| 1 | Supply, Install, Commissioning & Testing of Advance Encapsulated Compound based CPRI type-tested Maintenance Free, Pipe-in- Pipe Technology upgraded (Zinc & Alloy Coated), ZINC COATED (80-100) Microns with pure Zinc (99.9%) & ALLOY COATING (150- 200) microns. Earthing System confirming IS 3043.The outer and inner pipe should be 76.2 mm & 41.9 mm dia, 3.0 mtrs Length, Zinc coated with additional Special Alloy coating 300 mm on the topside for additional protection of the Terminal. The annular space between the pipes being filled up with compact filled (Crystalline Conductive Compound). The compact filled mixture which is machine pressed in the pipes should disintegrate or collapse when outer pipe corrodes. The inner pipe should be extended with terminals for connectivity. The job includes digging the pits and refilling the same with 2 x 25 Kgs bags of BARON Electrodite Back Fill Earth Enhancing Carbon Based Conductive Concrete compound. The Back Fill Compound should be Electronically Conductive with Noncorrosive Properties & Environmentally Neutral Material. Electrodite Back Fill Compound shall be suitable to be installed in either slurry or dry form and shall not be mixed with any soil/cement etc. while pouring in the bore hole so that it improves conductivity of the earth electrode and ground contact area with & incl FRP Chamber & Cover complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. |
| 2 | The Back-fill material/compound shall have following characteristics :a) Resistivity 0.20 Ohm-meters as per Clause 5.4.1 of IEC 62561-7:2018b) Tested as per IEC : 62561-7 and the test certificates (Corrosion Test, Leach Test, Sulphur Test & Resistivity Test )shall be submitted to the Engr-In-Charge.c) Shall not depend on the continuous presence of water / moisture / salt to maintain its conductivity.d) Shall not decompose or leach out with time.e) Shall solidify when mixed with water and set like concrete.f) Shall not contain hazardous chemicals and necessary Test certificate from reputed accredited laboratories shall be submitted to the Engr-In-Charge.g) Shall not be affected by drought and shall be stable between -10˚ to +50˚ C temperature.h) Shall be suitable for any kind of soil.j) Shall be supplied in sealed, moisture proof bags. These bags shall be marked with Manufacturer’s Name or Trade Name & Quantity. |
| 3 | The following test certificates shall be submitted to the Engr-In-Charge by the Contr prior to supply of ELECTRODITECarbon based Back fill compound from an independent laboratory (NABL Accredited Laboratory) along with Routine Test Report :a) Corrosion Test Certificate as per IEC : 62561-7 b) Leach Test Certificate as per IEC : 62561-7c) Sulphur Test Certificate as per IEC : 62561-7d) Resistivity Test Certificate as per IEC : 62561-7Model - ASEEL-39 3.0 m length (ZINC & ALLOY COATED) of Make ELMECH or techno-commercially equivalent of ERICO/CAPE ELECTRIC. |
| 4 | IMPORTANT NOTES :1) The complete work of the Earthing System is to be got done from the OEM or their authorized sister concern/ channel partner only.2) Any items missed out in the technical specification, but technically required for efficient working of the system is deemed to be included in the unit quote rates.3) The contractor/firm is required to visit the site prior to quoting of the subject items/ work so as to ascertain the actual ground requirements. Any further query at a later date shall not be entertained & responsibility of the same shall rest on the contractor/ firm.4) Comparative analysis in respect of the items wherever techno-commercially equivalent w.r.t the given Cat/Part/Model ref concerned is to be submitted to the Engr-In-Charge & GE for approval.5) The cost of making good the disturbed surfaces is deemed to be included in the unit quoted rate of relevant items.6) Purchase Vouchers & Manufacturers test certificates to be submitted in Original to the Engr-In-Charge.7) Design/Drawing/BOM/Technical Specifications of the complete Earthing System showing the layout including dimensions is to be obtained from OEM strictly keeping in view the actual ground requirements & the same is to be got approved from Engr-In-Charge & GE before placing final order to the OEM.8) The contractor should submit a detailed Report of Test results from OEM after completion of work and same is to be certified from Engr-In-Charge & GE. If the test results are not satisfactory or not within the permissible limits of relevant National/International Standards then the job is to be redone without any extra cost to the Dept with & incl any numbers of additional 25 Kg Bags of BFC till the results are satisfactory i.e. less than 1.0 Ohm. |
