| 1 | Excavation in trenches not exceeding 1.5M wide and not exceeding 1.5M in depth and getting out in soft/loose soil for laying of under ground cable and foundation of poles complete all as specified and directed. |
| 2 | Returning, filling in, including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and directed. |
| 3 | Removing of excavated soft/loose soil not exc 50 m & depositing where as directed at a level n.exc 1.5 m above from starting point completed all as specified and directed. |
| 4 | M&L for sand cushioning with layer of sand 8cm thick before laying of cable and 15cm after laying of cable in trenches, punning complete all as specified and directed (Note:- Punning thickness of 18 cm will be considered for payment.) |
| 5 | M&L for brick protection to cable using old size fly ash bricks, laid flat/length wise perpendicular to the axis of cable complete all as specified and directed. |
| 6 | Laying only oldbricks for protection of cablecomplete all as specified and directed. |
| 7 | S&F in replacement40 mm bore dia GI pipe light grade of following dia for cable protection, fixed to pole/ alongwall/ floor/ under road/ across the drain or nallaha etc complete all as specified and directed. |
| 8 | S&F in replacement50 mm bore dia GI pipe light grade of following dia for cable protection, fixed to pole/ alongwall/ floor/ under road/ across the drain or nallaha etc complete all as specified and directed. |
| 9 | S&F in replacement80 mm bore dia GI pipe light grade of following dia for cable protection, fixed to pole/ alongwall/ floor/ under road/ across the drain or nallaha etc complete all as specified and directed. |
| 10 | Taking out old unserviceable LT cabel any type and size from trenches or fixed on poles or through pipes/ walls/ laid under roads/ paths/ drains/ culvert complete all as specified and directed. |
| 11 | Supply, jointing, laying and testing ofXLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty), conforming to IS 7098 Part-I 1988 with stranded aluminium conductor 1100 volt grade, laid in trenches/ ducts, fixed on wall/ inside panel, drawn through pipe of cross sectional area10 Sqmm 4 core complete all as specified and directed. |
| 12 | All as per Ser item No 11 here-in-before but 25 sqmm 4 core complete all as specified and directed. |
| 13 | All as per Ser item No 11 here-in-before but 50 sqmm 3.5 core complete all as specified and directed. |
| 14 | All as per Ser item No 11 here-in-before but 95 sqmm 3.5 core complete all as specified and directed. |
| 15 | All as per Ser item No 11 here-in-before but 120 sqmm 3.5 core complete all as specified and directed. |
| 16 | All as per Ser item No 11 here-in-before but 185 sqmm 3.5 core complete all as specified and directed. |
| 17 | All as per Ser item No 11 here-in-before but 240 sqmm 3.5 core complete all as specified and directed. |
| 18 | All as per Ser item No 11 here-in-before but 400 sqmm 3.5 core complete all as specified and directed. |
| 19 | S&F heat shrinkable straight through jointing kit suitable for 1100 volts grade XLPE insulated stranded aluminium conductor cable including testing on completion for 25 swmm to 50 sqmm 3.5/ 4 core complete all as specified and directed. |
| 20 | S&F heat shrinkable straight through jointing kit suitable for 1100 volts grade XLPE insulated stranded aluminium conductor cable including testing on completion for 70 swmm to 150 sqmm 3.5 core complete all as specified and directed. |
| 21 | S&F heat shrinkable straight through jointing kit suitable for 1100 volts grade XLPE insulated stranded aluminium conductor cable including testing on completion for 185 swmm to 240 sqmm 3.5 core complete all as specified and directed. |
| 22 | S&F heat shrinkable straight through jointing kit suitable for 1100 volts grade XLPE insulated stranded aluminium conductor cable including testing on completion for 300 swmm to 400 sqmm 3.5 core complete all as specified and directed. |
| 23 | Relaying only serviceable LT UG cable obtained from existing of any size and discription including necessary cable lugs complete all as specified and directed. |
| 24 | M&L for preparing old painted surface of LT panel board indoor/ outdoor type of any size by cleaning removing of the old paint by scraping with wire brush/ sand paper etc. nd including minor repair to panel in different location where required with arc/ gas welding with replacement of hinges and place the door in original position denting/ patching of broken/ rusted surfaces etc and applying two coat of synthetic enamel paint by spray painting on inside/ outside surface of panel complete all as specified and directed. |
| 25 | S&F in replacement cross arms, bracings, supports, clamps, back plate fabricated from structural steel sections such as channels, angles, flat iron including 16mm dia bolts, nuts, washers, welding, bending, cold or hot drilling holes for bolts/insulators in any shape and size as directed and inclusive of one priming coat of red oxide zinc chrome, one under coat and one finishing coat of aluminium paint complete all as specified and directed. |
