| 1 | Taking down carefully existing surface / concealed unserviceable aluminum/ copper point wiring (light, fan, socket, power or sunken box) complete including fittings such as switches, ceiling roses, pendants, regulators, sockets, bracket holder, boards light fittings etc. and making good to disturbed surfaces of walls, floors, ceilings etc. where required and finished the existing surfaces after complete of new point wiring, complete all as specified and directed. |
| 2 | Taking down unserviceable sub main wiring of any type and any size including wooden batten, PVC conduit or casing caping, complete all as specified and directed. |
| 3 | Taking down unserviceable main switch / DBs of any size and capacity including MCB of any type & capacity for reuse, carefully disconnecting and making good to disturbed surfaces to match with existing surface, complete all as specified and directed. |
| 4 | M&L for point wiring using approved color coding as per IS code (Red, Black and Green for single phase circuit) with multi stranded copper condutor 1.5 Sqmm nominal cross section area, single core, PVC insulated and unsheathed FRLSH cable 1100V grade in and including medium grade,PVC concealed conduit ISI marked of dia not less than 20mm and conduit accessories, concealed in wall/ roof/ floor etc. with terminated to new pressed flush metal box and readily available cover with outer plates and inner plates etc, suitable for mounting modular type switches, sockets, fan regulators etc. and PVC insulated multistranded copper condutor 1.5 Sqmm nominal cross section area, single core FRLSH cable as earth continuity conductor to common earth and connecting to earth dolly, complete all as specified and directed for the followings :- One Light Point, controlled by one, one way switch. |
| 5 | All as per serial item No. 4.00 here-in-above but for one ceiling fan point, controlled by one way switch. |
| 6 | All as per serial item No. 4.00 here-in-above but for one exhaust fan, controlled by one way switch. |
| 7 | All as per serial item No. 4.00 here-in-above but for one bell point, controlled by one way switch. |
| 8 | All as per serial item No. 4.00 here-in-above but for 3 Pin 5 Amp socket on the same board with other switches. |
| 9 | All as per serial item No. 4.00 here-in-above but 3 Pin 5 Amp Socket on independent board. |
| 10 | All as per serial item No. 4.00 here-in-above but one light point, controlled by two way switch. |
| 11 | All as per serial item No. 4.00 here-in-above but for point wiring with two runs of FRLSH PVC insulated unsheathed, 1100 V grade cable multi stranded copper conductor of size 2.5 Sqmm, drawn through in and including PVC conduit size of not less than 25mm concecled in wall / surface. |
| 12 | All as per serial item No. 4.00 here-in-above but for geyser / AC point with 4 Sqmm on independent board including 4 Sqmm multi stranded copper conductor earth wire connected to common earth/ earth dolly complete. |
| 13 | S&F modular switch, single pole, one way, 6 Amps, 240 volts with polycarbonate body, complete all as specified and directed. |
| 14 | S&F modular socket, 6 Amps, 5 pin, flush type, 240 volts with polycarbonate body, complete all as specified and directed. |
| 15 | S&F modular socket outlet, 5 pin, 6 Amps and 15 amps, multipurpose 2 in 1, flush type, 230 volts with polycarbonate body, complete all as specified and directed. |
| 16 | S&F modular switch, single pole, one way, 16 Amps, 240 volts with polycarbonate body, complete all as specified and directed. |
| 17 | S&F modular switch, single pole, two way, 6 Amps, 240 volts with polycarbonate body, complete all as specified and directed. |
| 18 | S&F modular electronic fan regulator, step type, two module, 120 watt, 230 Volt and making all necessary connections, complete all as specified and directed. |
| 19 | S&F modular bell push, 6 Amps, 1 module, complete all as specified and directed. |
| 20 | S&F call bell, ding dong type, complete all as specified and directed. |
