| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group-C |
| 2 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc as required.(c) Group -C |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.(a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 4 | (b)2 x 2.5 + 1 X 2.5 sq. mm earth wire |
| 5 | (b) 2 X6 sq. mm + 1 X 6 sq. mm earth wire |
| 6 | S&F of suitable size GI boxwith modular plate and coverin front on surface or in recess , includingproviding and fixing 6 pin 5/6 & 15/16 amps modular Socket outlet and 15/16 amps modular switch, connectionetc. as reqd |
| 7 | S&F of suitable size GI boxwith modular plate and coverin front on surface or in recess , includingproviding and fixing 3 pin 5/6 amp modular Socket outlet and 5/6 amps modular switch, connectionetc. as reqd |
| 8 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required (a)3 Module (100mmX75mm) |
| 9 | Supply & Fixing following modular switch/socket on the existing modular plate & switch box i/c connections but excluding modular plate etc.as reqd.(a)5/6 Amp.Switch |
| 10 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 11 | Wiring for light/ power plug with 2x4 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVCconduit alongwith 1 No 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 12 | Supplying & Fixing following way,Single pole & Neutral,sheet steel,MCB Distribution board,240 V on surface/recess,complete with tinned copper bus bar,neutral bar,earth bar,dinbar,interconnections,powder painted i/c earthing etc.as reqd.(But without MCB/RCCB/Isolator).(A)6 Way, Double Door |
| 13 | (b) 12 Way, Double Door |
| 14 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10KA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.(a)Single pole |
| 15 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.(a)40 A |
| 16 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 17 | Supplying & fixing 20 A, 240 V, SPN Industrial type socket outlet with 2 pole & earth metal enclosed plug top along with 20A C Curve SP, MCB in sheet steel enclosure on surface or in recess with chained metal cover for the socket outlet & complete with connections, testing & commissioning etc as required. |
| 18 | Supply ,Installation, testing and commisioning of ceilling fan with Brush Less Direct Current (BLDC) Motor , class of insulation :B,3 nos. metal(Aluminium alloy) blades, 30cm long down rod , 2 nos. canopies ,shackle kit , saftey rope, copper winding , steel /AL body Power Factor not less than 0.9 , Service value (CM/M/W) minimum as below , 350 RPM (tolerence as per IS:374-2019), THD ( Total Hormonic Distortion) less than 10% , suitable for operation with regulator for speed control and all remaining accessories including saftey pin , nut bolts , washers, temperature rise =75 degree C (max.), insulation resistance more than 2 mega ohm , suitable for 230 V , 50 HZ, single phase AC ceilling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req. (c) 1200mm, service value >=6.0 CM/Min/Watt , air delivery 210 CM/ Min (Minimum) |
| 19 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.Upto 450 mm sweep |
| 20 | Supply of 10\"\" (250 mm )sweep, 1250 rpm exhaust fan Fresh air Typecomplete with shutter, blades etc as required. |
| 21 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body materialand construction as per IS : 10322 withdriver (Replaceable)as per the requirement with Driver efficiency >85% ,Operating voltage AC140-270 Volt,freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20,CRI>80, Flicker free, (flickershould be below 5 %), life time (LED,Driver & electrical circuitary), ofminimum 50000BurningHourswith,70%ofinitial Lumenmaintained tilllife ends, CCT3000°K/ 4000°K / 5700°K/6000°K/6500°K(AsperANSIBin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BISstandard andtrade markcertificate(T.C.).Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. completeinallrespecti/cconnectionswith1.5sqmmFRLS,PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy≥105 <120lm/Watt output . LM79 & LM80 Test reportfromNABLlab foralltestingrequiredforLED fixtures asper BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermalmanagement:heatsinkofaluminumhousing such that LED junction temperature shall not rise above 90°C).Powdercoated die cast/ Extrudedaluminium Body(Thickness ≥1.20 mm18-22 watt |
| 22 | LED Down lighter (COB Type) (System lumen efficacy ≥120 lm/Watt )Supplying, installation, Testing & Commissioning of LED Recessed /surface Down lighter (Round / square/ Rectangular) COB Type offollowing body material and construction as per IS : 10322 with driver as perthe requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 degcentigrade, internal surge protection of 2.5 KV with Short & Opencircuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (UnifiedGlare Rating) < 19, Flicker free (flicker should be below 5 %), life time(LED,Driver & electrical circuitry), life time of minimum 50000 Burning Hourswith , 70% of initial Lumen maintained till life ends , CCT 3000°K /4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(StandardDeviation Color Matching <3, Maximum power consumption should notmore than the specified rating and Fixture shall be of relevant BIS standardand trade mark certificate ( T.C.). Manufactures Word Mark/ NameEngraved/ Embossing/ Screen printing on housing. OEM must have itsown in house NABL lab setup for all testing facilities for LED fixtures.\"complete in all respect i/c connections with 1.5 sq mm FRLS, PVCinsulated copper conductor single core cable and earthing etc. as requiredwith Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement.(Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body including trim with Aluminium Reflector. (C) 12-15 Watt |
