| 1 | Excavation in trenches in soft/loose soil not exceeding 1.5m wide and not exceeding 1.5 metre in depth and getting out for laying of cable etc complete all as specified. |
| 2 | Returning, filling in soft/loose soil including spreading, levelling, watering and well ramming, in layers not exc 25 cm complete all as specified. |
| 3 | Removingof surplus soil to a distance not exc. 50 metre and depositing where directed at a level not exc.1.5 metre above the starting point complete all as specified. |
| 4 | Taking out of old unsv GI plate earthing from existing position ,complete all as specified. Note Only Earthing material goes to schedule of credit except GI strip |
| 5 | Material and labour for bore well earthing with the help of mechanical boring machine of 150mm dia 30mtr depth, supply and fix 150 mm bore , UPVC pipe 6 kg/sqcm rating, 06 mtr long with the help of suitable size clamp with nut bolt and washer -01no including charcoal dust, salt fill in bore well for achieve earth conductivity less than 1 ohm. M&L for covering of bore well mouth with PCC (1:2:4) type B-1/Brick masonry pit of size 45x45x45 cm complete and give the mimimum earth test result below 1 ohm complete all as specified.Note :- (i) The earth pit shall be refilled by boulders free from vegetable soil.(ii) Earthing shall be tested by contractor in presence of Engr-in-charge. Record shall be maintained.Payment shall be admissible only after satisfactory test results. (iii) GI pipe electrode and GI strip shall be measured & paid separately. |
| 6 | Supply & lowering of GI tubing 50mm dia medium grade including necessary fittings for lowering in borewell of depth upto 30 mtr and providing necessary holes in pipe to achieve goodearth conductivity complete all as specified. |
| 7 | Taking down old Unserviceable GI strip from wall or buried in ground or any other indicated situation including making good to disrurbed surface complete all as specified. |
| 8 | Refixing of serviceable GI Strip 32x6mm fixed on wall or buried in ground or any other indicated situation complete all as specified. |
| 9 | S&F GI Strip 32x6mm fixed on wall or buried in ground or any other indicated situation complete all as specified. Note:- Extra GI strip consider for borewell earthing which for existing earthing location |
| 10 | Material and labour for chemical earthing complete with copper earth plate electrode of size 600mm x 600mm x 3 mm thick buried directly in ground(earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5m deep below normal ground connected to and including copper earth strip 25 x 3 mm by means of copper bolts nuts check nuts and washer, returning & filling the pit with excavated soil mixing with charcoal 250 KG , Crystal salt 200KG , magnesium sulphate of 100 KG and vegetable soil all around the plate up to 350mm above from top edge of plate and balance portion filing with excavated soil in layers not exceeding 25mm thick, 25mm bore galvanised iron medium grade watering pipe up to top of plate, 50mmbore galvanisd iron light grade pipe for earth strip protection, including all excavation earth work in any type of soil, PCC 1:3:6 type C1for chamber of internal size 300mm x300 x 300mm with 120mm thick wall and 700 mm x 700mm x 150mm thick, bed concrete, RCC 1:2:4, type B1 for precast chamber cover 50mm thick, reinforced with welded steel wire fabric or XPM jali (weight not less than 4.00 Kg/sqm), funnel, with wire mesh, complete all as specified.Note:- (i) Quoted rates shall be deemed to include for earth strip with protection pipe up to 7.5 M length |
| 11 | Taking out of old unsv GI strip and supply & fix copper strip of size 25 x 3 mm complete with insulator/saddle and fixing with screw/accessories for roof and down conductor complete all as specified. |
| 12 | Taking down old Unserviceable air termination rod of any size and capacity complete all as specified. |
| 13 | Refixing of serviceable Air termination rod as obatin from Item No 12 above including new threading and grinding of tip of air terminationas per site requirement complete all as specified. |
| 14 | S&F single pointed air termination aluminium rod12 mm dia and 300 mm long complete all as specified. |
| 15 | Taking down old Unserviceable aluminium strip from roof and wall of ESHs any size and position including making good to disrurbed surface of wall and roof complete all as specified. |
| 16 | Refixing of serviceable aluminum strip 25x3 mm complete as obtained from above item with on new saddle / insulators, including straightning and fixing screws/accessories for roof and down conductor complete all as specified.Note:Rate of insulators shall be deemed included in quoted rate . |
| 17 | S&F aluminium srip of size 25x3 mm complete with insulator/saddle and fixing with screw/accessories for roof and down conductor complete all as specified. Note: Rate of insulators shall be deemed included in quoted rate . |
| 18 | Taking down old Unserviceable GI rusted pipe from roof orwallof size 40/50 mm in any position including making good to disrurbed surface of wall and roof complete all as specified. |
| 19 | S&F GI pipe light grade 40 mm dia for protection of GI strip complete all as specified. |
| 20 | S&F GI pipe medium grade 40 mm dia for protection of GI strip complete all as specified. ( For supporting air termination rod of ACSR conductor pole) |
| 21 | Supplying and stringingAluminium conductor, steel reinforced (ACSR)any type of ACSR conductor for airtermination points supported by GI tubing on the roof of the ESHs to inner connect the all termination points including taking down of existing conductor complete all as specified.(Notes : (i) The ACSR conductors shall be conforming to IS-398 and as specified in SSR Part-I.(ii) The unit rate quoted shall also be deemed to include for supply & fixing of aluminium binding wire, aluminium tapes etc which shall not be included in the weight of conductors.(iii) Weight of conductors shall be determined by measuring true horizontal distance between centers of two adjacent poles and compoundingthe weight of conductors of that size and length and 3% extra added for sag, jointing, jumpers etc.(iv) Weight of the conductors shall be calculated from the nominal weights given in tables in the relevant IS.) |