| 21 | S&F ceiling rose surface bakelite type, size 65x50mm three terminals, complete all as specified and directed.Notes for serial item Nos 7.00 to 15.00 :- (a) Make of fittings shall only be approved by GE/EIC OR as per existing fittings or site requirement as approved by GE/EIC before execution of work. No claim whatsoever shall be entertained on this acount. |
| 22 | M&L for point wiring using approved color coding as per IS code (Red, Black and Green for single phase circuit) with multi stranded copper condutor 1.5 Sqmm nominal cross section area, single core, PVC insulated and unsheathed FRLSH cable 1100V grade, in and including medium grade PVC concealed conduit ISI marked of dia not less than 20mm and conduilt accessories, concealed in wall/ roof/ floor etc. with including Tee, Junction boxes and provision of 3mm thick plastic laminated sheet cover of suitable size on existing terminal boxes with new brass screws for mounting switch, sockets and regulators and drawing continuous earth wire with and including PVC sheathed 1100 Volts grade cable with stranded copper conductor of size 1.5 Sqmm (Nominal area) and connected to main earth dolly, complete all as specified and directed for the followings :- One Light Point, controlled by one way switch. |
| 23 | All as per serial item No. 16.00 here-in-above but for one ceiling fan point, controlled by one way switch. |
| 24 | All as per serial item No. 16.00 here-in-above but for one exhaust fan point, controlled by one way switch. |
| 25 | All as per serial item No. 16.00 here-in-above but for one bell point, controlled by one way switch. |
| 26 | All as per serial item No. 16.00 here-in-above but for 3 Pin 5 Amp socket on the same board with other switches. |
| 27 | All as per serial item No. 16.00 here-in-above but for 3 Pin, 5 Amp, socket on independent board, complete all as specified and directed. |
| 28 | All as per serial item No. 16.00 here-in-above but one light point, controlled by two way switch. |
| 29 | All as per serial item No. 16.00 here-in-above but for point wiring with two runs of FRLSH PVC insulated unsheathed, 1100 V grade cable multi stranded copper conductor of size 2.5 Sqmm, drawn through in and including PVC conduit size of not less than 25mm concecled in wall / surface. |
| 30 | S&F switch piano, flush type, ivory finish, 5/6 Ampere, single pole, one way with marking as light, complete all as specified and directed. |
| 31 | S&F socket outlet 2 in 1, 3 Pin, suitable for 5/6 Ampere in same board, flush type, complete all as specified and directed. |
| 32 | S&F switch piano, flush type, ivory finish, 15/16 Ampere, single pole, one way with marking as light, complete all as specified and directed. |
| 33 | S&F socket outlet, multipurpose, 2 in 1, 3 Pin suitable for 5/6 Amp and 3 Pin suitable 15/16 Ampere, flush type, complete all as specified and directed. |
| 34 | S&F switch socket outlet combination 2 in 1, 3 Pin suitable for 5/6 Ampere for independant board, flush type, complete all as specified and directed. |
| 35 | S&F switch socket combination, flush type, multipurpose, 3 pin 16 Amps and one 3 pin 6 Amps, controlled by one switch with fuse & neon indicator, ISI Marked, complete all as specified and directed. |
| 36 | S&F bell push, ivory finish, 5/6 Ampere, single pole, one way, complete all as specified and directed. |
| 37 | S&F one 5/6 Amp, two way switch, complete all as specified and directed. |
| 38 | S&F stepped type 5 steps, 100 watts electronic fan regulator, flush type on the existing phenolic laminated sheets etc. as required, complete all as specified and directed. |
| 39 | S&F modular white cover plate with frame, 1 module, complete all as specified and directed. |
| 40 | All as per serial item No. 27.00 here-in-above but 2 module. |
| 41 | All as per serial item No. 27.00 here-in-above but 3 module. |
| 42 | All as per serial item No. 27.00 here-in-above but 4/5/6 module. |
| 43 | All as per serial item No. 27.00 here-in-above but 8 module. |
| 44 | All as per serial item No. 27.00 here-in-above but 12 module. |
| 45 | S&F in replacement modular metal flush box with 1.6mm thick, 1/2 module, flushing mounting in the wall for fitting cover plate with frame on switchs / sockets, complete all as specified and directed. |
