| 1 | Material and Labour for XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric power cables (heavy duty) with aluminium conductor, 11000 volts, (E) grade cross sectional area 120 sqmm, 3 core complete all as specified and directed by Engr-in-Charge. |
| 2 | Material and Labour for Cable jointing kit for 11 KV (Earthed) grade cable for outdoortermination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size120 sqmm complete all as specified and directed by Engr-in-Charge. |
| 3 | Material and Labour Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm complete all as specified and directed by Engr-in-Charge. |
| 4 | Material and Labour for earthing complete with galvanized Steel earth plate electrode 600 x 600 x 6.0 mm thick, buried directly in ground (earth pit not less than 2.25 meters below normal ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and incl galvanized iron strip 32x6 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth wire protected by GI protection pipe light grade 15mm dia connected to main earth wire on pole or controll board GI pipe light grade 20mm bore for watering funnel with wire mesh PCC chamber pit in PCC 1:3:6 type C-1 40mm yhick Precast RCC -25 cover reincorced with 8 mm dia TMT bars @ 10 cm C/C on both sides and handle, excavation and earth work in any type of soil and removal upto 50m complete all as sprecified and shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed by Engr-in-Charge. |
| 5 | Supply and laying GItubes light grade ISI marked , galvanized, 150 mm bore laid in trenches or under floor or fixed with poles/walls for protection of electric cable complete all as specified and directed by Engr-in-Charge. |
| 6 | Boring of hole under road/pavement/hard standing or any other situation by mannual means and suitable for passing of GI pipe 100 to 150 mm bore and making good both ends complete all as specified and directed by Engr-in-Charge. |
| 7 | Excavationin trenches not exceeding 1.5 metre wide & not exceeding 1.5 metre in depth for foundation,laying of cable or pipe ( where provided for protection of cable or fixing with poles and stays) and getting out in any type of soilincluding trimming the sides and forming bottom surfaces to required levels complete all as specified and directed by Engr-in-Charge. |
| 8 | Removing surplus excavated soil to a distance n.exc. 50 metre anddepositing where directed at a level n.exc.1.5 metre high from the starting point complete all as specified and directed by Engr-in-Charge. |
| 9 | Returning, filling in trenches in soft/loose soil in layers n.exc. 25 cmafter laying of cables including spreading, levelling, and well ramming complete all as specified and directed by Engr-in-Charge. |
| 10 | Material and Labour for sand filling in trenches with clean dry unwashed sand free from sharp particles, gently punning around the cables complete all as specified and directed by Engr-in-Charge.Note:-Measurement shall be taken after punning down. |
| 11 | Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx 180mm x 40mm complete all as specified and directed by Engr-in-Charge. |
| 12 | All as per srl item No 11 here-in-before but using old cable coverobtained under srl item No7 here in before complete all as specified and directed by Engr-in-Charge. |
| 13 | Supply and Fixing common burnt bricks as mechanical protection of cables using old size sub class ‘B’ bricks laid dry flat over the cable width equal to the length complete all as specified and directed by Engr-in-Charge. |
| 14 | All as per srl item No 13here-in-before but using old bricksobtained under srl item No 7 here in before complete all as specified and directed by Engr-in-Charge. |
| 15 | Boring of hole under road, pavement, hard standing by trenchless technology using ultra sound technique and any othernecessary machine including material and labour for HDPE pipe of 150 mm dia suitable for 0.6 mpa working pressure.During boring work,hard rock may appear as the site is a hilly terrain any damage to the trenchless machine or any other machine will be in the scope of contractor. The contractor should take the permission fromthe NHAI, GAIL , BSES , MTNL , Army and other concern authority for boring is mandatory prior to initiation of work. . If any of the services get damage during trenchless work the cost of repairing/replacement of the same is deemed to be included in the quoted rate by the contractor complete all as specified and directed by Engr-in-Charge.Note:- NOTES :- (i) The contractor will be responsible for taking permission from appropriate authority i.e. NHAI/IGL/ if needed units, needed for above said work.(ii) Trenchless depth shall not be less than 2 mtr from ground level until or otherwise required due to site requirement and contractor has to maintain the trenchless depth upto 4 mtrs from ground levelallquoted rates shall deemed to be included to maintain the trench less depth as directed during excavation to avoid damages to the existing services. (iii) The quoted rate shall deemed to be included for repairs/rectification for damaged done to the existing/ communication and water supply system /sewage system during excavation of work. |
