand cat no-4220 49 //Havells |
| 27 | Outgoing, MCCB 4P100 amp with thermal magnetic release , 415V, 25 KA- 02 No (for Distribution panel) Make Legrand cat no-4200 52/Havells |
| 28 | Outgoing, MCCB 4P63 amp with thermal magnetic release , 415V, 25 KA- 03 No (for Distribution panel) Make Legrand cat no-4200 53 /Havells |
| 29 | Digital Voltmeter 0 to 500 Vand Digital Ampmeter0 to 400A. with selector switich Make-Legrand/Minilac |
| 30 | Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles. |
| 31 | Supply, install testing and commissioning in repair factory madeout door typeLT panel board of size not less than 1.5mtr X 1mtr X 0.6 mtr, 440 volts, 3 phase , 4 wire system with powder coating providedto make it dust /vermin proof, manufactured by CPRI approved manufacturer. The panel shall be made with 3.15 mm thick CRCA sheet for outer shell and inner shell made out of 1.6 mm thick CRCAsheet, double door with front openable with locking arrangement, provision of threaded earthing stud at bottom, inner shell be compartmentalized, front openable single door system lockable. Inner shell completely vermin proof and to accommodate incoming/outgoing MCCBs, MCBs, and TPN aluminium bus and extension links. Aluminium bus bar of capacity 1200 Amps- 4Nos,including neutral duly insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size/rating of epoxy resininsulator all housed in suitable bus bar chamber.All control wires shall be as per the OEM recommendations and shall be properly bunched, tied, ferrulled for proper indentification and crimped with adequate size of lugs andprovision and fixing of Voltmeter,Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps completealong with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable size of cable glands etc. Computer cut shelf adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The panel shall consists of following accessories complete all as specified and directed:- |
| 32 | Note : (i) Electrical connection from switchgear to bus bar would be through copper strips of suitable size.(ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size.(iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminumlugs of suitable rating incommensurate with that of switchgear.(iv)Cable glands would be provided for incoming & out going cables in panels.(v)The cost of fixing of the panel on suitable PCC (1:3:6) type C-1 (using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item.(vi)The panel is to be fixed with Angle Iron Frame of size 65mm x 65mm x 6mm with bottam of panel having minimum 60cm height from existing ground/floor level.(vii) The operation of all MCCBs should be of Rotary handle type, the cost of rotory handles is deemed to be included in the quoted cost. |
| 33 | Aluminium bus bar strips with proper colour code -04 No, 1200 A capacity, insulator, nuts bolts etc complete. |
| 34 | Indicator Lamp-01 Set (Set of three) |
| 35 | IncommerACB 800 Amps Manual draw out type, 50 KA 4 pole 415 volts - 01 NosMake :- Legrand cat no -DMXS108N3MD4N or Havells cat no- IHAFE21060080 |
| 36 | Outgoing, MCCB 4P400 amp with thermal magnetic release , 415V, 36 KA- 01 No (for LT panel) Make Legrand cat no-4220 07 or Havells cat no- IHLLSEE40400 |
| 37 | Outgoing, MCCB 4P320 amp with thermal magnetic release, 415V, 36 KA- 03 No (for Startor panel) Make Legrand cat no-4220 06 or Havells cat no- IHLLSEE40320 |
| 38 | Outgoing, MCCB 4P160 amp with thermal magnetic release , 415V, 25 KA- 01No (for Startor panels ) Make Legrand cat no-4200 57 or Havells cat no- IHTT1DBF0160 |
| 39 | ON Load change over swtich 4 pole, 800 AmpsMake Havells |
| 40 | Digital Voltmeter 0 to 500 Vand Digital Amps meter0 to 1000A.with selector switich Make-Legrand |
| 41 | Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles. |
| 42 | Material and Labour in repair for earthing complete with galvanized steel earth plate electrode 60 cm x 60cmx6 mm thick, buried directly in ground vertically (earth pit not less than 2.25 mtr deep below ground level) with top edge of the earth plate not less than 1.5mtr below ground level , connected to 32mm x 6 mm GI stripas earthling lead by means of bolts and nuts check nuts and washers of galvanized iron and connected to main switch board including watering arrangement with PCC chamber (as per direction of Engineer-in-Charge), MS funnel, wire gauge.CI cover with frame , 40 MM dia GI pipe light grade for protection of wire/strip etc including necessary excavation in any type of strata , returning, fillingremoval of soil outside MD land ,filling ofcharcoal andsalt complete all as shown in electrical plate No. 3 of MES Sch Part I , connected to Earthing test point complete all as specified and directed. |
