| 1 | Complete rewinding and repairing of 35 HP three phase, 440 volts, 50 Hz, 2980 RPM 3 set Jyoti make induction motor having following works. |
| 2 | Dismanting of burnt winding wires from slots cleaning and straightening of slots. |
| 3 | Complete rewinding of motor by using super enmamlled copper wire with F-class insulation materials and varnishing, drying by heating process. |
| 4 | Providing and fitting ball bearing no 6312 & 6310 of any standard make. |
| 5 | Providing and fitting of terminal plate. |
| 6 | Providing and fitting of C.I housing sleeve. |
| 7 | Making of bearing seat by welding & lathe machine turning & knurling by chiesting, polishing on rotor shaft. |
| 8 | Complete reinsulation for taking out of motor for foundation sepration of motor and pump for base plate and opening the motor taken out rotor from stator cleaning and decarborizing rotor and stator 3 ohase winding reinsulation, heating etc. complete |
| 9 | Providing and making of diamatrically balacing rotor assembley |
| 10 | Providing & fixing of C.I. motor cooling fan |
| 11 | Complete refitting on motor and base plate checking of horizintal and vertical alignment of motor pump set, coupling with pump and trial testing etc. i/c including loading and unloading charge site to work shop and back. |
| 12 | Providing & repairing of 35 HP, 2920 RPM, 40 mtr. head Jyoti make 3 set pump including following the parts & work at Indira nagar pump house. |
| 13 | Labor charges for opening the pump assembly replacing, unservicable parts G.M. bush, packing nut bolt, ball bearing & lubrication system, glanding etc. complete job work & refitting of complete pump trail & testing etc. complete |
| 14 | Providing & fixing of hardware material including nut bolt packing gland etc. |
| 15 | Providing & fixing ball bearing no. 6207 make any standard |
| 16 | Providing & fixing G.M. long bush. |
| 17 | Providing & fixing G.I. gland bush. |
| 18 | Providing & making of bearing sheet by welding & lath machine turning & polishing on pump shaft. |
| 19 | Providing & changing of coupling rubber star L-190 tight fit with pump & motor coupling. |
| 20 | Providing & complete servicing of pump chamber fully movement of new impuller unit with as per required fitting work including check nut, nut bolt, wiser, oil paper etc. complete |
| 21 | Providing & making SS pump shaft made of EN- 9 materials |
| 22 | Providing and fixing of MS neck ring |
| 23 | Providing and fixing of MS pully with rubber star tight fit with pump and motor shaft |
| 24 | Providing & fixing of 150 mm. dia. Footvalve changing heavy duty new compressed lather complete opening, fitting, changing including with as per required G.I. nut bolt & wiser etc. |
| 25 | Complete refitting of pump after repairing and checking of horizantel and vertical alligment of motor pump set coupling with trial testing on load etc including loading uloading charge from site to work shop and back |
| 26 | Providing & complete repairing of 40 HP ATS starter for 2 nos. set at Indira nagar pump house i/c labor charge for fitting with burnet equipment & changing burnet wiring & lugs etc. as per required complete work. |
| 27 | Providing for complete replacing 250/300 amp., 415 volt, 50 Hz moulded case circuit breaker (MCCB) of any standard make for main power supply equipment. |
| 28 | ML-4 L & T make contactor 50 hr, 415 volt. |
| 29 | ML-2 L & T make contactor 50 hr, 415 volt. |
| 30 | ML-1.5 L & T make contactor 50 hr, 415 volt. |
| 31 | Volt meter 0-500 volt for starter. |
| 32 | Digital amp. meter 0-150 amp. for starter. |
| 33 | Current transformer coil range 50-100/5 amp. for starter |
| 34 | Relay unit range 0-80 amp. |
| 35 | Selector switch for volt meter. |
| 36 | Selector switch for amp meter. |
| 37 | LED indacator lamp unit for starter |
| 38 | Timer assembly unit for starter |
| 39 | On/Off switch unit for starter |
| 40 | Taking out of auto transformer coil set dismantling replacing & re-insulation of coil set and refitting and seating as required. |
| 41 | E.H.V. transformer oil for auto transformer starter. |
| 42 | Providing & fixing of incoming & outgoing fiber connection terminal plate with complete copper nut bolt & wiser. |
| 43 | Complete overhauling of panel & starter for using power circuit wiring & control circuit wiring as per required wire & lugs etc. trail & testing on load complete |
| 44 | Loading & unloading complete job repairing for site to work shop & work shop to site. |
| 45 | Providing and fully rewinding of ATS both coil set i/c dismantiling of ATS coil stamping after fitting fully varnishing, taping and setting of appearing range of connection trail testing on full load at site. |
| 46 | Providing and fixing of heavy duty capacitor 440 V. 15 KVAR capacitor with complete as per required work. |
| 47 | Providing & fixing of rubber mating 12 m.m. thick superior quality high density as per ISI mark |
| 48 | Labor charge for complete repairing opening & refitting of 150 mm dia non return valve & sluice valve i/c cutting of old damaged nut bolt & providing recasting finishing, machining of gate plate holding rod assembly as per sample & required packing, complete nut bolt for fitting on delivery pipe line at site as per following items. |
| 49 | Supply of S.S. 410 spindle rod without G.M. check nut for 150 mm. dia. |
| 50 | Recasting of 150 mm dia sluice valve G.M. check nut i/c recasting, finishing, machining & threading as per sample & cost of extra material complete work. |
| 51 | Repairing of 150 mm. dia. sluice valve C.I. fixture check nut catcher both side i/c welding, finishing cutting as per size of check nut. |
| 52 | Labor charge of opening & refitting of 150 mm. dia. sluice valve i/c cutting of old damaged nut bolt, removal of damaged gland packing, rubber packing, providing, fixing of new by fabricated parts & greasing properly cost of nut bolt, over hanting the valve transportation of material T&P testing & making with risk cover as per requirement. |
| 53 | Providing & fixing of presure gauge meter 0.0 to 7 or 0.0 to 10 Kg./cm2 size 150 mm dia with presure control tube, nut bolt, socket, GI nipple with GM valve 150 mm dia etc complete work. Please Enable Macros to View BoQ information |