| 1 | Disconnecting existing Cables and earthing strip from unserviceable panel. Dismantling and taking out the panel and making good the disturbed surface of the same location for fixing a new panel all as directed by Engr in charge. |
| 2 | Fabrication, supply, installation, testing and commissioning electrical cubical control panel board( KIOSK TYPE ) Double door CPRI approved factory assembled made out door feeder pillar box wheather and vermin proof fabricated of 3.15 mm CRCA MS sheet of Suitable size,3 phase 4 wire 415 Volt ac 50 Hz complete duly painted with powder coating complete with locking arrangement, earthing terminals with suitable rating aluminium Bus bars for incoming/outgoing MCCB\"s including and Mounting measuring instrument such as Volt meter, Ammeter, Selector switchs, CT\"s -03 Set, Phase indicator lamps with holder , toggle switches and MCBs etc including incoming and outgoing cables connections with suitable cable glands and end termination including grouting of feeder pillar box 60 cm above ground level by providing 105 cm long angle iron size 50x50x6mm welded onall four corner embedded in PCC (1:2:4) using 20mm graded upto 45cm and frame structure of panel will be made angle iron of size 50 x 50 x 6 mm. complete all as specified and directed. ( Feeder piller box shall be consisting the following)(a)4 Nos electrolytic aluminium bus bars high conductivity aluminium alloy proper insulated of Rating 1000 Amps with provision of extension and mounting on porcelain insulators.(b) ACB 630 amp FP, 415 volts, with Thermal Magnetic Release (Manual Drawout type), 50Hz = 01 No (Incoming)(c)MCCBTP200 amps, 36 KA , 415 volts, 50Hz - 02 Nos (Outgoing)(d) MCCBTP 160 amps, 25 KA , 415 volts, 50Hz- 02 Nos,(Outgoing)(e) MCCBTP 125 amps, 16 KA , 415 volts, 50Hz- 02 Nos,(Outgoing)(f)Digital Panel mounted Amp meter 96 mm square type complete with selector switch complete with suitable size of CT\"s - 01 Set(g) Digital Panel mounted Volt meter 96 mm square type complete with selector switch - 01 Nos.(h)RYB indicating lamp, LED type - 01 sets.(i)Cost of PCC for foundation is deemed to be included in quoted rate by the contractor.(j) Drawing shall be approved by GE before placing the order. |
| 3 | Fabrication, supply, installation, testing and commissioning electrical cubical control panel board( KIOSK TYPE ) Double door, CPRI approved factory assembled made out door feeder pillar box wheather and vermin proof fabricated of 3.15 mm CRCA MS sheet of Suitable size,3 phase 4 wire 415 Volt ac 50 Hz complete duly painted with powder coating complete with locking arrangement, earthing terminals with suitable rating aluminium Bus bars for incoming/outgoing MCCB\"s including and Mounting measuring instrument such as Volt meter, Ammeter, Selector switchs, CT\"s -03 Set, Phase indicator lamps with holder , toggle switches and MCBs etc including incoming and outgoing cables connections with suitable cable glands and end termination including grouting of feeder pillar box 60 cm above ground level by providing 105 cm long angle iron size 50x50x6mm welded onall four corner embedded in PCC (1:2:4) using 20mm graded upto 45cm and frame structure of panel will be made angle iron of size 50 x 50 x 6 mm. complete all as specified and directed. ( Feeder piller box shall be consisting the following)(a)4 Nos electrolytic aluminium bus bars high conductivity aluminium alloy proper insulated of Rating 2000 Amps with provision of extension and mounting on porcelain support(b) ACB 1250 amp FP, 415 volts, with Thermal Magnetic Release (Manual Drawout type), 50Hz = 01 No (Incoming)(c)MCCBTP 400 amps, 36 KA , 415 volts, 50Hz - 01 Nos (Outgoing)(d) MCCB TP 250 amps, 25 KA , 415 volts, 50Hz- 02 Nos,(Outgoing)(e) MCCB TP 200 amps, 25 KA , 415 volts, 50Hz- 01 Nos,(Outgoing) (f) MCCBTP 160 amps, 25 KA , 415 volts, 50Hz- 01 Nos,(Outgoing) (g) MCCB TP 125 amps, 16 KA , 415 volts, 50Hz- 01 Nos,(Outgoing)(h)Digital Panel mounted Amp meter 96 mm square type complete with selector switch complete with suitable size of CT\"s - 01 Set(i) Digital Panel mounted Volt meter 96 mm square type complete with selector switch - 01 Nos(j)RYB indicating lamp, LED type - 01 sets.(k)Cost of PCC for foundation is deemed to be included in quoted rate by the contractor.(l) Drawing shall be approved by GE before placing the order. |