| 26 | M&L for opening & disconnecting LT cable connections with carefully from Automatic Power Factor Panels of different capacity, checking of the panels installed at sub stations and pump house for testing their operation and mechanical system including detection and replacement of the unserviceable parts/accessories required at site to make the Power Factor Panel completely functional including cleaning/ servicing of complete unit and re-connection of the panel complete all as specified and directed. Note :- Provision of new spare parts as required shall be measured and paid separately.) |
| 27 | M&L for capacitor Heavy duty cylendrical/Square type, 5 KVAr Rating @ 440V, 3Ph, 50Hz including taking out old unserviceable complete all as specified and directed. |
| 28 | M&L for capacitor Heavy duty cylendrical/Square type, 10 KVAr Rating @ 440V, 3Ph, 50Hz including taking out old unserviceable complete all as specified and directed. |
| 29 | M&L for capacitor Heavy duty cylendrical/Square type, 15 KVAr Rating @ 440V, 3Ph, 50Hz including taking out old unserviceable complete all as specified anddirected. |
| 30 | M&L for capacitor Heavy duty cylendrical/Square type, 20 KVAr Rating @ 440V, 3Ph, 50Hz including taking out old unserviceable, complete all as specified and directed. |
| 31 | M&L for capacitor Heavy duty cylendrical/Square type, 25 KVAr Rating @ 440V, 3Ph, 50Hz including taking out old unserviceable, complete all as specified and directed. |
| 32 | M&L for capacitor Heavy duty cylendrical/Square type, 30 KVAr Rating @ 440V, 3Ph, 50Hz including taking out old unserviceable, complete all as specified and directed. |
| 33 | M&L for contactor 20 Amp, 3 pole, 1NO+1NC, MO C, AC3, 415 Vols, 50 Hz confirm to IS/IEC 60947-4-1 incl taking out old unserviceable complete all as specified and directed. |
| 34 | M&L for contactor 25 Amp, 3 pole, 1NO+1NC, MO C, AC3, 415 Vols, 50 Hz confirm to IS/IEC 60947-4-1 incl taking out old unserviceable complete all as specified and directed. |
| 35 | M&L for Contactor 30 Amp, 3 pole, 1NO+1NC, MO C, AC3, 415 Vols, 50 Hz confirm to IS/IEC 60947-4-1 incl taking out old unserviceable omplete all as specified and directed. |
| 36 | M&L for Contactor 40 Amp, 3 pole, 1NO+1NC, MO C, AC3, 415 Vols, 50 Hz confirm to IS/IEC 60947-4-1 incl taking out old unserviceable complete all as specified and directed. |
| 37 | M&L for Automatic Power Factor Controller Relay type Voltage 230 Volt 8 Step with 3 Phase / 3 CTs, connecting Single Phase and Three Phase Capacitors, compensation of each Phase, MeasuresPower Factor with RS-485 including taking out old unserviceable, complete all as specified and directed. |
| 38 | M&L for copper bus bar of size 50 x 6 mm with heat shrinkable PVC HT sleeves with nut bolts and washer of brass and fixing arrangement as required at site complete all as specified and directed. |
| 39 | M&L for LED indicator lamp (R,Y,B,G) including taking down old Unserviceable indicator lamps complete all as specified and directed. |
| 40 | M&L for standard push buttonfor ON/ OFF/ TRIP as per existing at site including taking down old unserviceable push button complete all as specified and directed. |
| 41 | M&L for selector switch for operating of ampere/ voltage including taking down old unserviceable switch complete all as specified and directed. |
| 42 | M&L for LED digital voltmeter, class 0.5 accuracy, 3 Phase, 415 Volts, 50 Hz, flush mounting 96mm x 96mm including taking down old unserviceable voltmeter complete all as specified and directed. |
| 43 | M&L LED digital ammeter, class 0.5 accuracy, 3 Phase, 415 Volts, 50 Hz, flush mounting 96mm x 96mm including taking down old unserviceable ammeter complete all as specified and directed. |
| 44 | M&L for CT suitable for APFC panel of cap 200A/ 5A Cl 1.5 VAcomplete with all necessary connection and remoing of old existing complete all as specified and directed. |
| 45 | M&L for MCB, TPN, 40 Amp, C - Curve 415 Volts, 50 Hz, including taking down old unserviceable MCB, TPN complete all as specified and directed. |
| 46 | M&L for MCB, TPN, 63 Amp, C - Curve 415 Volts, 50 Hz, including taking down old unserviceable MCB, TPN complete all as specified and directed. |
| 47 | M&L forMCB, SP, 6-32 Amp, C - Curve, 240 Volts, 50 Hz, including taking down old unserviceable MCB complete all as specified and directed. |
| 48 | S&F MCCB, 630 amps, 4 pole, 50 KA, with microprocessor based release with electronic Sg (LSIg) protection unit, Ics=100% of Icu with overload, short circuit & ground fault protections with inbuilt display for current metering with high accuracy of class 1, internal battery, communication port, inbuilt USB port for software diagnosis, all accessories including taking down existing MCCB complete all as specified and directed. |
| 49 | S&F MCCB, 400 amps, 4 pole, 50 KA, with microprocessor based release with electronic Sg (LSIg) protection unit, Ics=100% of Icu with overload, short circuit & ground fault protections with inbuilt display for current metering with high accuracy of class 1 , internal battery, communication port, inbuilt USB port for software diagnosis, all accessories including taking down existing MCCB complete all as specified and directed. |