| 43 | Supply, laying, jointing, commissioning and testing XLPEinsulated screened PVC bedded, armoured,heavy duty underground electric cable in repair with stranded aluminium conductor 1100 volts grade confirming to IS-7098 (Part-I-1988) laid in trenches/ducts/wall / floor / pipes/ poles including cable glands and aluminium lugsof appropriate size, PVC sleeve etcincluding dismantling of old LT UG cables complete all as specified and directed for following sizes . Make :- Havells / Gloster / Finolex / Polycab |
| 44 | 300 sq mm 3.5 core . |
| 45 | 95 sq mm 3.5 core |
| 46 | 50 sq mm 3.5 core . |
| 47 | 35 sq mm 3.5 core |
| 48 | 25 sq mm 3.5 core |
| 49 | 16 sq mm 4 core |
| 50 | NOTE :- Earth work , bricks , riddled earth , GI pipe for protection of cable will be measured & paid under under relevant items of schdule . |
| 51 | Excavation in trenches not exceeding 1.5mtr wide and not exceeding 1.5mtr in depth for foundation of poles stays laying of electric cables, pipes etc and getting out in soft/loose soil complete all as specified and directed. |
| 52 | All as per item No. 7 above, but in hard/dense soil complete all as specified and directed. |
| 53 | Removing excavated material soil to a distance not exceeding 50mtr and depositing where directed at a level not exceeding1.5mtr above the starting point complete all as specified and directed. |
| 54 | Returning, filling in,including spreading, levelling watering and well ramming in layers not exceeding25cm in soft/loose soil complete all as specified and directed. |
| 55 | Material and Labour for riddled earth forcushioning to under ground electric cable including spreading , levelling and hand punning complete all as specified and directed. Note - Punned thickness shall only be measured & paid . |
| 56 | Material and Labour for road cutting / foot path and making good with PCC 1:3:6 TYPE C-2 (using 40 mm graded stone aggregate) of 150 mm width/ depth complete all as specified and directed. |
| 57 | Supply and laying un-reinforced precast concrete cable cover LV, Type I, flat, size 250mm x 150mm x 40mmfor Under ground cable complete all as specified and directed. |
| 58 | Supply and laying GI tubes light grade, galvanized, 40 mm bore laid in trenches or under floor or fixed with poles/walls for protection of electric cable complete all as specified and directed. |
| 59 | All as per item No. 14 above, but 80 mm bore complete all as specified and directed. |
| 60 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size25 Sqmm to 50 Sqmm 3.5 core/4 core cable complete all as specified and directed. |
| 61 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts gradeof size from 70 Sqmm to 120 Sqmm 3.5 core /4 core cable complete all as specified and directed. |
| 62 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of sizefrom 150 Sqmm to 185 Sqmm 3.5 core/4 core cable complete all as specified and directed. |
| 63 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of sizefrom 240 Sqmm to 300 Sqmm 3.5 core/4 core cable complete all as specified and directed. |
| 64 | Material and Labour forhardcore of gauge n.exc 63mm ,deposited, spread, and levelled in layers n.exc15 cm thickness (below or above ground level), watered and rammedto a true shape with broken stone or boulders existing available on site and making good complete all as specified and directed. ( Sub Station Yards) |
| 65 | Supply, install, testing and commissioning out door type 100 KVAR APFC PanelFloor/Wall mountedfront operated totally enclosed vermin proof, weather proof and dust proof made out of 3.15mm thick CRCA sheet steel for housing all components of 8 stage, 100kVARAutomatic power factor correction panel including incoming MCCB 160 Amps 4 pole , Capacitor duty contactors, step protection MCB\"s, indicating lamps, APFC relay, 100 KVAR (4(20KVAR)+1(10KVAR)+1(5KVAR)+1(3KVAR)+1(2KVAR)) capacitor MPP-H in steps,ammeter, voltmeter with selector switches and all accessories complete all as specified and directed. Make of APFC Panel - Havells cat no- QHXTCB5100X0 or equivalentin Legrand/Schneider/BCHNote :- The size of panel should not be less than (1.1x0.7x0.250)mtr.Location :- Near 250KVA Transformer Aundh Camp. |
| 66 | Supply, install, testing and commissioning out door type 175 KVAR APFC PanelFloor/Wall mountedfront operated totally enclosed vermin proof, weather proof and dust proof made out of 3.15mm thick CRCA sheet steel for housing all components of 8 stage, 175kVARAutomatic power factor correction panel including incoming MCCB 315/320 Amps 4 pole , Capacitor duty contactors, step protection MCB\"s, indicating lamps, APFC relay, 175 KVAR (2(50KVAR)+2(25KVAR)+1(10KVAR)+3(5KVAR)) capacitor MPP-H in steps,ammeter, voltmeter with selector switches and all accessories complete all as specified and directed. Make of APFC Panel - Havells cat no- QHXTCB5175X0 or equivalentin Legrand/Schneider/BCHNote :- The size of panel should not be less than (1.1x0.8x0.54)mtr.Location :- Near 400KVA Transformer Aundh Camp. |