| 1 | S&F in replacement sheet metal enclosures 240 voltwith suitable rated bus bar for double doorIP-43 DB\"s suitable for one MCB SPN as incoming and 6 MCB SP as out going SPN 8 way completeincl dismentaling of unservceable DB complete all as specified and directed. |
| 2 | S&F in replacement sheet metal enclosures 240 voltwith suitable rated bus bar for double doorIP-43 DB\"s suitable for one MCB SPN as incoming and 10 MCB SP as out going SPN 12 way completeincl dismentaling of unservceable DB complete all as specified and directed. |
| 3 | S&F replacementsheet metal enclosures 415 voltTPN 4 way with 200 Amp rated bus bar, double door IP-43 DB\"s suitable forone No 63 to 100 Amp 10 KA TPN MCCBas incoming complete incl dismentaling of unservceable DB complete all as specified and directed. |
| 4 | S&F in replacement 240V,10KA , MCBSingle pole\"B\" series and current carrying capacity6-32 Amps ISI marked incl dismantaling old unserviceable MCB SPcomplete all as specified and directed. |
| 5 | S&F in replacement MCBSingle pole & neutral \"C\" series upto 63. Amps ISI marked incl dismantaling old unserviceable MCB SPN complete all as specified and directed. |
| 6 | S&F in replacementMCB TPN C Curve100 Amp,415 VMake incl disntaling of old unserviceable TPN MCBcomplete all as specified and directed. |
| 7 | S&F in replacementMCB TPN C Curve63 Amps 415V Make incl disntaling of old unserviceable TPN MCBcomplete all as specified and directed. |
| 8 | S&F in replacementMCB TP C Curve63 Amps 415 V Make incldismantaling of old unserviceable TP MCB complete all as specified and directed. |
| 9 | M&L in repairs sub main wiring withPVCinsulated and unsheathed 4x 6.0 Sq mm single core multistrandred copper conductor cable(FRLS) passing through inand including PVC conduit (25MM) surface onwalls with all required accesries of conduitISI markedand conduit accessaries fixed on surface of wall, ceiling etc, making good the distrurbed surface,incl 6 Sq mm single core copper conductor cable PVC insulated and unsheathed as earth wire.Note :- fourruns of cable 6 Sqmm (FRLS) and One run of 6 Sqmm copper conductor(FRLS) along with conduitshall be measured as one unit length including taking down old UNSV submain wiring complete all as directed |
| 10 | M & L in replacement Earthing complete with galvanised steel earth plate electrode 60 x x60cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) wih top edge of the plate not less than 1.5 metres below normal/hard/dense ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in elevtrical plate No. 3 connected to earthing test point complete all as specified or indicated including testing on completion . Note : Rates are deemed to be included for necessaryearth work , earth pit with RCC cover of size300X300 x25 mm etc complete all as specified and directed. |
| 11 | M&L in repairs sub main wiring withPVCinsulated and unsheathed 2x 4 Sq mm single core multistrandred copper conductor cable(FRLS) passing through inand including PVC conduit (25 MM) surface on walls with all required accesries of conduitISI markedand conduit accessaries fixed on surface of wall, ceiling etc, making good the distrurbed surface,incl 4 Sq mm single core copper conductor cable PVC insulated and unsheathed as earth wire. Note :- Two runs of cable 4 Sqmm (FRLS) and One run of 4 Sqmm copper conductor(FRLS) along with conduitshall be measured as one unit length including taking down old UNSV submain wiring complete all as specified and directed |
| 12 | M&L in repairs sub main wiring withPVCinsulated and unsheathed 2x 6 Sq mm single core multistrandred copper conductor cable(FRLS) passing through inand including PVC conduit (25 MM) surface on walls with all required accesries of conduitISI markedand conduit accessaries fixed on surface of wall, ceiling etc, making good the distrurbed surface,incl 6 Sq mm single core copper conductor cable PVC insulated and unsheathed as earth wire. Note :- Two runs of cable 6 Sqmm (FRLS) and One run of 6 Sqmm copper conductor(FRLS) along with conduitshall be measured as one unit length including taking down old UNSV submain wiring complete all as specified and directed |
| 13 | M&L in repairs sub main wiring withPVCinsulated and unsheathed 4x 10 Sq mm single core multistrandred copper conductor cable(FRLS) passing through inand including PVC conduit (25 MM) surface on walls with all required accesries of conduitISI markedand conduit accessaries fixed on surface of wall, ceiling etc, making good the distrurbed surface,incl 4 Sq mm single core copper conductor cable PVC insulated and unsheathed as earth wire. Note :- four runs of cable 10 Sqmm (FRLS) and One run of 10 Sqmm copper conductor(FRLS) along with conduitshall be measured as one unit length including taking down old UNSV submain wiring complete all as specified and directed |
| 14 | S&F Vertical Distribution Board, double Door, suitable for and including \"A\" Frame FP MCCB 100A made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating and IP 43 & IK 09 protection, TPN 4 way, 415 volts with bus bar rating 300 Amps, dust and vermin proof, suitable for incorporation of MCB’s and MCCB etc and making all necessary connections, duly flush of wall surface, complete all as specified and directed. Note: Rate are deemed to be included for 100 Amps MCCB in the quoted rate |
| 15 | M&L for sub main wiring with 2 run of 4 Sqmm FRLS, PVC insulated, unsheathed and stranded copper conductor cable with and incl 4 Sqmm (nominal area) FRLS, PVC insulated, unsheathed and stranded copper conductor cable as earth wire connected with thimble from main DB to sub main DB, drawn in to separate concealed medium grade, ISI marked, non metallic PVC conduit 25 mm dia size incl all conduit accessories & fittings / junction boxes / inspection covers etc, with and incl cutting chasing and making good of disturbed surface of wall / floor/ ceiling etc as original by brick work, plastering, white washing, OBD etc as required, complete all as specified and directed.Note:- Tworun of 4 Sq.mm. and one run of 4 Sq.mm (earth wire) cableincuding one run of conduit pipe will be measured as one length including making good the disturbed surfaces. |
| 16 | S&F in replacement Single pole and neutral enclosure 240 V with a two pin and earth plug and socket complete With One single Pole MCB of 20 Amp complete all as specified and directed. |
| 17 | M&L for Carrying out Load Balancing in Certain Buildings(Under AOR of GE(A) No.1) Including Minor Items Such as Insulation Tape, Copper/Aluminium Lux, Copper cable (1.5 to 6.0 sqmm) upto 1 mtr. , and Required T&P at sites Such as Clamp meter, hammer Drill, Screw,Nut, Bolts, Screw Gitti ,Screw Driver, plier etc complete all as specified and directed. |
| 18 | S&F in replacement PVC insulated armoured,heavy duty electric cable with Aluminium Conductor, 1100 Volts Grade, Cross Sectional Area 10 Sqmm 2 Core complete all as specified and directed.. |
| 19 | NOTE:-(i)-The contract sum shall be arrived at after duducting amount of schedule of \"Credit\" from the Total quoted amount |