| 1 | Total amount ofSchedule \"A\" PART-I (BUILDING WORK) |
| 2 | Total amount ofSch \"A\" PART-II(SHED WITH STEEL STRUCTURE) |
| 3 | Total amount ofSch \"A\" PART-III (DEMOLITION AND DISMANTLING WORK) |
| 4 | Total amount ofSch \"A\" PART-IV ( EARTH WORK AND SITE DEVELOPMENT WORK) |
| 5 | Total amount ofSch \"A\" PART-V ( RETAINING WALL ) |
| 6 | Total amount ofSch \"A\" PART-VI ( Section-I) (INTERNAL ELECTRIFICATION) |
| 7 | Sch \"A\" PART-VI ( Section-II)( INTERNAL ELECTRIC SUPPLY WORKS)Note : This schedule is not pre priced by MES and the pre priced rate indicated as \"Rs. 0.00\" under Col.5 signifies this fact only. |
| 8 | Supply and fixing LED light fitting 2x20 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable all as specified and directed.Make: Pluto cat part no PFC/LED/1036 / Sudhir / Shyam. |
| 9 | Supply and Fixing of Flameproof /weatherproof flood light fitting of 100W, IP66 protection of Cast Aluminum alloy material and Heat and Impact resistance toughen \"A\" clear glass having Anti corrosive epoxy powder coated finish complete with all accessories pre wired and including connecting up with three core flexible copper conductor cable with suitable size all as specified and directed.Make: pluto cat part no PFC/LED/2004 / Sudhir / Shyam. |
| 10 | M&Lof flame proofLighting distribution panel board minimum size (400x400x190 mm) encloser Triple pole & neutral 415 volts TPN 4 way complete with appropriate size copper bus bar and neutral link suitable for class 1 Zone 1 & EX IIC suitable for & including following accessories:(i) incomming : MCCB 4P,63 Amps-1No, ICS=100% of ICU adjustable type 0.8In to 1.0 In Out going: MCB 1P ,6 Amps/10/16 A-12 Noswith internal busbar & wiring up to terminalMake: Sudhir /Pluto cat part no PFC/IB/1030 / Shyam.Note: cable glands for termination of cable shall deemed to be included in the quoted rate. |
| 11 | M&Lof flame proofLighting distribution panel board minimum size (250x250 mm)encloser single pole & neutral 240 volts SPN 4 way complete with appropriate size copper bus bar and neutral link suitable for class 1Zone 1 & Ex iIC suitable for & including following accessories:(i) incomming : MCB 2P,16 Amps-1NoOut going: MCB 1P ,6 Amps-2 Noswith internal busbar & wiring up to terminalMake: Sudhir / Pluto cat part no PFC/IB/12/ Shyam.Note: cable glands for termination of cable shall deemed to be included in the quoted rate. |
| 12 | Supply and fixing Flame proof Weather proof 18\" 0.25 HPsingle phase exhaust fan all as specified qand directed. Make: Pluto cat part no PFC/EF/2040. |
| 13 | Supply and fixing Flame proof Weather proof 48\"single phase ceiling fan with regulator all as specified and directed. Make: Pluto cat part no PFC/EF/2040. |
| 14 | Total amount ofSch \"A\" PART-VI (Section-II) (INTERNAL ELECTRIC SUPPLY WORK) |
| 15 | Total amount ofSch \"A\" PART-VII (CULVERT ) |
| 16 | Total amount ofSch \"A\" PART-VIII( Section-I)PAVMENT ( PQC) WORKS |
| 17 | Sch \"A\" PART-VIII (SECTION-II)PAVMENT ( PQC) WORKS Note : This schedule is not pre priced by MES and the pre priced rate indicated as \"Rs. 0.00\" under Col.5 signifies this fact only. |
| 18 | Material and labour for soil subgrade (earth filling in floors or pavings) stabilised with 3% cement (OPC-43), laid and compacted in two layers of 250mm thick each, spread, levelled and rammed including watering to achieve 97% MOD & k-value of min 5kg /Sq.cm, complete all as specified and as directed. ( Soil obtained from earth work item shall be reused ) |
| 19 | Total amount ofSch \"A\" PART-VIII (SECTION-II)PAVMENT ( PQC) WORKS |
| 20 | Total amount ofSch \"A\" PART-IX (Section-I)(AREA DRAINAGE) |
| 21 | Total amount ofSch \"A\" PART- X( Section-I) (EXTERNAL ELECTRIFICATION ) |
| 22 | SCHEDULE `A\" PART-X( Section-II) (EXTERNAL ELECTRIFICATION ) Note : This schedule is not pre priced by MES and the pre priced rate indicated as \"Rs. 0.00\" under Col.5 signifies this fact only. |
| 23 | Disconnecting /dismantling of Existing HT bus bar box and Supply, installation, Testing & Commissioning of (1 LBS+4 VCB) 5way RMU, non- extendible outdoor type of rating 630 A aluminium busbar with a fault clearing capacity of 21 KA for 3 Sec, rated voltage 12 KV, operational voltage - 11 KV, frequency- 50 hz, totally enclosed Ring Main UnitSF6 gas filled with IP 65 protection for outdoor enclosure with selfpowered microprocessor based numerical relay with over current and earth fault protection. Entire RMU should be tested for internal arc test of 21 KA for 1 Sec as per IEC 62271-200 standards including provision of necessary foundation with PCC (1:3:6), type C-2 complete all as specified and directed. Note: Old HT bus bar box to be deposited at AGE E/M yard. |
