| 1 | Excavation in trenches in soft & loose soil not exceeding 1.5 meter deep and not exceeding 1.5 m width and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes etc.all as specified and directed including removing cable protection PCC covers/ bricks & stacking serviceable covers / bricks for reuse and disposal of unserviceable covers within 50 m all as specified and directed. Note : Excavation shall be made carefully in order to avoid damage of existing cables and protection covers. |
| 2 | Returning, filling in including spreading, levelling, watering and well ramming in layers of25 cm thickafter the cables etc. are laid, jointed & tested complete all as specified and directed. |
| 3 | Removal of surplus excavated soil not exceeding 50 Mtr distance and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 4 | S&F bricks well burnt sub class ‘B’ bricks in trenches on cable as cable protection across the length of the cable (width wise) complete all as specified and as directed. |
| 5 | M & L for sand cushioning for cable protection with dry river sand and punning to provide required cushioning for UG cable complete all as specified and directed. Note : Punned thickness of sand shall be measured & paid. |
| 6 | Disconnecting ,taking out and removing from trenches/ducts/sleeve/on pole/wall etc existing LT UG XLPE insulated,armouredcable of any description, any size/core and in any position complete all as specified and directed for the following sizes of cable :-Note:Earth work shall be measured & paid separately under respective item. 95 Sqmm 3.5 Core |
| 7 | 50 Sqmm 3.5 Core |
| 8 | 35 Sqmm 3.5 Core |
| 9 | 25 Sqmm 4 Core |
| 10 | Supplying, laying, jointing & testing XLPE insulated & PVC sheathed armoured LT cable, 1100 volts grade heavy duty with aluminium conductor of the following sizes laid in trenches/pipe/fixed on the wall etc complete all as specified and directed: (a) 95 Sqmm 3.5 Core |
| 11 | 50 Sqmm 3.5 Core |
| 12 | 35 Sqmm 3.5 Core |
| 13 | 25 Sqmm 3.5 Core |
| 14 | Taking up or down steel tubing as in cable protection pipe of 80 mm size complete all as specified and directed. |
| 15 | Supply, laying & fixingGI light grade pipes of size 80 mm Dia for cable protection laid in trenches/floor/roof and on the walls, with all accessories, complete all as specified and directed. |
| 16 | Taking up or down steel tubing cable protection pipe of 50 mm size complete all as specified and directed. |
| 17 | Supply, laying & fixing t GI light grade pipes of size 50 mm Dia for cable protection laid in trenches/floor/roof and on the walls, with all accessories, complete all as specified and directed. |
| 18 | Disconnecting & taking out of existing unserviceable phase indicator,Ammeter,Voltmeter,current transformer, ON/OFF rotary type selector switch, Indicating lamps neon, Moulded fuse holder, Single Phase preventer, selector switches, contactor, timer,MCCB,Isolator TPN, etc ofLT panel suitable for 20 HP to 40 HP of water supply installation, checking ofserviceability of parts / wiring and replacement of unserviceable control wiring with 1.5 Sqmm, and power wiring with suitable size single core, copper conductor, flexible, PVC insulated, unsheathed cablesuitable up to 1100 volts confirming to IS – 694, taking out, removing and replacement of unserviceable parts/spares /items, reassembling the panel and testing the panel on full load aftercompletion of repairsetc complete all as specified and directed.Note:- The quoted rates of the contractor shall be included for fixing the serviceable parts in position and replacement of unserviceable parts with new parts.The new replaced parts shall bemeasured and paid for separately under appropriate item of BOQas `supply only ‘ but quoted rates are inclusive of replacement of small/minor parts such as nuts, bolts, washers/lugs/gasketsetc |
| 19 | Supply only Ammeter 0 – 100 Amps, 96 mm x 96mm, digital type of accuracy class 0.5 suitable for 50Hz, 3 Phase, 415 Volts AC supply complete all as specified and directed. |
| 20 | Supply only Voltmeter 0 – 500 Volts,96 mm x 96mm, digital type of accuracy class 0.5 suitable for 50Hz, 3 Phase, 415 Volts AC supply complete all as specified and directed. |