| 16 | Supply & fixing danger notice plate 250 mm x 200 mm made of mild steel sheet 1.6mm thick & vitreous enamelled white on both sides and with letters, figures and conventional skull and bones in signal red colourand fixed with MS clamps, bolts and nuts of approved size for HT 11 KV as required.complete all as specified and directed by Engr-in-Charge. |
| 17 | Supply, installing, testing and commissioning in replacement offactory made and testedHT Panel board, size: 1200 mm x1200 mm x 900 mm ,cubical compartmentalized , out door type double door, suitable for 11000 Volts, 3 phase,50 HZAC supply system having bus bar chamber with insulated aluminium bus bars of size ,50 mm x 10 mm, 3 Nosinstalled on SMC insulators suitable for 11000 Volts.The panel shall be dust and vermin proof. IP-65 class protection and shall be made of 3.15 mm CRCA MS sheet, and 50x 50 x 6mm thick MS angle iron frame work,powder coated front and rear opening type, with apron for cable entry closing locking . The fixing of doubledoors shall be on MS hinges with anti-theft provision (the door can’t be removed from enclosure without cutting enclosure). including excavation,earth workand platform for the panelwith PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed sotne aggregate on top and grouting bolts etc for panel.The platform shall be such that it is of a height 45 cm above the nearest road level complete all as specified and directed by Engr-in-charge. |
| 18 | Supplying, fabrication, installation, testing and commissioning in replacement of LT panel not less than 3mm thick ofmodular polycarbonate thermoplastic enclosures Indoor type with copper bus bar of capacity 400A, factory made, CPRI approved,e floor mounting type, environment friendly, recyclable, UV resistant, halogen and silicon free, anti-acid and anti corrosive, enclosure should be IP-65 Protection in accordance with IEC 60529.The gasket material shall be polyurethane while the gasket shall be internally embedded including suitable working space in bus bar chamber suitable for 3 phase 4 wire system 415V,50HZ,AC supply and fixed on raised PCC 1:2:4,type B1 (20mm graded aggregate) raised base with cable glands, phase indicators, internal wiring, CT of suitable Ratio, digital voltmeter and ammeter, air passing holes with bproper spacing to accommodate to all control switches and other accessories, cable connections with suitable size of lugs/thimble etc including suitable size canopy to cover the panel with proper fixing arrangement including excavation and elarth work including dismantling the unserviceable panel and complete all as specified and directed by Engr-in-Charge comprising the followings.Incoming:-(a) MCCB 250 Amps 3 Pole,36 KA- 01 No(b) Rotary handle- 01 No(C) spreader Link- 01 set( 08 Pcs)(d) RYB Indicating lamp(e) Digital laVoltmeter and ammeter of suitable rating(f) set of ibtCT of ratio - 250/05 AmpsOutgoing.(a) Suitable hole in bus bar for out going cable connection including suitable size nut bolt and fastener complete all as specified and directed. |
| 19 | Supply, installing, testing and commissioning in replacement of factory made and tested (including CPRI type tested certified panel) LT on load change over Panel board ,cubical compartmentalized , out door type double door , mounted on angle iron legs 50x50x6mm thick, suitable for 415 volts, 3 phase, 4 wire, 50 HZAC supply system accomodated with 01 No, on load change over switchexecution of capacity 630 Amps , 4 pole , 415 volt , 50 Hz fixed in any type of . The panel shall be dust and vermin proof. IP-65 class protection and shell be made of 3.15 mm CRCA MS sheet, and 50x50x6mm thick MS angle iron frame work,powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front and rear opening type, with apron for cable entry closing locking arrangement . including excavation,earth workand platform for the panelwith PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed sotne aggregate on top and grouting bolts etc for panel.The platform shall be such that it is of a height 45 cm above the nearest road level complete all as specified and directed by Engr-in-Charge. NOTE:- the LT panel shall not be less than 1000X1000X800MM. |