| 46 | All as per serial item No. 33.00 here-in-above but 3 module. |
| 47 | All as per serial item No. 33.00 here-in-above but 6 module. |
| 48 | All as per serial item No. 33.00 here-in-above but 8 module. |
| 49 | All as per serial item No. 33.00 here-in-above but 12 module. |
| 50 | M&L for sub main wiring with two run single core 1.5 Sqmm FRLSH copper conductor cable PVC insulated, unsheathed, 1100 V grade including 25mm dia in PVC concealed conduit/ PVC casing & caping medium grade ISI marked with all accessories such as Tees, elbows, junctgion boxes etc. as required, fixed on wall alongwith one run of 1.5 Sqmm single core PVC FRLSH insulated unsheathed copper conductor cable as continuous earth wire and connecting to existing main switch board/ distribution board complete including taking down unserviceable submain of any type and size and testing on completion etc, complete all as specified and directed.Note :- Two runs of 1.5 Sqmm and one run 1.5 Sqmm cable and one run of PVC conduit shall be measured as one RM/ Unit. |
| 51 | All as per serial item No. 38.00 here-in-above but using two run single core 2.5 Sqmm FRLSH copper conductor cable PVC insulated, 1100 V grade alongwith one run of 2.5 Sqmm single core PVC FRLSH insulated unsheathed copper conductor cable as continuous earth wire and connecting to existing main switch board/ distribution board complete.Note :- Two runs of 2.5 Sqmm and one run 2.5 Sqmm cable and one run of PVC conduit shall be measured as one RM. |
| 52 | All as per serial item No. 38.00 here-in-above but using two run single core 4.0 Sqmm FRLSH copper conductor cable PVC insulated, 1100 V grade alongwith one run of 4.0 Sqmm single core PVC FRLSH insulated unsheathed copper conductor cable as continuous earth wire and connecting to existing main switch board/ distribution board complete.Note :- Two runs of 4.0 Sqmm and one run 4.0 Sqmm cable and one run of PVC conduit shall be measured as one RM. |
| 53 | All as per serial item No. 38.00 here-in-above but using two run single core 6.0 Sqmm FRLSH copper conductor cable PVC insulated, 1100 V grade alongwith one run of 6.0 Sqmm single core PVC FRLSH insulated unsheathed copper conductor cable as continuous earth wire and connecting to existing main switch board/ distribution board complete.Note :- Two runs of 6.0 Sqmm and one run 6.0 Sqmm cable and one run of PVC conduit shall be measured as one RM. |
| 54 | S&F in replacement single pole and neutral sheet metal steel powder coated distribution board for MCBs, fitted with bus bar neutral link earth bar and din rail suitable for use on 240 V, 50 Hz, double door, 4 Way, complete all as specified and directed. |
| 55 | All as per serial item No. 42.00 here-in-above but 6 Way. |
| 56 | All as per serial item No. 42.00 here-in-above but 8 Way. |
| 57 | All as per serial item No. 42.00 here-in-above but 12 Way. |
| 58 | All as per serial item No. 42.00 here-in-above but size double door MCB DB, TPN 4 ways, 415 volts grade IP-43 Protection. |
| 59 | S&F in replacement VTPN MCCB double door distribution board, 4 Way, 415 Volts grade IP-43 Protection with provision for MCCB as incoming and three / single phase (TP/SP) outgoings, complete with insulated bus bar arrangements, fixed/ flush to wall complete including connections with and including necessary reducer lugs, complete all as specified and directed. |
| 60 | S&F in replacement of MCCB, 4 Pole, 63 Amps, 415 Volts, 16 KA, Ics=100% Icu, Adjustable Overload Setting Ir = (0.8 to 1.0)xIn, short sircuit setting, fixed Thermal magnetic, complete all as specified and directed. |
| 61 | All as per serial item No. 48.00 here-in-above but capacity 100 Amps. |
| 62 | All as per serial item No. 48.00 here-in-above but capacity 125 Amps. |
| 63 | S&F in replacement connection and testing \"C\" series TPN MCB 40 to 63 Amp, 440 V, 50 Hz, 10 KA for lighting and other domestic loads include necessary copper lugs etc, complete all as specified and directed. |
| 64 | All as per serial item No. 51.00 here-in-above but SPN MCB 40 to 63 Amp, 240 V, 50 Hz, 10 KA. |