| 4 | M& L, for earthing with galvanised steel earth plate of size 600 x 600 x 6 mm thick burried directly in ground not less than 2.5 mtr below groud level with top edge of earth plate not less than 1.5 meters below ground level connected by 32 X 6 mm GI strip as earth lead by means of brass nuts and bolt, thimbles, check nuts, washers including concrete chamber of PCC 1:3:6 type C1 using 20 mm graded stone aggregate, with fair finish, inetrnal surface of concrete chamber shall be given internal dia 300mm X 300mm , 15 mm thick plaster in CM 1:4 funnel with wire mesh, RCC pit cover of 320 x 320 x 80 mm size (1:2:4) type B1 using 20 mm graded stone aggregate, adequate quantity of common salt, charcoal etc all, as shown in electrical plate No 3 of MES SSR Part-1(2009) and specified incuding and provision of GI strip upto 7.5 mtr long with 40 mm dia light grade GI pipe protection and watering pipe of GI 20 mm bore, Medium grade, including all excavation and earthn work and connecting the earth strip to an earthing test point/panel including testing on completion complete alll as specified and directed. |
| 5 | Disconnecting existing cables fromincomer and outgoingACB, mccbs of existing panel cleaning the complete surface of the panel, including removal of rust, dirt, loose paint, and moisture using sandpaper , brush or blower. Jointing ofbroken door with welding and other required accessoriesi.e Kabja, hing etc.Preparation of LT panel with one coat anti-rust primer and two coats of industrial-grade enamel paint on both sides . cleaning and painting of legs of the panels are included . After painting connections ofthe cables with mccbs of panels with news thimbles/lugs andsuitable size of cable glands with making holes if required and connecting accessories etc. Note: refixing of the panel if required to be included this item. Approx Size of the panel :600mmx300mmx450mm, with following accessories. These accessories will be uninstalled for painting and replacement of store said part. Reinstallation of these parts is included in this item.as directed by Engr in charge. a) No of Incomming ACB 1250 Amp - 01, Size of cable - 180 sq mm to 400mm x 3.5/4 core b) No of OutgoingMCCBs250 Amp- 01, Size of cable - 25 sq mm to 240 sq mm x 3.5/4 Corec) No of OutgoingMCCBs250 Amp-01, Size of cable - 25 sq mm to 240 sq mm x 3.5/4 core d) No of OutgoingMCCBs200 Amp-01, Size of cable - 25 sq mm to 240 sq mm x 3.5/4 coree) No of OutgoingMCCBs63 Amp-01, Size of cable - 25 sq mm to 180sq mm x 3.5/4 core f) No of OutgoingMCCBs160 Amp-01, Size of cable - 25 sq mm to 180sq mm x 3.5/4 core |
| 6 | Fabrication, supply, installation, testing and commissioning electrical cubical control panel board( KIOSK TYPE ) Double door CPRI approved factory assembled made out door feeder pillar box wheather and vermin proof fabricated of 3.15 mm CRCA MS sheet of Suitable size,3 phase 4 wire 415 Volt ac 50 Hz complete duly painted with powder coating complete with locking arrangement, earthing terminals with suitable rating aluminium Bus bars for incoming/outgoing MCCB\"s including and Mounting measuring instrument such as Volt meter, Ammeter, Selector switchs, CT\"s -03 Set, Phase indicator lamps with holder , toggle switches and MCBs etc including incoming and outgoing cables connections with suitable cable glands and end termination including grouting of feeder pillar box 60 cm above ground level by providing 105 cm long angle iron size 50x50x6mm welded onall four corner embedded in PCC (1:2:4) using 20mm graded upto 45cm and frame structure of panel will be made angle iron of size 50 x 50 x 6 mm. complete all as specified and directed. ( Feeder piller box shall be consisting the following)(a)4 Nos electrolytic aluminium bus bars high conductivity aluminium alloy proper insulated of Rating 1000 Amps with provision of extension and mounting on porcelain insulators.