| 5 | 9) Repair/ Servicing / Preventive & Breakdown maintenance of the complete Earthing system is to be got donefrom the OEM/ Sister Concern/ Channel partner only by the contractorfor the entire defect liability period i.e two years from the certified date of completion & the cost of the same is deemed to be included in the unit quote rates.10) Testing at an interval of 6 months of the entire Earthing system is to be got done from the OEM/ Sister Concern/ Channel Partner only by the contractor & report submitted accordingly to the Engr-In-Charge for the entire defect liability period & and the cost of the same is deemed to be included in the unit quote rates.11) Cost of FRP Chamber & Cover all as per OEM recommendations is deemed to be included in the unit quote rates.12) Earthing Electrode and Copper Strip 20 x 3 mm shall be welded using Exothermic Welding for interconnecting the Earth Electrodes whereever required or as directed (if any) and from Earth to Grid Point up to 7.5 m along with 40 mm dia GI light grade protection pipe & the cost of the same is deemed to be included in the unit quoted rates. 13) All the joints except Test Point shall be welded / brazed properly and the Copper Earth Strip whenever laid / fixed on the wall, floor etc. shall be fixed / fitted on DMC/FRP Insulators not more than 600 mm apart & the cost of the same is deemed to be included in the unit quoted rates. 14) The Contractor shall give Guarantee for maintaining Earth Resistance value of less than 1.0 Ohm for a period of 05 years from the Certified Date of Completion and is required to deposit a Security Deposit of Rs 2000/- for each Earthing in this regard. |
| 6 | M&L for earthing complete with Copper earth plate electrode 600 x 600 x 3.15 mm thick buried directly in ground (in vertical position) earth pit not less than 2.25 mtr below normal ground level with the top edge of the earth plate not less than 1.5 mtr (B.G.L.) and connected to Copper earth strip 20 x 3 mm by means of bolts, nuts, check nuts, and washers of galvanized iron including PCC Chamber & Cover with suitable handle, including necessary excavation and earth work in any type of soil, 20 mm dia med grade galvanized steel tube for watering with one end fixed with suitable funnel and wire mesh, 40 mm bore medium grade galvanized steel tubing for drawing earth lead GI strip protection & common salt, charcoal in alternate layers etc. complete all as shown in EP No 3 of SI Part 1 and testing on completion incl taking down old unsv earthing assy complete all as specified and as directed by the Engr-in-Charge. |
| 7 | M&L for earthing complete with Galvanised steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (in vertical position) earth pit not less than 2.25 mtr below normal ground level with the top edge of the earth plate not less than 1.5 mtr (B.G.L.) and connected to GI earth strip 32 x 6 mm by means of bolts, nuts, check nuts, and washers of galvanized iron including PCC Chamber & Cover with suitable handle, including necessary excavation and earth work in any type of soil, 20 mm dia med grade galvanized steel tube for watering with one end fixed with suitable funnel and wire mesh, 40 mm bore medium grade galvanized steel tubing for drawing earth lead GI strip protection & common salt, charcoal in alternate layers etc. complete all as shown in EP No 3 of SI Part 1 and testing on completion incl taking down old unsv earthing assy complete all as specified and as directed by the Engr-in-Charge. |
| 8 | M&L for earthing complete with Galvanised steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (in vertical position) earth pit not less than 2.25 mtr below normal ground level with the top edge of the earth plate not less than 1.5 mtr (B.G.L.) and connected to GI earth strip 25 x 4 mm by means of bolts, nuts, check nuts, and washers of galvanized iron including PCC Chamber & Cover with suitable handle, including necessary excavation and earth work in any type of soil, 20 mm dia med grade galvanized steel tube for watering with one end fixed with suitable funnel and wire mesh, 40 mm bore medium grade galvanized steel tubing for drawing earth lead GI strip protection & common salt, charcoal in alternate layers etc. complete all as shown in EP No 3 of SI Part 1 and testing on completion incl taking down old unsv earthing assy complete all as specified and as directed by the Engr-in-Charge.IMPORTANT NOTES FOR ITEM NOS 2 to 4 : 1) On completion of the complete work/job the Contr is to perform earth resistance tests for each earthing job in the presence of the Engr-In-Charge or his rep & submit test certificates duly signed & certified. If the test results are not satisfactory or not within the permissible limits of 1.0 Ohm then the job is to be redone without any extra cost to the Dept till the results are satisfactory.2) Cost of GI/Copper Earth Strip and GI Protection Pipe upto 7.5 mtr length & welding/brazing work is deemed to be included in the unit quoted rates.3) Cost of Wire Mesh, Funnel, Earthwork, PCC Chamber with Cover, Test Point etc.is deemed to be included in the unit quoted rates. |
| 9 | S&F Aluminium Strip 25 x 3 mm with DMC / FRP insulators & fixing screws of appropriate size/type etc. for Roof / Down Conductors / connection to Earth pit / Equipment etc. including necessary brazing all the joints incl taking down old unsv / damaged one complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. |
| 10 | S&F Copper Strip 20 x 3 mm along with DMC / FRP insulators & fixing screws of appropriate size/type etc. for connection to Earth pit / Equipment etc. including necessary brazing all the joints incl taking down old unsv / damaged one complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. |
| 11 | S&F GI strip 32 x 6 mm with DMC / FRP insulators & fixing screws of appropriate size/type etc. for connection to Earth pit / Equipment etc. including necessary brazing all the joints incl taking down old unsv / damaged one complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. |