| 50 | S&F MCCB, 250 amps, 4 pole, 36 KA, with microprocessor based release with electronic Sg (LSIg) protection unit, Ics=100% of Icu with overload, short circuit & ground fault protections with inbuilt display for current metering with high accuracy of class 1, internal battery, communication port, inbuilt USB port for software diagnosis, all accessories including taking down existing MCCB complete all as specified and directed. |
| 51 | S&F MCCB, 160 amps, 4 pole, 36 KA, with microprocessor based release with electronic Sg (LSIg) protection unit, Ics=100% of Icu with overload, short circuit & ground fault protections with inbuilt display for current metering with high accuracy of class 1, internal battery, communication port, inbuilt USB port for software diagnosis,all accessories including taking down existing MCCB complete all as specified and directed. |
| 52 | S&F MCCB 4 Pole, 415 V, 200 Amps with adjustable type, breaking capacity 36 KA, Ics=100% of Icu with Copper spreader including taking down existing MCCB complete all as specified and directed |
| 53 | S&F MCCB 4 Pole, 415 V, 100 Amps with adjustable type, breaking capacity 25 KA, Ics=100% of Icu with all accessories including taking down existing MCCB complete all as specified and directed |
| 54 | S&F MCCB 4 Pole, 415 V, 63 Amps with adjustable type, breaking capacity 25 KA, Ics=100% of Icu with all accessories including taking down existing MCCB complete all as specified and directedNote for item No. 35 to 41:-(i) MCCB Should be calibrated at 50°C for accurate performance in higher ambient.(ii) Over load Protection of MCCB should be adjustable 63-100% of nominal Current.(iii) Short Circuit Protection of MCCB shall be adjustable 6 to 10 times in nominal current.(iv) Neutral Protection of MCCB Shall be adjustable to OFF/50% & 100%. |
| 55 | S&F on load Changeover switch 63 Amp three phase, 415 Volts, 50 Hz, Four Pole including taking down old unserviceable complete all as specified and directed. |
| 56 | S&F in repairs on load changeover switch 100 Amp three phase, 415 Volts, 50 Hz, Four Pole including taking down old unsv complete all as specified and directed. |
| 57 | S&F on load changeover switch 200 Amp three phase, 415 Volts, 50 Hz, Four Pole including taking down old unserviceable complete all as specified and directed. |
| 58 | S&F on load Changeover switch 400 Amp three phase, 415 Volts, 50 Hz, Four Pole including taking down old unserviceable complete all as specified and directed. |
| 59 | S&F on load Changeover switch 800 Amp three phase, 415 Volts, 50 Hz, Four Pole including taking down old unserviceable complete all as specified and directed. |
| 60 | S&F on load Changeover switch 1000 Amp three phase, 415 Volts, 50 Hz, Four Pole including taking down old unserviceable complete all as specified and directed. |
| 61 | S&F ACB, 800 amps, 4 pole, with microprocessor based release, Ics=50% of Icu, manual drawout type, with overload, short circuit & ground fault protections with inbuilt display for current metering with high accuracy of class 1, internal battery, communication port, inbuilt USB port for software diagnosis, all accessories including taking down existing ACB complete all as specified and directed. |
| 62 | S&F ACB, 1000 amps, 4 pole, with microprocessor based release, Ics=50% of Icu, manual drawout type, with overload, short circuit & ground fault protections with inbuilt display for current metering with high accuracy of class 1, internal battery, communication port, inbuilt USB port for software diagnosis, all accessories including taking down existing ACB complete all as specified and directed. |
| 63 | S&F ACB, 2000 amps, 4 pole, with microprocessor based release, Ics=50% of Icu, manual drawout type, with overload, short circuit & ground fault protections with inbuilt display for current metering with high accuracy of class 1, internal battery, communication port, inbuilt USB port for software diagnosis, all accessories including taking down existing ACB complete all as specified and directed. |
| 64 | Disconnection of electric connection from APFC Panel of any size dressing of cable including replacement of burnt out aluminium lugs and fixing with new lugs, nuts bolt etc complete including all inter connection with copper cablesuitable current ratingincluding painting of panels incl welding work if reqd complete with inner & outer with two coats ofsynthetic enamelled paint over a coat of primer including excavation & earth work required for taking out & refixing the incoming and out going cable etc complete all as directed. |
| 65 | M&L Repairing Damaged Earth Pit/Chamber in Cement Concrete 1:3:6(20mm graded stone aggregate) as shown in Electrical Plate No 3 of MES Schedule Part-I including providing Pre-cast RCC Cover in Cement Concrete 1:2:4 (20mm graded stone aggregate) of 350x350x50mm in size, reinforced with and including 10mm dia TMT Bars @ 100mm Centre to Centre in both ways including Funnel and cleaning the surrounding of Earth Pit Cover and pouring Salt Water to improve the resistace and measuring and recording the same in presence of Engr-in-Charge, complete all as specified and directed. |
