| 1 | Wiring for circuit/submain wiring along with earth wire with 2 X 2.5 sq. mm +1 X 2.5 sq.mm earth wire of FRLS PVC insulated copper conductor, single core cable in surface/recessed PVC conduit as required. |
| 2 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 3 | 15/16A switch |
| 4 | 6 pin 15/16A socket outlet |
| 5 | Supplying and fixing of 5-32A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Matter: AC / Normal / Emergency Power) etc. as required. |
| 6 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 7 | 8 way, Double door |
| 8 | Supplying and fixing 63A rating, double pole, 240 V, MCB \"C\" Series in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 9 | Supplying, installation, Testing & Commissioning of LED Surface Down lighter (Round/square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60hz, Operating temp range -5 0C to 40 0C centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10%, P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), lifetime of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5sqmm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminium Body including trim. |
| 10 | 12-15 watt |
| 11 | Supplying and making end termination with brass compression gland and aluminium lugs for 4X25sq.mm size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 12 | Supplying and fixing 3 Module waterproof PVC modular box along with modular base & cover plate including 16A Switch & 6 -Pin 16/20A Modular socket complete with all accessories in surface / recess etc. as required. |
| 13 | Supplying, installation testing and commissioning of 80watt multi-functional LED Luminaire to Illuminate under canopy Light suitable for existing 80w LED in indore / outdoor stadium: Housing Die-cast aluminium housing (heat sink) for efficient thermal management, sturdiness & excellent corrosion resistant. SS Hardwares, silicon gasket and M16x1.5 gland is used for cable entry for maintaining ingress protection. Optics & Cover UV Stablized, polycarbonate lens with tempered protective toughened glass5 mm, thermal shock and impact resistant (IK-07) fixed to the housing with aluminium frame and SS screws (for detailed photometric data , please refer LM 79 report & IES file). Light source High efficiency long life LEDs with lumen efficacy of >150 lm/W with view angle 120º to ensure better uniformity of light distribution (For detailed photometric data, please refer LM 79 report & IES file). Electronic driver Built-in electronic LED driver with lower THD, Open Circuit Protection, Surge Voltage Protection & other safety test as per IS 15885 Part-2/Sec 13. Mounting wall or surface mounting using adjustable MS bracket of thickness 5 mm provided with the fixture by 2 elliptical slots of 10x20 mm at center distance of 86mm. including all accessories etc. as required. |
| 14 | Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray/ open duct/ wall as required. |
| 15 | 4 X 25sq. Mm |
| 16 | Supplying and laying of one number PVC insulated and PVC sheathed armoured aluminium conductor cable of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required. |
| 17 | 4 X 25sq. Mm |