| 1 | Material and labour for sub main wiring (concealed/surface) complete with two single core 4 Sqmm FRLSH PVC insulated unsheathed stranded copper conductor cable drawn through in and including 20 mm dia rigid non-metallic PVC conduit heavy grade and conduit accessories including 4 Sqmm FRLSH PVC insulated unsheated stranded copper earth cable connected to common earth dolly complete and including cutting chasing in walls for concealed wiring using machine cutting and making good the disturbed surface all as specified and directed. Make of cable : Polycab, Finolex, Havells. Note: 3 run of 4 sqmm&one run of PVC conduit shall be measuredas single unit. |
| 2 | Supply and fix power unit with 20A SP MCB alongwith 20 A Plugfor AC upto 2 ton, 3 module, 240 volts all as specified and directed. Make: Legrand , Seimens, Anchor Roma, Havells |
| 3 | Supply and fix MCB SP 6-32Amps, breaking capacity 10 KA \"C\" curve confirming to IS/IEC 60898-1 2002,integrated label holder, sliding bottom clamp , IP 20 protected terminal, sliding shutters, 240 volts, 50 HZ including making necessary incoming and outgoing electrical connection with suitable size of copper lugs etc, complete all as specified and directed.Make : Legrandor equivalent in ABB,Seimens |
| 4 | Supply and fix MCB TPN40-100 Amps, breaking capacity 10 KA \"C\" curve confirming to IS/IEC 60898-1 2002,integrated label holder, sliding bottom clamp , IP 20 protected terminal, sliding shutters, 240 volts, 50 HZ including making necessary incoming and outgoing electrical connection with suitable size of copper lugs etc, complete all as specified and directed. Make : Legrand , ABB , Seimens |
| 5 | Material and labour for laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade withstranded aluminum conductor of size 35 sqmm 4 Core all as per IS , complete all as specified and directed. |
| 6 | Material and labour for laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade withstranded aluminum conductor of size 50 sqmm3.5 Core all as per IS , complete all as specified and directed. |
| 7 | Material and labour for laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade withstranded aluminum conductor of size 150 sqmm3.5 Core all as per IS , complete all as specified and directed. |
| 8 | Material and labour for laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade withstranded aluminum conductor of size 120 sqmm3.5 Core all as per IS , complete all as specified and directed. |
| 9 | Material and labour for laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade withstranded aluminum conductor of size 185 sqmm3.5 Core all as per IS , complete all as specified and directed. |
| 10 | Material and labour for laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade withstranded aluminum conductor of size 240 sqmm3.5 Core all as per IS , complete all as specified and directed.. |
| 11 | Excavationin trenches not exceeding 1.5 metre wide & not exceeding 1.5 meter in depth for foundation,laying of cable or pipe ( where provided for protection of cable or fixing with poles and stays) and getting out in any type of soilincluding trimming the sides and forming bottom surfaces to required levelscomplete all as specified and directed. |
| 12 | Removing surplus excavated soil to a distance n.exc. 50 metre anddepositing where directed at a level n.exc.1.5 metre high from the starting point. |
| 13 | Returning, filling in trenches in soft/loose soil in layers n.exc. 25 cmafter laying of cables including spreading, levelling, and well ramming complete all as specified and directed. |
| 14 | Boring of hole under road/pavement/hard standing or any other situation by mannual means and suitable for passing of HDPE pipe 40 to 100 mm bore and making good both ends all specified and directed |
| 15 | Material and labour for High density polyethylene pipes (HDPE) DWC duct pipe of size 50 mm inner dia laid in trenches for passing of LT cable complete all as specified and directed. |
| 16 | Material and labour for High density polyethylene pipes (HDPE) DWC duct pipe of size 90 mm inner dia laid in trenches for passing of LT cable complete all as specified and directed. |
| 17 | Material and labour for demolition of Hardstanding , road & concrete in floor for laying of LT cable and making goodthe disturbed surfaces of floor by applying cement plaster matching with the existing surfaces complete all as directed. |
| 18 | Material and labour for PCC 1:3:6 type C-2 (using 40 mm gradded aggregate) for foundation, filling and mass concrete etc complete all as specified and directed . |
| 19 | Note : The amount against Schedule of Credit on Page No. 23 shall be deducted from the total amountquoted against Sch \"A\"while deriving lum Sum for Acceptance. |