| 24 | S&F ofperforated G.I. sheet cable tray of size 150 x 50mm with necessary angle iron suspension supports ,anchor fasteners etc. complete all as specified and directed. Note:- Maximum height of suspension shall not exceed 500 mm. size of the tray shall be suitable for laying the above mentioned cables. |
| 25 | Disconnecting ofexisting overground/underground LTCable of size 25 Sqmm2/4 core to 185 Sqmm 3.5 core cable along with disconnection with LT Panel/Pole or Other electrical equipment withall electrical connection as directd by Engineer -in -chargecomplete including taking down old complete all as specified and directed by Engr-in-Charge of |
| 26 | (a)150 Sqmm,3½ core cable |
| 27 | (b)120 Sqmm,3½ core cable |
| 28 | (a) 70 Sqmm,3½ core cable |
| 29 | (b)50 Sqmm,3½ core cable |
| 30 | Supply and fixing of DWC HDPE tubing 90 mmbore conforming to IS 16205for protection of open/underground laying of cable, cut to size and making thetubing forcable protection including cutting of road etc/cutting of PCC complete all as specified and directed by Engr-in-Charge.Note:- (a) The using of GI Clamp in the wall/drainageare deemed to be included in the quoted rate.(b)Drawing existing cable through DWC pipe shall be deemed to be included in the quoted rates. |
| 31 | Supply and fixing of DWC HDPE tubing 50 mmbore conforming to IS 16205for protection of open/underground laying of cable, cut to size and making thetubing forcable protection including cutting of road etc/cutting of PCC complete all as specified and directed by Engr-in-Charge.Note:- (a) The using of GI Clamp in the wall/drainageare deemed to be included in the quoted rate.(b)Drawing existing cable through DWC pipe shall be deemed to be included in the quoted rates. |
| 32 | Supply and fix 250 watt LED flood light, with IP 66 protection, PF>=0.90, lumen efficiency >=110 Lm/Watt, 5700 k SPD of voltage rating > 10kv luminaire engergy saving, environmental friendly long life with high power led as light source suitable for highlighting architectural feature or area lighting also suitable to rough services /installation complete as specified and directed. Make- Wipro/Crompton/Bajaj |
| 33 | M&L of Automatic High mastlight switch NATURE SWITCHfor automatic switching of High mast lights based on lux level of natural light. The sensor (nature switch ) along with suitable power contactor, MCB and support terminals should be enclosed in pole /wall mountable enclosure made out of rust proof, electric shock proof, termite proof and FR grade special moulding compund (sintex make SMC Junction Box or equivalent as approved by GE ) conforming to IP-54. The contactor, MCB and circuit wiring 16 sqmmcopper shall be suitable enough to take load of 25 KW three phase load /8 KW load equally distributed over 3-phase (8 KW/phase), contactor rating 40 Amps(2 pole)and 40 amps 4 pole and MCB (single pole) rating 63 amps (SP-3 Nos) complete including sheet metal enclosure with stand made of suitable size angle iron and grouting of enclosure using cement concrete 1:2:4 type B-I (using 20mm graded crushed stone aggregate) all as specified and directed by Engineer-in-ChargeMake :-SWADEEP-02EC25kW 3 PHASE/Havells/Hensel or equivalent . |
| 34 | S&Fof heavy duty porcelain/poly carbonate insulators of size 32 x 32 mm to be fixed on wall/roof/pipe for laying of copper strip as roof/down conductor on building of height between upto 25 metres including nuts & bolts of brass of appropriate size all as specified and as directed by Engr-in-Charge. |
| 35 | Supply and fix 100 watt LED flood light, with IP 66 protection, PF>=0.90, lumen efficiency >=110 Lm/Watt, 5700 k engergy saving including driver and surge protection system,environmental friendly long life exclusive innovative die cast aluminium flood light with high power led as lightsource suitable for highlighting architectural feature or area lighting also suitable to rough services /installation incl taking down old one etc complete as specified and directed Make- Wipro/Crompton/Bajaj |
| 36 | Total amount of Schedule A part -X( Section-II) (EXTERNAL ELECTRIFICATION) |