| 12 | S&F GI strip 25 x 4 mm with DMC / FRP insulators & fixing screws of appropriate size/type etc. for connection to Earth pit / Equipment etc. including necessary brazing all the joints incl taking down old unsv / damaged one complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge.IMPORTANT NOTES FOR ITEM NOS 5 TO 8 : 1) DMC / FRP insulators are to be fixed/placed at an interval/spacing of 1.2 Mtrs in case of Roof Conductors & at an interval/spacing of 1.0 Mtr in case of Down Conductors. 2) In case of Roof Conductors, DMC / FRP insulators are to be fixed on PCC Blocks of size 150 x 150 x 150 mm. 3) Cost of DMC / FRP insulators is deemed to be included in the unit quoted rates & cost of PCC Blocks shall be measured & paid separately under relevant items. |
| 13 | S&F Air Termination, Single pointed, Aluminium rod 12 mm dia and 300 mm long incl taking down old unsv / damaged one complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. |
| 14 | S&F Air Termination, Single pointed, Copper rod 12 mm dia and 300 mm long incl taking down old unsv / damaged one complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. |
| 15 | S&F Earthing / Grid point made out of 4mm thick copper bus-bar 250 mm length duly fixed on porcelain insulators housed in suitable sized powder coated MS box and connecting up existing/new earthing together to achieve the grid earthings barest minimum ohmic value incl taking down old unsv / damaged one complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. |
| 16 | S&F Earthing / Grid Indicator made out of 3 mm thick MS sheet of size 300 x 200 mm duly welded with 500 mm long 25 x 25 x 6 mm angle iron duly fixed near to the grid point with cement grouting including writing complete Earthing details such as Earth resistance, Connected to, Date of Checking etc. incl taking down old unsv / damaged one complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. |
| 17 | S&F Test Point Terminal Block made of Gun Metal or Phosphorus Bronze size 75 x 75 x 25 mm, drilled and screwed and including 3 Nos 8 mm dia 25 mm long hex head screws incl taking down old unsv / damaged one complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. |
| 18 | S&F Bib Tap, Cast Copper Alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule of size 15 mm dia incl taking down old unsv / damaged one complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. |
| 19 | M&L for Pre-fabricated Heavy Duty RCC Earth Pit Chamber of size 45 cm X 45 cm X 45 cm with 50 mm thick RCC Cover with suitable lifting handle including necessary excavation, returning/filling & removal as required at siteincl taking down old unsv / damaged one complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. |
| 20 | Excavation in trenches by any means n.exc 1.5m wide and n.exc 1.5m in depth for laying of pipe and getting out in hard dense soil complete. |
| 21 | Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm thick. |
| 22 | Removing of excavated material n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point. |
| 23 | M&L for checking of Earth Resistance of the existing Earthings in Technical/Domestic area etc. once in three months and recording the Test Results in the Earth Resistance Test Register including obtaining Signature of User Rep, MES Rep & Contr Rep in the subject Register complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge.IMPORTANT NOTE : 1) The Earthing Resistances shall be tested in the presence of User Rep & MES Rep. 2) One time testing including entering the same in the register will be considered as one job. 3) First testing shall be carried out within 30 days from the date of commencement of the Contract. |
| 24 | S&F DMC / FRP insulators of size minimum 50 mm to facilitate fixing of the earth strips on the wall / roof duly screwed on the PCC Blocks (only for roof) and making holes in the earth strips by drilling and fixing the earth strip rigidly with the insulators with GI bolts, nuts, washers etc. incl taking down old unsv / damaged one complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge.IMPORTANT NOTE : 1) DMC / FRP insulators are to be fixed/placed at an interval/spacing of 1.2 Mtrs in case of Roof Conductors & at an interval/spacing of 1.0 Mtr in case of Down Conductors. 2) In case of Roof Conductors, DMC / FRP insulators are to be fixed on PCC Blocks of size 150 x 150 x 150 mm. 3) Cost of PCC Blocks shall be measured & paid separately under relevant items. |
| 25 | M&Lfor GI pipe light grade 40 mm dia with all running fittings (ISI Marked), laid in trenches, under road or fixing on wall/pole/crossing drain/nallah etc. for protection of earth lead etc. incl taking down old unsv / damaged one complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. Make : TATA/JINDAL/PRAKASH.IMPORTANT NOTE : Wherever GI Protection pipes are to be placed/fitted above earths surface, cost of necessary clamping/fixing arrangements to the entire satisfaction of Engr-In-Charge is deemed to be included in the unit quoted rates. |
| 26 | M&L for PCC (1:2:4) Type B-1 (using 20mm graded stone aggregate) for making PCC Blocks of size 150 x 150 x 150 mmm to facilitate mounting of Roof Conductors at every 1.2 Mtr spacing duly finishing the surfaces even & smooth without using extra cement incl necessary formwork complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. |