| 23 | Supplying, installation, Testing & Commissioning of Flood Light, powde coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >80 , under voltage and over voltage protection, EMIEMC as per CISPR -15 , lenses for beam angle 30 deg-120deg as per the application and the project requirement deg., suitable tilt able fitting, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy > 135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). 70 watt |
| 24 | Online UPS - Input supply: Single Phase, Output Supply :SinglePhaseSupplying, installation, Testing & Commissioning of following capacity at full load(Unity Power Factor) ON LINE Uninterrupted Power Supply (UPS) system suitable for Single Phase input, Single Phase output AC Supply. The UPS shallinclude a Rectifier, inverter, battery bank suitable for 30 minutes back up(Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container)and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. The UPS systems shall beMicroprocessor based Digital Control,using Insulated Gate Bipolar Transistor (IGBT)\"s both for the rectifier & inverter with PWM (Pulse Width Modulation) Technology. The quality of design, manufacturingand inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE.The operating efficiency of the UPS systems shall be >95% at 100%non-linear loads. Current total harmonic distortion (ITHD)/ total demand distortion (TDD) on the input gridshall be< 5% at 100 %load. (The required LCfilters shall be included in UPS cost), extreme power factor kit to be include to limit the input pf to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ) however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall besuitable for incoming supplyAC single phase 160-270V 50 Hzand delivering output ACsupply true sine wavesingle phase 220/230/240 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins and 150% for 1 minute.. Operating temperature0 to 40 deg C, Relative humidity 0-95% non condensing, noise level less than 60db at 1 meter distance, Protection for Under voltage, over voltage, abnormal output voltage, battery over charging, output over current, short circuit, battery deep discharge , 10 KV surge. Displayfor watt/VA,Amp and Voltage power parametersetc. UPS shall comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2,it shall be a Voltage and Frequency Independent (VFI) type UPS (as per standard IEC 62040-1, 2 & 3) . The UPS should be withIGBT Based Inverter Technology, Communication RS232/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge. Required battery racks, DC breaker of suitable rating and interconnecting copper conductorcable of suitable size and connectors and all required accoseries are inclusive in the cost. The UPSshould have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc. 3KVA |
| 25 | Supply , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU),copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). 1.5 TR with 5 Star BEE Rating |
| 26 | S/I/T/ C of4 KVA Voltage stabilizer having input voltage 150V - 270V and output voltage of 195 V -245 V. |
| 27 | S/I/T/C of stand for split AC |
| 28 | S/I/T/C of copper pipe for split AC |
| 29 | S/I/T/C of Drain Pipe |
| 30 | S/I/T/C of 3 Core, 4 Sqmm. Electrical wire for Air Conditioner |
| 31 | Supply of XLPE insulated and PVC Sheathed Al conductor armoured cable 1.1 KV grade conforming to IS-7098 (P-I) as required.2C*6 Sqmm |
| 32 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 33 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. (a)Upto 35 sq. mm |
| 34 | Supplying and fixing of full stainless steel body self-contained drinking water cooler with cooling capacity 150ltr per hr, storage capacity 150ltr and suitable for 230V supply as required. |
| 35 | Supplying AND Installation of Reverse Osmosis (RO) water purifier of capacity 50 ltr/hr complete as required. |
| 36 | P/FHot press sheet mouldedcompound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof polebox of innerdimension 200x160x98mm (NS) complete with suitable arrangement for fixing of 2 nosof 6 to 32 amp single pole MCB & 63 Amp. Doublepole isolator (MCB/Isolator excluded) withneutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plateofsuitable size with danger monogram property printed on the coveretc asreqd. asreqd. |
| 37 | SITC of single phasemonoblock pumpset complete with all accessories workable of 240 Volts 50 Hz AC supply (a) 1 HP (0.75 KW) single phase pumpset head from 12-30 metre suction and delivery 25X25 mm. |
| 38 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. |
| 39 | Providing and fixing 6 SWG dia G.I wire on surface or in recess for for loop earthing as required. |