| 1 | M&L in repair/replacement ofTube settler of 80 KLD made out of fabricated from structural steel section of Channels/ angles/ supports bracings,clamps and black plates,MS sheetsincluding nuts, bolts, washers, welding ,bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint out side and epoxy paint inside including taking out existing u/s MS work and testing on completion all as directed. |
| 2 | M&L in repair/replacement of Chlorine contact tank of 80 KLD located at Baxipalli made out of fabricated from structural steel section of Channels/ angles/ supports bracings,clamps and black platesincluding nuts, bolts, washers, welding ,bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint out side and epoxy paint inside including taking out existing u/s MS work complete all as directed. |
| 3 | M&L in repair/replacement ofTube settler of 60 KLD STP located at AD centre made out of fabricated from structural steel section of Channels/ angles/ supports bracings,clamps and black platesincluding nuts, bolts, washers, welding ,bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint out side and epoxy paint inside including taking out existing u/s MS work complete and testing on completion all as directed. |
| 4 | M&L in repair/replacement ofTube settler of 30 KLD STPs located at AD centre Near Pump house and near JCOs Mess made out of fabricated from structural steel section of Channels/ angles/ supports bracings,clamps and black platesincluding nuts, bolts, washers, welding ,bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint out side and epoxy paint inside including taking out existing u/s MS work complete all as directed. |
| 5 | M&L for dismanting complete Air compressor set of any type and supply installation testing and commissioning of Air Blower Model AEW -45,Cap 150 Cum/Hr,.0.5 KG pressure Out let - 80 NB Motor - 7..5 HP |
| 6 | M&L for dismanting complete Air compressor set of any type and supply installation testing and commissioning of Air Blower Model AEW -44,Cap 125 Cum/Hr,.0.5 KG pressure Out let - 80 NB Motor - 5 HP |
| 7 | M&L for dismanting sewage transfer Pumpany type and supply installation testing and commissioning sewage Transfer pumpModel SP2HM Centrifugal size 50x50 MM 3 Phase 440 V |
| 8 | M&L for dismanting sewage transfer Pumpany type and supply installation testing and commissioning sewage Transfer pumpModel SP3LM Centrifugal size 80x80 MM 3 Phase 440 V |
| 9 | M&L for dismanting sewage transfer Pumpany type and supply installation testing and commissioning sewage Transfer pumpModel SP2HM Centrifugal size 50x50 MM 3 Phase 440 V |
| 10 | M&L for dismanting sewage submercible pump any type and supply installation testing and commissioning sewage submerciblePump 20 HPsewage Transfer pump size 150 MM 3 Phase 440 V |
| 11 | M&L for dismanting complete Air compressor set of any type and supply installation testing and commissioning of Air Blower Model AEW -55,Cap 280 Cum/Hr,.0.5 KG pressure Out let - 100 NB Motor - 12.5 HP |
| 12 | M&L for dismanting Mono block pumpset of any type and supply installation testing and commissioning ofMono block KDI 235 2 HP 50x40 MM |
| 13 | Supply and laying or fixing or passing in repalcement in well/sump in replacement,1100 volts grade heavy duty, PVC insulated and PVC sheathed mutistranded copper conductor submesible cable 3 core flatincluding connection to submersible motor/ starter panel with & including necessary jointing materials if required and testing on completion complete all as specified and direced for 4.00 sqmm |
| 14 | All as per item no. 13 but for 10.00 sqmm |
| 15 | All as per item no. 13 but for16.00 sqmm |
| 16 | Supply, installation, testing and commissiioning of CPRI approved LT panel board, outdoor type, with front and back door openable type fitted with nuts, bolt and washers fitted with knob and hinges, floor mounted fabricated out of 3.15mm thick MS sheet to be placed over pedestals in PCC 1:3:6 type C-1 cement concrete extending 300mm above ground level with one meter wide plaform in all round panel LT panel shall be totally enclosed weather proof and verming proof with front and rear opening with IP-54 protection as per IS-8623 duly powder coated for connection, RYB, insulator complete pre-wired and cable connection with copper conductor wire upto aluminium bus bar including all incoming and outgoing cable connection with suitable size of aluminium lugs/gland completeall as specified and directed by Engr-in Charge and also comprising of the following.(i)MCCB FP, 25KA,100A Adjustable thermal & Fixed magnetic setting. 01 Nos. incoming (ii)Star delta starter of 2 to 12.5 HP- 5Nos(iii)MCB SPN -32 A - 5Nos(iv)Aluminiumbus bars sleeve insulated of 200 amps capacity TPN -01 No(v)Digital voltmeter 0 - 500 V range with selector switch - 01 No(vi)Digital ammeter 0 - 200 A range with selector switch and CTs - 01 No (vii)Indicators RYB - 01 Set (viii) Internal wiring of the panel board with single core copper cable PVC insulated of suitable size and control fuses. |