| 1 | Excavation in trenches n.exc 1.5 m wide and n. exc 1.5 m in depth and getting outin soft/ loose soil for removing/ laying of cables complete all as specified and as directed by Engineer-in-charge. |
| 2 | Returning, filling in including spreading, leveling, watering and well ramming in layers n.exc 25 cm with soil complete all as specified and as directed by the Engineer-in- Charge. |
| 3 | Removing excavated material to a distance n.exc 50 m and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and as directed by Engineer-in-Charge. |
| 4 | Material & Labour sand filling under floors or in foundation including watering & consolidation for cable cushioning all as specified and directed |
| 5 | Supply and laying DWC HDPE pipes of pressure rating 6 Kg/Cm sq of size 32 mm laid in trenches complete all as specified and directed. |
| 6 | Supply and laying DWC HDPE pipes of pressure rating 6 Kg/Cm sq of size 40 mm laid in trenches complete all as specified and directed. |
| 7 | Supplying and laying unreinforced precast concrete cable cover class LV type 1, flat, size 250 x 150 x 40 mm complete all as specified and directed by the Engineer - in - charge. |
| 8 | Supply and fixing, install, test and commissioning of LT Feeder pillar box indoor type totally enclosed with only front opening hinged doors with canopysloped top projected and raised platform of suitable sizes weather dust vermin proof IP-54 protection CPRI approved, factory fabricated, cubical panelfree standing type, made out of 2.00 mm thick CRCA sheet with locking arragement, factory made powder coatedas approved colour, copper bus bar suitable for 3 phase 4 wire LT, AC, 50Hz, 433 volts, 300Amps rating capacity RYBN insulated with sleeved insulation complete with multifunctional meter LED type by showing Amps, volts, frequency etc along with suitable size of CT on outgoing, indicating lampRYB , complete internal wiring with suitable size of PVC insulated copper conductor cable, including cable glands and lugs for incoming and out going cables as per required sizes,PCC platform made out of 1:2:4 type B1 and pedestal of 30 cm height from GL with suitable nut, bolts, washers etc, all as specified and directed for suitable to accomodate the following items including supply and fix following items and all as specified and directed by dismantling exisiting unserviceable LT panel complete with Make of LT Panel-L&T/ Legrand/ HPL.Loc: Panel behind bldg No 118 at MO (MB) Ghatkopar. |
| 9 | Incoming:MCCB 4 pole 200 Amp with breaking capacity 25 KA adjustable type with exended terminals- 01 Nos |
| 10 | Outgoing(a)MCCB 4 pole 100 Amps with breaking capacity 16 KA adjustable type with extended terminals-04 Nos |
| 11 | (b)MCCB 4 pole 63 Amps with breaking capacity 16 KA adjustable type with extended terminals-03 No\"s |
| 12 | (c)MCB TPN 40 Amps,breaking capacity 16 KA- 02 Nos |
| 13 | (d) MCB SPN 32 Amps,breaking capacity 10 KA- 03 Nos |
| 14 | (e) Current Transformers- 03 Nos |
| 15 | (f) Multi functional Meter- 01 |
| 16 | (g)LED RYB indicator lamps- 01/Set |
| 17 | Note:- The panel must have separate Bus bar chamber, cable chamber and proper spacingmust be maintained between each chamber ofpanel as per IS . |
| 18 | Supply and fixing, install, test and commissioning of LT Feeder pillar box outdoor type totally enclosed with front and rear opening hinged doors with canopysloped top projected and raised platform of suitable sizes weather dust vermin proof made out of 3.15 mm thick CRCA sheet, factory made powder coatedas approved colour, aluminum bus bar suitable for 3 phase 4 wire LT, AC, 50Hz, 433 volts, 160Amps rating capacity RYBN insulated with sleeved insulation complete with multifunctional meter LED type by showing Amps, volts, frequency etc along with suitable size of CT on outgoing, indicating lampRYB , complete internal wiring with suitable size of PVC insulated copper conductor cable, including cable glands and lugs for incoming and out going cables as per required sizes,PCC platform made out of 1:2:4 type B1 and pedestal of 30 cm height from GL with suitable nut, bolts, washers etc., all as specified and directed for suitable to accomodate the following items including supply and fix following items and all as specified and directed by dismantling exisiting unserviceable LT panel complete with LT panel made by CPRI approved manufacturer confiring to IS:-8623-1993.Location:Panel at NSV near Bldg No NS-111 at MO (MB) Ghatkopar |
