| 1 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr deep for foundation, laying GI pipes and UG cables etc not exc 10 sqmtr on plan, in soft/loose soil and getting out complete all as specified and directed. |
| 2 | Returning filling in with approved excavated soil including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and directed. |
| 3 | Removing excavated soils to a distance not exceeding 50 metres and depositing where directed at a level nexc. 1.5 metre above the starting point complete all as specified and directed. |
| 4 | Materials and labour for 50 mm outer dia double wall corrugated(DWC SN-8) HDPE pipe, ISI marked for enclosing cable below ground/road surface to a required depth including suitable size couplers for jointing of pipe all as per site requirement etc complete all as specified and directed. |
| 5 | Materials and labour for GI tubing of 40 mm bore light grade with all fitting fixed to wall/ceiling/pole or in trench formed by road/PCC cutting/boring as cable protection laid on floor all as specifed and directed. |
| 6 | Materials and labour for GI tubing of 50 mm bore light grade with all fitting fixed to wall/ceiling/pole or in trench formed by road/PCC cutting/boring as cable protection laid on floor all as specifed and directed. |
| 7 | Supply and laying in trenches/wall LT UG XLPE insulated ,armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 25 sq mm x 4 coreincluding taking down old unserviceable cable and making necessery connections all as specified and as directed. |
| 8 | All as item no 7 but of size 16 sqmm 4.00 core |
| 9 | All as item no 7 but of size 10 sqmm 4 core |
| 10 | Materials and labour PCC, type B1, (1:2:4), using 20mm graded crushed stone aggregated as in PCC/Road cutting /installation area and foundation of pole, coping etccomplete all as specified and as directed. |
| 11 | Materials and labour for boring holes 100mm dia upto 2mtr deep in soil under roads/PCC as directed for cable passing through pipes of required size and disposal of soil to a distance not exc. 50m. (Note: Connected items like Pipes is measured and paid seperately under relevant items). |
| 12 | Materials and labour for earthing complete with galvanized steel pipe electrode 40mm bore, medium grade, 3.5 meters length, buried directly and preferably vertically in ground with top edge not less than 1.25 meters below ground level connected with earthing lead galvanized iron strip of size 25x4 mm connected to galvanized earth pipe by means of bolts, nuts, checknuts and washer of galvanized iron including PCC (1:2:4) type B1 precast RCC cover slab with suitable handle made of 6mm round bar, including necessary excavation and earth work in any type of soil, 20mm dia medium grade galvanized steel tube for watering with one end fix with cast iron funnel and wire-mesh, with protection pipe of 32 mm dia light grade galvanized steel tubing upto 7.5 meters length for drawing earthlead including common salt, charcol , bentonite in alternate layers etc all in around of earthing pipe of 600mm dia, complete all as shown in EP number 2 of SSR Part-1 including testing on completion and including taking down old U/S earthing & testing complete all as specified and as directed. |
| 13 | Materials and labour for water proof, 3 core PVC insulated and PVC sheathed, copper conductor cable of size 1.5 sqmm, 1100 Volts grade for electrical connection of street light fittings, complete all as specified and directed. |
| 14 | Supply and fixing thermoplastic polycarbonate cable junction box havingIP 67 protection, dust proof, acid resistant, shock proof, fire retardent self extinguisher for outside installation with knockout entry for cable of size 10-25 sqmm and of size 200x140x95mm with terminals, brackets for street light pole mounting and provision of one 6A MCB SP all as specified and as directed. |
| 15 | Supply and fixing thermoplastic polycarbonate cable junction box havingIP 67 protection, dust proof, acid resistant, shock proof, fire retardent self extinguisher for outside installation with knockout entry for cable of size 10-25 sqmm and of size 295x195x95mm with terminals, brackets for street light pole mounting and provision of one 6A MCB SP all as specified and as directed. |
| 16 | Supply and fixing in repair 70 Watt street security light made up of pressure die-cast aluminium housing with high power LED as light source and lens embedded toughened glass cover including electronic driver, should have luminaire efficacy ≥ 130 lumens/watt, CRI>70, PF>0.95, CCT=5700±300, IP 66 protection with impact resistance of IK07, inbuilt protection against lightening, over voltage, short circuit and surge/spike protection upto 10kV, including connection with PVC insulated, PVC sheathed multistranded copper conductor of 1.5 sqmmX3 core completeall as specified and as directed. |
| 17 | Supply, fixing and connecting in repair vertical runway aviation LED edge lights of capacity 20 Watts lampshed injection moulded with PC material, with round shape bottom to be fixed on PCC stand, input voltage 180-265 A, 50Hz,IP-65 rating, light intensity50 CD in colour blue/red/yellow as per site requirement, with all necessary fixtures, mounting plate and connection with 1.5sqmm copper conductor cable complete all as specifiedand as directed.(Make :LOKOZO model No. REL-Z-20W-G/W or equivalent ofPhilips/ Crompton) |
| 18 | Materials and labour Street light bracket, made out of 40 mm dia GI pipe (light grade) 1.5 m long bend to shape as required and welded and fixing in position with two sets clamps grouted in wall with four wall fastners including dismantling and taking down old unserviceable bracket complete all as specified and directed. |
| 19 | Supply and fixing in repair 8 KW ,three phase automatic Street Light timer switch for automatic switching on/off street light based on lux level of nature light, consistingof sensor overload protection fuse gear, power contactor & MCB of suitable capacity, terminal blocks for cable entry & control unit enclosed in pole/Wall mountable elcosure made out of rust proof, shock proof, termite proof FR grade SMC, conforming to IP 66 with universal lock and key arrangement complete all as specified and as directed by Engr- in- Charge Make: kakatiya energy system Pvt Ltd Cat No. Swadeep 66-02EC-5KW 3P or equivalent in Havells/GE |