(b)ACB630 amps, 415 volts, 50Hz Manual drawout type = 01 No (Incoming)(c)MCCBTP 200 amps, 36 KA , 415 volts, 50Hz - 02 Nos (Outgoing)(d) MCCB TP 120 amps, 16 KA , 415 volts, 50Hz- 03 Nos,(Outgoing)(e) MCCBTP 63 amps, 16 KA , 415 volts, 50Hz- 03 Nos,(Outgoing)(f)Digital Panel mounted Amp meter 96 mm square type complete with selector switch complete with suitable size of CT\"s - 01 Set(g) Digital Panel mounted Volt meter 96 mm square type complete with selector switch - 01 Nos (h)RYB indicating lamp, LED type - 01 sets.(i)Cost of PCC for foundation is deemed to be included in quoted rate by the contractor.(j) Drawing shall be approved by GE before placing the order. |
| 7 | Disconnecting existing cables fromincomer and outgoingACB, mccbs of existing panelcleaning the complete surface of the panel, including removal of rust, dirt, loose paint, and moisture using sandpaper , brush or blower. Jointing ofbroken door with welding and other required accessoriesi.e Kabja, hing etc.Preparation of LT panel with one coat anti-rust primer and two coats of industrial-grade enamel paint on both sides . cleaning and painting of legs of the panels are included . After painting connections ofthe cables with mccbs of panels with news thimbles/lugs andsuitable size of cable glands with making holes if required and connecting accessories etc. Note: refixing of the panel if required to be included this item. Approx Size of the panel :600mmx300mmx450mm, with following accessories. These accessories will be uninstalled for painting and replacement of store said part. Reinstallation of these parts is included in this item.as directed by Engr in charge. a) No of Incomming ACB 1250 Amp - 01, Size of cable - 180 sq mm to400 sq mm x 3.4/4 core lead b) No of OutgoingMCCBs200 Amp- 01, Size of cable - 25 sq mm to 150 sq mm x 3.5/4 Core c) No of OutgoingMCCBs125 Amp-01, Size of cable - 25 sq mm to 150 sq mm x 3.5/4 Core d) No of OutgoingMCCBs160 Amp-01, Size of cable - 25 sq mm to 150 sq mm x 3.5/4 Core e) No of OutgoingMCCBs160 Amp-01, Size of cable - 25 sq mm to 150 sq mm x 3.5/4 Core f) No of OutgoingMCCBs160 Amp-01, Size of cable - 25 sq mm to 150 sq mm x 3.5/4 Coreg) No of OutgoingMCCBs100 Amp-01, Size of cable -25 sq mm to 150 sq mm x 3.5/4 Core |
| 8 | Disconnecting existing cables fromincomer and outgoingACB, mccbs of existing panelcleaning the complete surface of the panel, including removal of rust, dirt, loose paint, and moisture using sandpaper , brush or blower. Jointing ofbroken door with welding and other required accessoriesi.e Kabja, hing etc.Preparation of LT panel with one coat anti-rust primer and two coats of industrial-grade enamel paint on both sides . cleaning and painting of legs of the panels are included . After painting connections ofthe cables with mccbs of panels with news thimbles/lugs andsuitable size of cable glands with making holes if required and connecting accessories etc. Note: refixing of the panel if required to be included this item. Approx Size of the panel :600mmx300mmx450mm. These accessories will be uninstalled for painting and replacement of store said part. Reinstallation of these parts is included in this item.as directed by Engr in charge. a) No of Incomming MCCBs 250 Amp - 01, Size of cable -25 sq mm to 150 sq mm x 3.5/4 Core b) No of OutgoingMCCBs200 Amp- 01, Size of cable - 25 sq mm to 150 sq mm x 3.5/4 Core c) No of OutgoingMCCBs200 Amp-01, Size of cable - 25 sq mm to 150 sq mm x 3.5/4 Cored) No of OutgoingMCCBs100 Amp-01, Size of cable - 25 sq mm to 150 sq mm x 3.5/4 Coree) No of OutgoingMCCBs100 Amp-01, Size of cable - 25 sq mm to 150 sq mm x 3.5/4 Core f) No of OutgoingMCCBs100 Amp-01, Size of cable - 25 sq mm to 150 sq mm x 3.5/4 Core |
| 9 | Disconnecting carefully old unsericeable Ammeter from panel board and supply & fix of new 96 mm size square digital type ammeter of range 0-100 Ampere with set of CTs of suitable rating Supply and laying or fixing. complete all as specified & directed. |
| 10 | Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv (size 2x1m) for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m.complete all as specified & directed. |