| 19 | Incoming (a) MCCB 4 pole 400 Amps with breaking capacity 35KA adjustable type with extended terminals-01 No |
| 20 | Outgoings(b)MCCB3 pole 100 Amps with breaking capacity 35KA adjustable type with extended terminals-05 Nos |
| 21 | (c)MCCB3 pole 63 Amps with breaking capacity 35KA adjustable type with extended terminals-03 Nos |
| 22 | (d)MCBTPN 40 Amps with breaking capacity 10KA- 02 Nos |
| 23 | (e) MCB SPN 40 Amps with breaking capacity 16KA adjustable type with extended terminals-02 Nos |
| 24 | (f) Digital Ammeter with C.T- 03 Nos |
| 25 | (g)Digital Volt Meter- 01 |
| 26 | (h)(f) LED RYB indiacator lamps-01/Set |
| 27 | (j)Single phase preventor-01 Set |
| 28 | Note:-The panel must have separate Bus bar chamber, cable chamber and proper spacingmust be maintained between each chamber ofpanel as per IS . |
| 29 | Supply and laying in repairs cable LT XLPE insulated and screened PVC bedded, galvanised steel strip armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade complete all as specified and directed by Engineer in charge for the size10 Sqmm 4 Core including taking up existing u/s LT cable from trenches, poles, walls & floor etc. Complete all as specified and directed.Note: Exacavation and earth work if required shall be measured separately. |
| 30 | All as per item no 10 above but 16 Sqmm 4 Core. |
| 31 | All as per item no 10 above but 25 Sqmm 3.5 Core. |
| 32 | All as per item no 10 above but 35 Sqmm 3.5 Core. |
| 33 | All as per item no 10 above but 95 Sqmm 3.5 Core. |
| 34 | All as per item no 10 above but 120 Sqmm 3.5 Core. |
| 35 | All as per item no 10 above but 150 Sqmm 3.5 Core. |
| 36 | All as per item no 10 above but 185 Sqmm 3.5 Core. |
| 37 | All as per item no 10 above but 240 Sqmm 3.5 Core. |
| 38 | Dismantling of existing RCC & steel tubular poles with bracket & light and in lieu S&F 7 metre long hot dipped galvanised octagonal poles with top A/F 70mm bottom A/F 130 mm, made out of 3mm thick HT sheet alongwith base plate of size 220*220*12mm, including 1500mm long single arm bracket made out of 48mm dia, GI pipe, M20 in PCD 205mm, 700mm long and projected 100mm, \"J\" type EN8 grade set of 4 Nos foundation bolts alongwith templates, also including provision of the followings :- (a)MCB,SP,6A,230V, B series, 10KA mounted on and including 3mm thick plastic laminated sheet-01 No.(b)4 way connector, bolt type having locking arrangement, weather proof and water proof control space : 01 No.Notes:(a) The rate quoted shall also be deemed to include the cost for provision of 50mm bore PVC pipe from cable trench to centre of the pole concrete of the pole concrete.(c) The earth work, RCC foundation reinforcement and form work will be measured and paid separately.(d) .quoted rate shall also be deemed to include for fixing of old light fitting retrived from dismantling.Make : BAJAJ Model BOP-7030 or its equivalent in Crompton/ Philips / Wipro as approved by the GE. |
| 39 | M&L for mild steel TMT bars 6 mm to 8mm dia cut to length, bent to shape required, stirrups, spaces and binders and binding with mild steel wire (annealed) not less than 0.9 mm dia or securing with clips, complete all as specified and directed. |
| 40 | M &L for TMT steel bars 10 mm dia and over in reinforcement cut to length,bent to shape required, including cracking bending spirally forhooping for coloumns, hooking ends and binding with and including mild steel wire(annealed) not less than 0.9 mm di or ecuring with clips etc, complete all as specified and directed |
| 41 | M&L for RCC type B-1, 1:2:4 (nominal mix) using 20 mm graded stone aggregate as in footing, columns, post, pillars, piers, wall of culverts, suspended slabs, edges and struts etc complete all as specified and directed. |
| 42 | M&L for form work to sides of concrete footings, columns, posts, pillars, piers, edges and struts of rectangular or triangular shape for rough finished flat concretesurface complete all as specified and directed. |
