| 1 | Excavation in trenches not exc. 1.5 mtr wide and depth not exc. 1.5 mtr for foundation, laying GI pipes and UG cables etc not exc 10 sqmtr on plan, in soft/loose soil and getting out complete all as specified and directed. |
| 2 | Returning filling in with approved excavated soil including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and directed. |
| 3 | Removing excavated soils to a distance not exceeding 50 metres and depositing where directed at a level nexc. 1.5 metre above the starting point complete all as specified and directed. |
| 4 | Supply and laying 50 mm outside dia double wall corrugated pipe (DWC pipes SN-8) ISI marked for enclosing cable below ground/road surface to a required depth including suitable size couplers for jointing of pipe all as per site requirement etc complete all as specified and directed. |
| 5 | Supply and laying 75 mm outside dia double wall corrugated pipe (DWC pipes SN-8) ISI marked for enclosing cable below ground/road surface to a required depth including suitable size couplers for jointing of pipe all as per site requirement etc complete all as specified and directed. |
| 6 | Materials and labour for GI tubing of 40 mm bore light grade with all fitting fixed to wall/ceiling/pole or in trench formed by road/PCC cutting/boring/ laid on floor as cable protection all as specifed and directed. |
| 7 | Materials and labour for GI tubing of 50 mm bore light grade with all fitting fixed to wall/ceiling/pole or in trench formed by road/PCC cutting/boring/ laid on floor as cable protection all as specifed and directed. |
| 8 | Materials and labour for GI tubing of 80 mm bore light grade with all fitting fixed to wall/ceiling/pole or in trench formed by road/PCC cutting/boring/ laid on floor as cable protection all as specifed and directed. |
| 9 | Supply and laying in trenches/wall LT UG XLPE insulated ,armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 240 sq mm x 3.5 coreincluding taking down old unserviceable cable and making necessery connections all as specified and as directed. |
| 10 | All as item no 9 but of size of cable 185 sqmm 3.5 core |
| 11 | All as item no 9 but of size of cable 150 sqmm 3.5 core |
| 12 | All as item no 9 but of size of cable 120 sqmm 3.5 core |
| 13 | All as item no 9 but of size of cable 95 sqmm 3.5 core |
| 14 | All as item no 9 but of size of cable 70 sqmm 3.5 core |
| 15 | All as item no 9 but of size of cable 50 sqmm 3.5 core |
| 16 | All as item no 9 but of size of cable 25 sqmm 4 core |
| 17 | All as item no 9 but of size of cable 16 sqmm 4 core |
| 18 | All as item no 9 but of size of cable 16 sqmm 2 core |
| 19 | All as item no 9 but of size of cable 10 sqmm 4 core |
| 20 | All as item no 9 but of size of cable 10 sqmm 2 core |
| 21 | Supply and fixingSteel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts, nuts and screws of type 410 SP-31(9 metre long) including taking down old unserviceable RCC pole complete all as specified and directed. |
| 22 | Supply and fixing cable jointing kit for 1.1 KV grade for straight through joint cold shrink type, complete with jointing materialand accessories suitable for 3.5 core XLPE, armoured, aluminium conductor cable of size 70 to 185 Sqmm, Outdoor type, including taking out old damaged joint kit complete all as specified and as directed. (Note:- Excavation and connected items will be measured and paid separately) |
| 23 | Supply and fixing cable jointing kit for 1.1 KV grade for straight through joint heat shrink type, complete with jointing materialand accessories suitable for 3.5/4 core XLPE, armoured, aluminium conductor cable of size 16 to 50 Sqmm,complete all as specified and as directed. (Note:- Excavation and connected items will be measured and paid separately) |
| 24 | Materials and labour for PCC, type C1, (1:3:6), using 20mm graded crushed stone aggregated, as in coping of poles including formworkincluding demolition of old damaged concrete from pole complete all as specified and as directed |
| 25 | Materials and labour PCC, type D2, (1:4:8), using 40mm graded crushed stone aggregated, as in PCC on road cutting /installation area and foundation of pole etccomplete all as specified and as directed. |
| 26 | Materials and labour for boring holes 1mtr deep in soil under roads/PCC as directed for cable passing through pipes of required size and disposal of soil to a distance not exc. 50m. (Note: Connected items like Pipes is measured and paid seperately under relevant items). |