| 21 | Supply only current transformer of CT ratio 100/5 Amps suitable for 50Hz, 3 Phase, 415 Volts AC supply complete all as specified and directed. |
| 22 | Supply only3 way ON/OFF rotary type selector switch suitable for 50Hz, 3 Phase, 415 Volts AC supply complete all as specified and directed. |
| 23 | Supply only Indicating lamps neon type with holder for 12 volts DC supply complete all as specified and directed. |
| 24 | Supply only Moulded fuse holder and fuse base, HBC type for 415 volts AC circuit having rating of 20 Amps with BS type fuse link complete all as specified and directed. |
| 25 | Supply only phase indicator LED type (red/green) complete all as specified and directed. |
| 26 | Supply only Single Phase preventer complete all as specified and directed. |
| 27 | Supply and fixing in repair of MCCB of 25 to100 Amps, 16 KAThree Pole, 415 V all as specified and directed for following Amps & breaking capacity :- |
| 28 | All as item 21 abovebut capacity of 125 Amps, 16 KA |
| 29 | Supply and fixing in repair of MCCB of 160 Amps, 36 KAfour Pole, 415 V all as specified and directed for following Amps & breaking capacity :- |
| 30 | ditto- all as above but capacity of 200 Amps , 36 KA |
| 31 | Supply and fixing in repair of Isolator TPN, 415 V, 40 Amps (‘C’ series) having current rating 10 KA complete all as specified and directed. |
| 32 | All as item 25 but 63 Amp |
| 33 | All as item 25 but 80 Amp |
| 34 | All as item 25 but100 Amp |
| 35 | Supply and Fixing in repair of new Aluminium bus bars of any shape and size suitable up to 400 amp as directed by Engineer-in- Charge. |
| 36 | Supply and Fixing in repair of mild steel door assembly200 mm size clip & bolt type, stove enamelled black, with bright bolt not lessthan 12mm Dia with andincluding welding the sliding bolt & staple plate including nut, bolts and washers in existing LT feeder pillar boxes complete all as specified and directed by Engineer-in-Charge. |
| 37 | Supply and Fixing in repair of of MS Hinge plate in existing feeder piller boxes/ panel boards with necessary spot welding etc including making necessary adjustment for free and smooth movement of panel and locking arrangements complete all as specified and directed by Engineer-in-Charge. |
| 38 | Supply and Fixing in repair of2 mm thick CRCA sheet duly fabricated in existing shape and size with and including and all jointing material such as nuts bolts or washer and welding etc. complete all as specified and directed. NOTE : (I). The panel board repaired shall be made totally enclosed, weather proof, warming proof for installing incoming/ outgoing MCCB / Switch fuses/ cable etc. complete all as directed (ii)The rates quoted by the contractorshall be included necessary cutting, welding, levelling and jointing etc. as directed to match & accommodate with the existing feeder pillar box / panel board .(iii)The replaced portion shall be painted with two coat of synthetic enamelled paint to match existing colour over a coat of red oxide primer. |
| 39 | Disconnecting / Dismantling Taking out old Spreader terminalsand Supply & Fixing new Spreader MCCB Terminals Current Rating 150/175/200/250 Amps all as specified and directed. |
| 40 | M&L for preparation of the old decorated existing external and internal steel surfaces of feeder pillar boxes/panels/ boards of any description and in any position including removal of disintegrated & deteriorated paint either by hand scrapping or by blow lamps, applying necessary filler coat and stopping as required and applying two coats of synthetic enameled paint (grey in color) with using spray machine on old prepared surfaces complete all as specified and directed . Note :Rates quoted by the contractor shall be included for writing the MES /SM No and other relevant details with paint in the pattern and style as approved by the Engineer-in-Charge |
| 41 | Taking down old /unsv thermal over load relay any capacity and any make, S&F thermal over load relay auto and manual resetting having capacity 17-25 Ampsuitable for contactor CN5 to CN6 complete all as specified and directed. |
| 42 | Taking down old /unsv over load relay & S&F in repair thermal over load relay auto and manual resetting having capacity 30-40 Ampsuitable for contactor CN5 to CN6 complete all as specified and directed. |