| 43 | M & L in repairs forPVC copper cable 2.5 sqmm 3 core copper conductor 1100 Volt grade multi core multi stranded PVC insulated unsheateddrawn through and including PVC conduit and accessories fixing on poles/ wall with clamps, nuts bolts etc from FRP box to street light fitting complete all as specified and direcetd |
| 44 | M & L for earthing complete with Galvanised steelearth plate electrode 60 cm x 60 cm x 6 cm thick buried directly in ground vertically at a depth not less than 2.25 m belownormal ground level with top level of earth plate at depth not less than 1.5 m below normal ground level surrounded form all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connection by using GI strip32 mm x 6 mm by means of bolts, nuts, check nuts and washers of galvanized iron upto test pointand protected by GI pipe light grade 40 mm bore up to 7.5 Mtr connected to a main switch board or main control board and GI pipe light grade 20 mm bore for watering and including funnel, wire mesh, 80 mm thick pre-cast RCC 1:2:4, type B-1 cover reinforced with hard drawn steel wire fabric weighing not less than 4 Kg/Sqm in lieu of CI cover, PCC 1:3:6 type C2 pit / chamber including all necessary excavation and earth work, disposal of surplus soil to a distance not exceeding 50 m all as specified and as shown in Electrical Plate No 3 of MES Schedule Part – I of 2009.Note: Test of earthing results submitted to GE specified and directed by Engr-in-Charge. |
| 45 | Supply and fixing in repairs maintenance lithium battery 11.1/33Ah (suitable for 32 watt solar lights) BMS circuit and other necessary wiresconnectors suitable for 32 watt integrated solar lights complete all as specified and directed. Make: Axxon or equivalent. |
| 46 | Supply and fixing in repairs maintenance lithium battery 11.1/19.8 Ah (suitable for 12 watt solar lights) BMS circuit and other necessary wiresconnectors suitable for 12 watt integrated solar lights complete all as specified and directed. Make: Axxon or equivalent. |
| 47 | Supply and fixingin repairs highly efficient high power multi LED flood light fitting 100 watts with pressure die castaluminium housing reflector and enclosed with toughened glass IP66 complete prewired and connecting with 0.5 sqmm 3 core flexible wire including fixing arrangement on wall etc complete including dismantling of existing unserviceable flood light fittings complete all as specified and directed by Engineer in Charge. |
| 48 | Supply and fixin repairs highly efficient high power 45 Watt LED street light fitting with pressure die cast aluminium housing reflector and enclosed with heat resistant toughened glass IP66 protection AC 240 Volts 50 HZ refractive lens with suitable electronic drive PF > 0.9 complete including taking exiting unserviceable street light fitting. |
| 49 | Supply and fixin repairs highly efficient high power 60 Watt LED street light fitting with pressure die cast aluminium housing reflector and enclosed with heat resistant toughened glass IP66 protection AC 240 Volts 50 HZ refractive lens with suitable electronic drive PF > 0.9 complete including taking exiting unserviceable street light fitting. |
| 50 | Supply and fixin repairs highly efficient high power 90 Watt LED street light fitting with pressure die cast aluminium housing reflector and enclosed with heat resistant toughened glass IP66 protection AC 240 Volts 50 HZ refractive lens with suitable electronic drive PF > 0.9 complete including taking exiting unserviceable street light fitting. |
| 51 | Supply and fixing in repairs LED post top lanterns fitting made in cast aluminium spigot housing with decorative clear acrylic diffuser and IP66 protection upto 20watt, warm white complete all as specified and directed. |
| 52 | Supply and fixing in repairs LED garden lights fitting made in cast aluminium spigot housing with decorative clear acrylic diffuser and IP66 protection upto 20watt, warm white complete all as specified and directed. |
| 53 | Supply and fix in repairs ofFRP looping box of size 250x200x100 mm with connector, MCB 6 Amps, Din Rail, GI clamps made out of GI flat of size 25mm X 3 mm channelincluding making connections complete all as specified and directed. |
| 54 | Supply and fix in repairs ofFRP looping box of size 200x140x95 mm with connector, MCB 6 Amps, Din Rail, GI clamps made out of GI flat of size 25mm X 3 mm channelincluding making connections complete all as specified and directed. |