| 27 | Supply and fixing in repair Indicator lamp (AC/DC), LED, type for as per existing fitting.complete all as specified and as directed by Engr-in-Charge. |
| 28 | Supply and fixing in repair 3 Phase LED Ammetercomplete all as specified and as directed by Engr-in-Charge. |
| 29 | Supply and fixing in repair, 3 phase LED Voltmeter complete all as specified and as directed by Engr-in-Charge. |
| 30 | Supply and fixing as in repairsMCCB four pole , 415 Volt, 63 Amps,16 KA , fixed thermal &magnetic setting complete all as specified and directed |
| 31 | Supply and fixing as in repairsMCCB four pole , 415 Volt, 100 Amps,25 KA , fixed thermal &magnetic setting complete all as specified and directed . |
| 32 | Supply and fixing as in repairsMCCB four pole , 415 Volt, 125 Amps,25 KA , fixed thermal &magnetic setting complete all as specified and directed. |
| 33 | Supply and fixing MCCB, 160 Amps, 4P, 25 kA, 415 Volts, with adjstable thermal release & adjustable magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed. . |
| 34 | Supply and fixing MCCB, 200 Amps, 4P, 25 kA, 415 Volts, with adjstable thermal release & adjustable magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed. |
| 35 | Supply and fixing MCCB, 250 Amps, 4P, 25 kA, 415 Volts, with adjstable thermal release & adjustable magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed. |
| 36 | Supply and fixing MCCB, 400 Amps, 4P, 36 kA, 415 Volts, with adjstable thermal release & adjustable magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed. |
| 37 | Materials and labour for earthing complete with galvanized steel pipe electrode 40mm bore, medium grade, 3.5 meters length, buried directly and preferably vertically in ground with top edge not less than 1.25 meters below ground level connected with earthing lead galvanized iron strip of size 25x4 mm connected to galvanized earth pipe by means of bolts, nuts, checknuts and washer of galvanized iron including PCC (1:2:4) type B1 precast RCC cover slab with suitable handle made of 6mm round bar, including necessary excavation and earth work in any type of soil, 20mm dia medium grade galvanized steel tube for watering with one end fix with cast iron funnel and wire-mesh, with protection pipe of 32 mm dia light grade galvanized steel tubing upto 7.5 meters length for drawing earthlead including common salt, charcol , bentonite in alternate layers etc all in around of earthing pipe of 600mm dia, complete all as shown in EP number 2 of SSR Part-1 including testing on completion and including taking down old U/S earthing & testing complete all as specified and as directed. |
| 38 | Materials and labour for earthing complete with galvanized steel pipe electrode 40mm bore, medium grade, 3.5 meters length, buried directly and preferably vertically in ground with top edge not less than 1.25 meters below ground level connected with earthing lead galvanized iron wire of size 4 mm dia connected to galvanized earth pipe by means of bolts, nuts, checknuts and washer of galvanized iron including PCC (1:2:4) type B1 precast RCC cover slab with suitable handle made of 6mm round bar, including necessary excavation and earth work in any type of soil, 20mm dia medium grade galvanized steel tube for watering with one end fix with cast iron funnel and wire-mesh, with protection pipe of 32 mm dia light grade galvanized steel tubing upto 7.5 meters length for drawing earthlead including common salt, charcol , bentonite in alternate layers etc all in around of earthing pipe of 600mm dia, complete all as shown in EP number 2 of SSR Part-1 including testing on completion and including taking down old U/S earthing & testing complete all as specified and as directed. |
| 39 | Materials and labour for water proof, 3core PVC insulated and PVC sheathed, copper conductor cable of size 1.5 sqmm, 1100 Volts grade for electrical connection of street light fittings, complete all as specified and directed. |
| 40 | Supply and fixing thermoplastic polycarbonate cable junction box having protection IP 66\"dust proof, acid resistant, shock proof, fire retardent self extinguisher\" for outside installation with knockout entry for cable of size 25sqmm and 155x155x100 mm with terminals, brackets for street light pole mounting and provision of one 6A MCB SP all as specified and as directed. |