| 43 | Taking down old /unsv MPCB any capacity and any make and S&F MPCB relay range 13-18 Amp , breaking capacity not less than 15kA at 415 Volt type MB2-20complete all as specified and directed. |
| 44 | Taking down old /unsv MPCB any capacity and any make and S&F MPCB relay range 17-23 Amp , breaking capacity not less than 10kA at 415 Volt type MB2-21 complete all as specified and directed. |
| 45 | Taking down old /unsv MPCB any capacity and any make and S&F MPCB relay range 24-32 Amp , breaking capacity not less than 10kA at 415 Volt type MB2-32 Make: Havellsor equivalent of CROMPTON/INDO ASIAN with and including MPCB enclosure having IP-65 protection type MB2-Ecomplete all as specified and directed. |
| 46 | Taking down star- delta starter any make and capacity and S&F deluxe automatic star-delta submersible pump starter MU-G20 FASD Three Phase Submersible Controller with Single Phase Preventer and Amp Volt Meter complete all as specified and directed. |
| 47 | Taking down star- delta starter any make and capacity and S&F deluxe automatic star-delta submersible pump starter MU-G30 FASD Three Phase Submersible Controller with Single Phase Preventer and Amp Volt Meter complete all as specified and directed. |
| 48 | Taking down star- delta starter any make and capacity and S&F deluxe automatic star-delta submersible pump starter MU-G40 FASD Three Phase Submersible Controller with Single Phase Preventer and Amp Volt Meter complete all as specified and directed. |
| 49 | Taking down DOL starter any make and capacity and S&F Single Phase 220/240 Volt L T Starter Panel, upto 2000 Amps Controller with Single Phase Preventer and Amp Volt Meter complete all as specified and directed. |
| 50 | Taking down old /unsv power contactor and S&F new power contactor type MNX 415 Volts having capacity 18 Amp 1 No and1 NC MNX 18 complete all as specified and directed. |
| 51 | Taking down old /unsv power contactor and S&F new power contactor type MNX 415 Volts having capacity 22 Amp 1 No and1 NC MNX 22 complete all as specified and directed. |
| 52 | Taking down old /unsv power contactor and S&F new power contactortype MNX 415 Volts having capacity 32 Amp 1 No and1 NC MNX 32 complete all as specified and directed. |
| 53 | Taking down old /unsv power contactor and S&F new power contactor type MNX 415 Volts having capacity 50 Amp 1 No and1 NC MNX 50 complete all as specified and directed. |
| 54 | Taking down old /unsv power contactor and S&F new power contactor type MNX 415 Volts having capacity 80 Amp 1 No and1 NC MNX 80 complete all as specified and directed. |
| 55 | Taking down old /unsv Flat submersible cable of any size S&F Flat submersible three core copper pvc insulated industrial cable for submersible of 6 sqmm complete all as specified and directed. |
| 56 | Taking down old /unsv Flat submersible cable of any size and S&F Flat submersible three core copper pvc insulated industrial cable for submersible of 4 Sqmm complete all as specified and directed. |
| 57 | Taking down old /unsv motor protection relay of any size and S&F motor protection relay including single phase prevention, Dry running motor, under current, over current phase reversal protecting type MPRD2 complete all as specified and directed. |
| 58 | Taking down old /unsv Voltage protection relay of any size S&F Voltage protection relay including adjustable setting and protection of unbalance, phase failure, under voltage, over voltage type VMRD2, complete all as specified and directed. |
| 59 | Disconnecting and dismantling old unserviceable change over switch of any capacity and make from any position all as specified and directed. |
| 60 | Supplying, Fixing, jointing and testing ON LOAD change over switch (open execution), 3 pole, 415 volts of current rating 400 Amps complete all as specified and directed.. |
| 61 | Description all as per item No. 51above but of current rating 250 Amps |
| 62 | Description all as per item No. 51above but of current rating 100 Amps |
| 63 | S&F Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicatedsituation for loop earthing etc. as required 32x6mm galvanised iron or steel wire complete all as specified and directed. |