| 55 | M&L for preparation of old painted surfaces of Steel Tubular pole 7/9 mtr long by scarping old paint and applying two coats of Aluminium paint including numbering of pole with black oil paint and painting the base of the pole in alternate black and yellow stripes each 30 Cm apart up to 1.5 mtr height including marking of MES No. with black paint on the pole all complete all as specified and directed. |
| 56 | M&L for straight through joint (epoxy) suitable for 3.5 core or 4 core up to 95 Sqmm size underground cable complete all as specified and directed. |
| 57 | M&L for straight through joint (epoxy) suitable for 3.5 core or 4 core 95 to 240 Sqmm size underground cable complete all as specified and directed. |
| 58 | M&L for finding faults of LT UG cable XLPE of any size and any length by using computerised / primary current injection method / any other method as directed by the GE and locating fault, cutting and removing the faulty portion of the cable and jointing with suitable cable joint and testing after jointing all as required and directed.Note:Joints shall be paid separately. |
| 59 | M&L for secure/hanging of electrical XLPE/PVC cable/wires of any size on walls/ceiling with clamps, hooks, nuts , bolts and other accessories for electrical hyigen complete all as specified and directed. |
| 60 | Materials and labour for servicing & spray painting factory made powder coatedas approved colour and servicing of LT panel with burnts wiring, cleaning of panel , lugs, glands of any size, and others connected accessories complete all as specified and directed. |
| 61 | Material and labour for street/security pole numbering complete all as specified and directed. |
| 62 | S&F in repairs LED bulb retrofit 15 Watt E27 base with flat surfase of reflection light should be fixed with silicon gel on both side to protect from water complete all as specified and directed. MakeRenesola Cat Part No . RA67013S0230 13/15 W, 3000K E27 or equivalent. |
| 63 | Suppy and fixing in repairs of GI cable tray of size 300 mm with connected accessories complete all as specified and directed |
| 64 | Suppy and fixing in repairs of GI cable tray of size 150 mm with connected accessories complete all as specified and directed |
| 65 | Suppy and fixing in repairs of GI cable tray of size 100 mm with connected accessories complete all as specified and directed |
| 66 | Supply and fix in repairs MCCB 4 pole,630 Amp 415 Volt adjustable type with breaking capacity 50 KA from panel boards etc complete all as specified and directed. |
| 67 | Supply and fix in repairs MCCB 4 pole,400 Amp 415 Volt adjustable type with breaking capacity 36 KA from panel boards etc complete all as specified and directed. |
| 68 | Supply and fix in repairs MCCB 4 pole,250 Amp 415 Volt adjustable type with breaking capacity 36 KA from panel boards etc complete all as specified and directed. |
| 69 | S&F in repairs LED bulb retrofit 12/15 Watt E22 base complete all as specified and directed. |
| 70 | Supply and fix in repairs MCCB 3 pole,25 to 125 Amp 415 Volt adjustable type with breaking capacity 16 KA from panel boards etc complete all as specified and directed. |
| 71 | Supply and fix in repairs GI strip 32mm x 6mm buried in ground complete all as specified and directed. |
| 72 | Supply and fix in repairs GI strip 25mm x 4mm buried in ground complete all as specified and directed. |
| 73 | M&L for the earthing test of through complete all as specified and directed by the Engineer-in-charge. |
| 74 | M&L for Plates chequaredof Fe 410 W Gde E-250 quality A channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment completeall as specified and directed |
| 75 | Supply only Aluminum lugs for cable 120 to 400 sqmm, 3.5 core complete all as specified and directed. |
| 76 | Supply only Aluminum lugs for cable 25 to 95 sqmm, 3.5 core complete all as specified and directed. |
| 77 | Supply only Aluminum lugs for cable 6 to 16 sqmm, 4 core complete all as specified and directed. |
| 78 | Supply only Aluminum glands for cable 120 to 400 sqmm, 3.5 core complete all as specified and directed. |
| 79 | Supply only Aluminum glands for cable 25 to 95 sqmm, 3.5 core complete all as specified and directed. |