| 66 | M&L for pre-cast RCC Cover in cement concrete 1:2:4 (20mm graded stone aggregate) of size 350x350x50mm, reinforced with and including 10mm dia TMT Bars @ 100mm Centre to centre in both ways, complete all as specified and directed. |
| 67 | M&L cement concrete 1:2:4 (20mm graded stone aggregate) provided Around Earthing Pit having Top size 200x200mm and bottom size 300x300mm having 150mm in height, size of PCC Plateform 900x900x100mm with fair finished Concrete Surfaces including necessary Formwork and Earth Work as required/ordered at Site including dismantling PCC, complete all as specified and directed. |
| 68 | Taking out loose/ displaced serviceable aluminium Strip/ copper strip/ GI strip of any size and any description with Accessories and refixing the same with necessary Fixing Arrangement like Screws, Saddles, Nuts and Bolts, complete all as specified and as directed. NOTE : Cost of Screws, Saddles, Nuts and Bolts, etc. will deemed to be included in the Quoted Unit Rate. |
| 69 | S&F GI tubing 50mm bore medium grade in trenches/ floor/ fixed along pole for cable/ earth strip protection with proper size of clamp, nuts and bolts or for fixing lightening conductors etc complete all as specified and directed. |
| 70 | M&L for PCC (1:2:4) type B-1 using 20 mm graded crushed stone aggregate as in coping of poles / pipes / strip alignment etc using necessary formwork and finishing the exposed surfaces even and smooth without using extra cement complete all as specified and directed. |
| 71 | S&F porcelain insulator of size 50mm with fixing arrangements including taking down old unserviceable complete all as specified and directed. |
| 72 | M&L in repair for aluminium Strip of size 25 x 3.00 mm fixed to wall or on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc.including taking down old unserviceable strip complete all as specified and directed. |
| 73 | M&L in repairs for copper strip 20mm x 3.00mm with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as directed. |
| 74 | M&L for galvanized Iron Strip of size 25 x 4.00 mm fixed to wall or on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc.including taking down old unserviceable strip complete all as specified and directed. |
| 75 | M&L for galvanized iron strip of size 32 x 6.00 mm fixed to wall or on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc.including taking down old unserviceable strip complete all as specified and directed. |
| 76 | M&L in repairs of earth continuity conductor or main earthing lead 4mm dia fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire including taking down unserviceable strip complete all as specified and directed. |
| 77 | S&F in repair air termination, single pointed, Aluminium rod 12mm dia and 300mm long complete all as specified and directed. |
| 78 | S&F in repair air termination, single pointed, copper rod 12mm dia and 300mm long complete all as specified and directed. |
| 79 | S&F in repairs of Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and directed. |
| 80 | S&F in repair Integrated LED Solar street light fitting 20 Watt with integrated solar panel, 150 lumen per watt, CCT 5700K, in built lithium ion phosphatebattery and highly efficient high power LEDs with secondary optics offering precise distribution and control. The aluminium body acts as an excellent heat sink for better luminaire and LED life, with PIR motions detectors add to extended battery life during non peak hours of operation, IP 66, compete all as specified and directed. |
| 81 | M&L in replacement Earthing complete with Galvanised iron earth plate electrode 600mm x 600mm x 6mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below ground level connected with GI wire 4.00 dia connected with nuts, bots, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe 25mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (reinforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessaryearth work in excavation, returning filling and removal of surplus earth upto a distance not esceeding 50 Mtr etc all as shown on electrical plate No.3 of MES Schedule Part-I complete and testing on completion. |
| 82 | M&L in replacement Earthing complete with Galvanised iron earth plate electrode 600mm x 600mm x 6mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below ground level connected with galvanised earthing strip of size 25mm x 4mm by means of nuts, bots, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe 40mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (reinforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessaryearth work in excavation, returning filling and removal of surplus earth upto a distance not esceeding 50 Mtr etc all as shown on electrical plate No.3 of MES Schedule Part-I complete and testing on completion. |