| 65 | All as per serial item No. 51.00 here-in-above but SPN MCB 32 Amp, 240 V, 50 Hz, 10 KA. |
| 66 | All as per serial item No. 51.00 here-in-above but SP MCB 6-32 Amp, 240 V, 50 Hz, 10 KA. |
| 67 | All as per serial item No. 51.00 here-in-above but SP MCB 40 Amp, 240 V, 50 Hz, 10 KA. |
| 68 | All as per serial item No. 51.00 here-in-above but SP MCB 63 Amp, 240 V, 50 Hz, 10 KA. |
| 69 | S&F in replacement of LED light fitting with high output diffuser 20 watt 220 Volts, Trimline Neu is a robust and high performance batten. This LED luminaire comprises of extruded channel in thermally conductive material. High translucent serrated milky white/warm white diffuseris used to get glare free and smooth light distribution. Efficacy: 100 lm/W. Also available in warm white and natural whiteconnecting up with three core flexible copper conductor cable of suitable size, complete all as specified and directed. |
| 70 | All as per serial item No. 57.00 here-in-above but 2 feet, 10 watt. |
| 71 | S&F in replacement LED bulk head (6500K) fitting of 9/10 Watt, surface mounting type, extruded polycorbonate body with diffuser complete with testing, CRI > 80, IP - 20, CCT - 6500K. complete all as specified and directed. |
| 72 | S&F in replacement ceiling mounting LED warm light fitting POLARIS PAN NIO-III,PANEL 2\"x2\" PLR 36 FO-ww, 35/36 watt LED environmental friendly, new generation, aesthetically designed, ultra modern recess mounting luminaire with high brightness SMD LEDs as light source suitable for Armstrong / grid / ceiling, CRI > 80, IP - 20, CCT - 6500K, complete all as specified and directed. |
| 73 | S&F in replacement of decorative wall mounting chrome finish fixture with opal glass diffuser suitable for 7.5 Watt A60 LED filament lamp E27 base including with LED lamp, complete all as specified and directed. |
| 74 | S&F in replacement of surface / recessed mounting LED down lighter, round/ square shape, 10/12 Watt, 220 volts, AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size, complete all as specified and directed. |
| 75 | All as per serial item No. 62.00 here-in-above but 15 Watt. |
| 76 | All as per serial item No. 62.00 here-in-above but 20/22 Watt. |
| 77 | S&F in replacement surface mounting LED, square shape, 18 Watt (size 1\" x 1\"),220 volts, AC, recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size, complete all as specified and directed. |
| 78 | S&F energy saving LED garden light fitting, pressure die cast, powder coated housing with PC diffuser. Efficient high output LED with IP-65 protection decorative, bollard type of capacity 9/10 watt with opal diffuser & aluminium reflector complete with all accessories and fixing arrangement on PCC block of size 45cm x 45cm alogwith fixing nuts, bolts and PVC insulated aluminium conductor stranded type of size 4.0 Sqmm 2 Core including taking down old unserviceable garden light fitting of any type and wattage, complete all as specified and directed. |
| 79 | S&F in replacement LED street light fitting, 35 Watt, 230 Volts, AC,IP-66 protection, efficacy ≥ 110 lm/W, outdoor type with high pressure die cast aluminum housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with and including 0.60 mtr long 20/25mm (as per manufacturer\"s standard) dia GI Pipe in 45 degree bend shape and necessary clamping devices required at site, complete all as specified and directed. |
| 80 | S&F decorative 20 Watt LED decorative gate light fitting, 240 Volts, made up of high grade unbreakable polycarbonate material, suitable for 20 Watt LED lamp B22 base with opening die cast cover, anti corrosive stainless steel screws and silicon gasket, HET PMMA diffuser, IP-65 protection driver duly prewired upto terminal on firms to IS:10322 Part 5, Sec 1:1987, suitable for pole of dia 40-75mm inbuilt electronic driver including taking down old unserviceable gate light fitting of any type, complete all as specified and directed. |
| 81 | S&F in replacement metal clad plug socket, single pole enclosure with two pin earth plug and socket with one single 20 Amp, 240 volts MCB, complete all as specified and directed. |