| 80 | Supply only Aluminum glands for cable 6 to 16 sqmm, 4 core complete all as specified and directed. |
| 81 | Supply only Aluminum ferrules for cable 120 to 400 sqmm, 3.5 core complete all as specified and directed. |
| 82 | Supply only Aluminum ferules for cable 25 to 95 sqmm, 3.5 core complete all as specified and directed. |
| 83 | Supply only Aluminum ferules for cable 6 to 16 sqmm, 4 core complete all as specified and directed. |
| 84 | Replacing ofcable lugs, SSnut bolts after finding out all loose connection/ rusted connection for LT Panels/LT Feeder/Street lights poles all as specified and directed. |
| 85 | Supply and fix in repairs ACB 3 pole,800 Amp 415 Volt microprocessor based ET6G trip unit with breaking capacity 50 KA from panel boards etc as per existing site requirment complete all as specified and directed. Make- Schneider cat part no MVS08N3NW6L or equivalent in L & T/ legrand/Merlin Gerin |
| 86 | Supply and fix in repairs ACB 3 pole,1000 Amp 415 Volt microprocessor based ET6G trip unit with breaking capacity 50 KA from panel boards etc as per existing site requirment complete all as specified and directed. Make- Legrand cat part no 028622 or equivalent in L & T/ legrand |
| 87 | S & F in repairs 4 way connector, bolt type having locking arrangement, weather proof and water proof control space with MCB, SP, 6A, 230V, B series, 10KA mounted on and including 3mm thick plastic laminated sheet Suitable for LT feeder pillar / street light pole complete all as specified and directed. |
| 88 | Supply install, test and commissioning of Powder coated LTFeeder panel cubical out door type Channel mounted compartmentalized in construction allConfirming to IS 8623 Part 1 1993CPRI approved factory fabricatedmade out of 3 mm thick CRCA sheet & suitable size to accomodate all accessories / fittings, to accommodate incoming MCB and TPN Copper bus bars, incomer MCB and outgoing MCB, ContactorsThe TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator. The bus bar shall have copper extension links for connecting with out going MCB. The connecction between Bus Bar & MCB should be done by copper bus bar link. Thecubicle shallhaveabottomchannel & free standing frame made of angle iron of size not less than 40mm X 40mm X 6mm ut of A detachable predrilled gland plateof thickness not less than 3 mm thickpowder coated should be used at thebottom for entry of armoured cableof adequate size with glands.The above panel shall be front openable lockable /openable by key from both side.The panel shall be Dust, vermin proof and powder coated of approved thickness complete including, control wiring by 1.5 Sqmm Wireand consisting the following, including taking down of old unsv panel after disconnecting Existing cables & Reconnecting the cables to new panels and including PCC foundation, excevation, grouting boltsa) MCB DP 10 Amps- 01 Nosb) MCB SPN 10 Amps-03 Nosc) Street Light Timer Circuit With the Following - i) M L 2 Contactor 02 Nosii) Street Light Timer FM 1 Quartz - 1 NosNote - The lay out drawing of the panel shall be got approved by the contractor before panel fabrication and shall be fabricated from CPRI approved manufacture. |
| 89 | Repairs and overhauling of Air Circuit Breaker (ACB) 3 or 4 pole, 415 Volt, upto 1200 Amp with thermal magnetic release by replacement of worn out parts and cleaning the complete ACB and testing the same after repair for smooth functioning etc completeall as specified and directed. |
| 90 | S&F in repairs Air Circuit Breaker (ACB) Relay415 Volt, upto 1200 Ampwith thermal magnetic release by replacement of worn out parts and cleaning the complete ACB and testing the same after repair for smooth functioning as per site requirment etc completeall as specified and directed. |
| 91 | Deduct Credit for Demolished/ Dismantled material Rs. (-) 62,725.00 (Minus) as listed in Schedule of Credit.Note 1:- Tenderers will not quote against this item being a tentative amount to be considered to arrive at the \"Contract Sum\".Note 2:- The tenderer must keep in mind when quoting rates against items out in multiple store house having height 4 mts to 7 mts. Necessary scaffolding and saftey measures required during execution of work are including in this items. |