| 22 | M&L for Test point with Junction box of polycarbonate body with minimum rating IP 65 ofsize not less than 130mmx170mmx80mm complete including 01 No gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw fixedwith earth strips including nut bolt with washer on both sideinside the junction box and junction box shall be fixed on wall/ pole with suitable clamp including accessories complete all as specified including dismantling of old unservieable MS test point box complete. |
| 23 | S&F in repairDMC inculator for wall down conductorfor 32 X 6 strip with one meter intervel secured with suitable screw complete all as specified. |
| 24 | S&F in repair porceiline insulator for wall down conductorfor 32 X 6 strip with one meter intervel secured with suitable screw complete all as specified. |
| 25 | M&L for framed brackets of angles or tee with web and flanges cut to shape, drilled and counter sunk for screw including bending and welding angles as necessary gusset plates riveting etc not exc 10 kg in weight each brackets, clamps for holding pipe and aluminium strip for lightning protectionincluding insulator 1100 volt andtaking out old materials complete all as specified. |
| 26 | Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by mean of GI strip 32x6mm as earthing lead by means of bolts, nuts check nuts and washers of GI or steel and connecting to earthing test point, main switch board, testing on completion includingGI pipe 20 mm dia light grade for watering and bringing the same upto 30 cm above normal ground level with plug at top including pipe fittings etc complete and GI pipe 40 mm dia light grade for the protection of GI strip upto 1.5 Meter complete including necessary excavation and earth work in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50 m all as specified as shown in electrical plate No 3 SSR Part-I.Note: earth pit cover is to be made 10mm MS Plate with the projection to overlap the four side of the road covered up to 10 cm with collapsable MS Handle includingtaking out old unserviceable earthing. |
| 27 | M & L for cutting of bituminous road or PCC upto 30cm deep and 20cm wide for laying of pipe lines for protection of GI strip and making good surface by PCC 1:2:4 type B-1,( Using 20mm grade stone aggregate) complete all as specified. |
| 28 | Demolition of cement concrete (un-reinforced) of any description and any position n.exc 15 cm thickness (below or above GL) complete all as specified. |
| 29 | M & L for stay assembly to support GI pipe for Air Termination by providing 4mm dia GI wire 15 RM, 16mm MS Rod 1.35 RM and PCC block 1:3:6 size of 0.6x0.6x0.15M including earth work in sof soil including dismantlingold Stay assembly complete all as specified. |
| 30 | M&L of PCC 1:2:4 type B-1, 20 mm graded aggregate filling and mass concrete, for road finishing, PCC blocks, earthing pit cover, and foundation concrete complete all as specified. |
| 31 | M&L for Checking/testing of Earth resistance value of earthing pits Installed inside Depot areaas requirement basis as directed by Engr in Charge or as schedule and making the damaged earthing serviceable by pouring salted water into earthing or making continuity by GI strips and bringing down the resistance value within specified limits, including maintenance of existing earthing by cleaning the earth chamber funnel and cleaning of vagetation surrouding earthing pit up to 2 mtr complete all as specified.Note: (i) The entire station will be divided intotwo zones as per earthing location and the contrcator will deploy seperate team for each zone to test the resistance value of earthings in each zone to complete the process within one month. (ii) One earthing testing in one season is measured one job. (iii) Digital Earth tester will be arrange by the contractor his own. (iv) Date of testing and due date of testing is to be written on a register with sign ofuser rep & Engr-in Charge submitted to GE. (iv) Testing and correction action is to be done within one month from date of commencement i.e. approx 300 earthings is to be completed within one month. Thereafter on half yearly basis or as directed by Engr-in charge and same is to be completed within one month.The contractor has to deploy electrician with helper and testing equipment and all the resources to complete the task within one month.(v) If any material required for improvement of resistence value which value is more than their permissible limit will be measured and paid seperately. |
| 32 | Dismantling of existing broken PCC earth chambers of any description and providing earth chamber of size 300 mm x 300mm (Internal size),and depth 280mm and 75mm thick with PCC 1:3:6 type C1 using 20mm graded stone aggregate complete all as specified. |
| 33 | M&L for Replacement of broken earth chamber coverby providingRCC cover of1:2:4, Type B-1, using 20mm graded stone aggregateofsize 300mmx300mmx40mm thick, reinforced with 8mm dia MS TMT bars @100 mm C/C both ways with MS handle 08mm dia complete all as specified. |
| 34 | S&FGI Funnel with wire meshon existing20 mm dia pipecomplete all as specified. |
| 35 | Labour wok only for alignment of existing earth pit by necessary earth work complete all as specified. |
| 36 | Refixing of broken earthing strip of Al/ GI strip joint with providing new nuts, bolts and washer ( min size 10mm dia) incl drilling work & necessary T&P complete all as specified. |
| 37 | M&L for earthing plate of 2mm thick MS plate with 2 coats black paints of size 300mm x 150mm with 15mm GI pipe of size 1 meter lenths with conncted items and required foundationcomplete all as specified. |