| 82 | M&L for earthing complete with galvanized steel earth plate electrode of size 600x600x6mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to earth lead wire of GI strip of size 25x4mm dia by means of nuts, bolts, washers and check nuts of galvanized iron and including 40mm bore GI pipe light grade upto 1.5 mtr below GL as protection pipe and excavation, earth work, charcoal dust, common salt, PCC 1:3:6 type C-1 chamber with cover and RCC 1:2:4 type B-1 (using 20mm graded crushed) stone aggregate, reinforced with 6mm dia round bars @ 75mm c/c both way with MS handle 12mm dia, PGI funnel and wire mesh, complete all as shown in electrical plate No. 3 of SSR Part-I and connected to earthing test point including testing on completion, complete all as specified and directed. |
| 83 | Supply, laying and testing of cable XLPE insulated screened PVC bedded, galvanized steel strip, electric power cables (heavy duty) with aluminium conductor of size 6 Sqmm 2 Core, 1100 Volts grade including cable glands, lugs, saddling on wall (if required), nuts, bolts and washers of suitable size including taking out old unserviceable cable, complete all specified and directed. |
| 84 | Excavation in trenches, exceeding 1.50 mtr wide and not exceeding 1.50 mtr in depth for foundation, electric pole, laying of UG cables/ pipes etc. and getting out in any type of soil, complete all as specified and directed. |
| 85 | Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick, complete all as specified and directed. |
| 86 | Removing excavated material to a distance exc. 50 mtr and depositing where directed at a level not exc. 1.5 mtr above the starting point, complete all as specified and directed. |
| 87 | M&L for dry river sand as in cushioning to underground cables, provided with a layer of sand 8cm thick before laying the cable and 15cm thick after laying the cable and stretching the cable, complete all as specified and directed. |
| 88 | Supply and laying sub class \"B\", old size brick, well burnt as covering or mechanical protection to UG cable, complete all as specified and directed. |
| 89 | M&L for 40mm bore GI tubing, light grade with all fittings and fixed to wall with MS clamps of suitable size or laid in floor/ trenches, complete all as specified and directed. |
| 90 | S&F in replacement fan capacitor, 2.5/3.15 MFD, complete all as specified and directed. |
| 91 | S&F of digital ding dong door bell, complete all as specified and directed. |
| 92 | Supply only of rigid non-metallic PVC casing & caping exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc, complete all as specified and directed. |
| 93 | Supply, installation, testing and commissioning of factory made LT control panel board of adequate size totally enclosed front opening type, cubical, floor mounted and indoor type, made out of 2mm thick MS sheet with base frame of angle iron of size 40x40x4mm thick provided with copper bus bar - 04 Nos with colour coated sleeves of capacity 1.5 times of incommer and internal wiring with PVC insulated copper conductor cable of adequate size for making connections to various eqpts/ accessories including powder caoated painting (internal & externally) complete over a coat of red oxide primer, CPRI approved and including PCC 1:2:4 type B-1 foundations, complete all as specified with comprising of following accessories :- (a) Fixing only electric meters with complete - 08 Nos properly isolated from panel body by means of providing backelite sheet not less than 3mm thick as base plate cable connections (b) S&F MCCB 160 Amps, TPN, four pole, 16 KA, 415 Volts - 01 No. (c) S&F MCB 40 to 63 Amps, TPN, 10 KA, 415 Volt - 08 Nos (d) S&F RYB indicator (set of three) - 01 Set(e) S&F MCB SPN 32 Amp, 10 KA - Qty required at site.Note :- Old existing serviceable electric meters will be disconnet and deposit to MES store yard and refixing the same after completing of work. |
| 94 | S&F in repair rigid non - metalic PVC casing caping of 25/12mm inclusive of all elbow, tees,etc complete all as per the direction of Engr-in-Charge. |