| 20 | Supply, laying, jointing, testing and commissioning in replacment of LT underground cables 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavyduty armoured, with multistranded aluminium conductors, IS-1554 marked, laid in trenches complete all as specified and directed by Engr-in-Charge. Cables of the following sizes:-Note Excavation, earth work ,cable protection , sand fillings , cable joint shall be measured and paid separately. |
| 21 | 95 Sqmm 3.5 core |
| 22 | 185 Sqmm 3.5 core |
| 23 | 16 Sqmm 4 core |
| 24 | Supply and Fixing in replacement of LED Street light fittings of capacity 90 Watt complete all as specified and directed by Engr-in-Charge. |
| 25 | Supply and Fixing in replacement of LED Flood light fittings of capacity 50 Watt complete all as specified and directed by Engr-in-Charge. |
| 26 | Supply and Fixing in replacement of LED Flood light fittings of capacity 120 Watt complete all as specified and directed by Engr-in-Charge. |
| 27 | Supply, installing, testing and commissioning of factory made and tested (including CPRI type tested certified timer panel) LT Panel board ,cubical compartmentalized , out door type double door , plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 HZAC supply system having bus bar chamber with insulated aluminium bus bars four pole installed on porcelain/SMC insulator. The panel shall be dust and vermin proof. IP-65 class protection and shell be made of 3.15 mm CRCA MS sheet, and 50x50x6mm thick MS angle iron frame work,powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front and rear opening type, with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked,1100 volts grade of appropriate size ( but not less than 2.5 Sqmm) complete all as specified and directed by Engr-in-Chargeand comprising of the following:-(a) Incoming (i)MCCB 4 pole , 125 Amps,50 Hz,415 Volts, 25 KA withAdjustable thermal and fixed magnetic type- 01 Nos(ii) 3 Pole power contractor, type MNX 110 having 2 NO +2 NC -01 No(iii) Electromechanical class time switch day programme with resume- 1 Nos(iv)Auto /manual selector switch -01 No(iv) Voltmeter digital typewith 4 way rotary selector swicth -01No (v) Ammeter digital type with 4 way rotary selector switch-01No (vi)CTsratio 125/5 A ,class 1, ISI marked -01 sets of three (vii) Indicating lamp- 01 set of three(viii)Aluminium bus bar of rating 250 Amp- set of four (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The platform shall be such that it is of a height 45 cm above the nearest road level. |
| 28 | Supply, installing, testing and commissioning in replacement of factory made and tested (including CPRI type tested certified panel) LT Panel board ,cubical compartmentalized , out door type double door , plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 HZAC supply system having bus bar chamber with insulated aluminium bus bars four pole installed on porcelain/SMC insulator. The panel shall be dust and vermin proof. IP-65 class protection and shell be made of 3.15 mm CRCA MS sheet, and 50x50x6mm thick MS angle iron frame work,powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front and rear opening type, with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked,1100 volts grade of appropriate size ( but not less than 2.5 Sqmm) complete all as specified and directed by Engr-in-Charge and comprising of the following:- (Mall Road)(a) Incoming :-(i) ACB 4 pole, 800 Amp, 50 KA, 415 Volt AC Horizontal draw out type motorized, front operated with Micro processor based LCD protection release for adjustable over current, short circuit and earth fault protection-01 No(ii) Voltmeter digital typewith 4 way rotary selector swicth -01 No. (iii) Ammeter digital type with 4 way rotary selector switch-01No. (iv) CTsratio 800/5 A ,class 1, ISI marked -01 sets of three (v)Indicating lamp- 01 set of three(vi) Aluminium bus bar of rating 1600 Amp- set of four (b) Outgoing(i)MCCB 4 pole ,400Amps,50 Hz,415 Volts, 36 KA with microprocessor release- 03 Nos.(ii) MCCB 4 pole ,200Amps,50 Hz,415 Volts, 36 KA with microprocessor release- 02 Nos. (iii)Rotary handle - 05 No(c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The platform shall be such that it is of a height 45 cm above the nearest road level. Note :-(i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCBwithadjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer |
| 29 | Note : Contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work orderand shall be verified by the Engr-in-charge. |