| 41 | Supply and fixing thermoplastic polycarbonate cable junstion box having protection IP 66\"dust proof, acid resistant, shock proof, fire retardent self extinguisher\" for outside installation with knockout entry for cable of size 25sqmm and 295x195x100 mm with terminals, brackets for street light pole mounting and provision of one 6A MCB SP all as specified and as directed. |
| 42 | Materials and labour for painting old painted LT Panel/feeder pillar by two coats of synthetic enamel paint after preparation of surfaces complete all as specified and as directed. |
| 43 | Servicing of LT Panel after shut downand removing all dust particles and proper layout of LT panel wlth gland packing including 2.5 sqmm copper single core copper cable including repairing/replacing door hinges/door lock etc amd for necessary connections complete all as specified and directed |
| 44 | Materials and labour for Preparation of metalic surface with sand paper for street light pole and other steel surface complete all as specified and as directed by Engr- in-Charge |
| 45 | Materials and labour for aluminium paint two coats on newly primed metalic surface of street light pole and other steel surface complete all as specified and as directed by Engr- in-Charge |
| 46 | Materials and labour for two coats of Yellow/black synthetic enamel paint on metalic surface complete all as specified and as directed by Engr- in-Charge |
| 47 | Materials and labour for preparation of old decorated concrete/plastered surfaces and applying two coats of Cement based paint complete all as specified and as directed by Engr- in-Charge |
| 48 | Supply, installing, testing and commissioning outdoor type stainless steel (SS 304) cubical enclosure complete all as specified including providing, fixing and connecting following accessories of approved make :- Incoming :- (i) Copper busbar rating shall be minimum 600 Ampsratings and minimum width of bus bar shall not be less than 50 mm and thickness shall not be less than 10 mm(ii) MCCB 400 Amps 4 pole breaking capacity 25 KA thermal mag protection with Icu = 100% & rated impulse with stand voltage (Vimp) 8 KV with over current & short circuitprotection having double insulation & positive insulation-01 No.Outgoing :-(i) MCCB 250 Amp 4 pole 01 Nos breaking capacity 25 KA, (ii) MCCB160A - 02 Nos breaking capacity 25 KA, (iii) MCCB 125A- 02 Nos breaking capacity 16 KA, (iv) MCCB 100 A - 01No. All MCCB shall have thermal mag protection with Icu = 100% & rated impulse withstand voltage (Vimp) 8 KV with over current & short circuitprotection having double insulation & positive insulation. (v) MCCB TPN 40 Amps-02 Nos.(ii) Current transformer 100/5Amps class-1 15 VA - 2 Nos, Digital Ammeter with inbuilt selector switch -02 No, Digital Voltmeter with in built selector switch -02 No and Modular Indication lamp for main incomer LED type RYB (set of 3)-2 Set (at both incomer MCCB) |
| 49 | Supply, installing, testing and commissioning outdoor type stainless steel (SS 304) cubical enclosure complete all as specified including providing, fixing and connecting following accessories of approved make :- Incoming :- (i) Copper busbar rating shall be minimum 300 Ampsratings and minimum width of bus bar shall not be less than 50 mm and thickness shall not be less than 8 mm(ii) MCCB 100 Amps 4 pole breaking capacity 16 KA thermal mag protection with Icu = 100% & rated impulse with stand voltage (Vimp) 8 KV with over current & short circuitprotection having double insulation & positive insulation-01 No.Outgoing :-(i) MCCB 63 Amp 4 pole 01 Nos breaking capacity 16 KA with thermal mag protection with Icu = 100% & rated impulse withstand voltage (Vimp) 8 KV with over current & short circuitprotection having double insulation & positive insulation. (iii) MCB TPN 40-63 Amps-05 Nos (iii) MCB SP 20 A- 03 Nos.(ii) Current transformer 100/5Amps class-1 15 VA - 2 Nos, Digital Ammeter with inbuilt selector switch -02 No, Digital Voltmeter with in built selector switch -02 No and Modular Indication lamp for main incomer LED type RYB (set of 3)-2 Set (at both incomer MCCB) |
| 50 | Supply, installing, testing and commissioning outdoor type stainless steel (SS 304) cubical enclosure complete all as specified including providing, fixing and connecting following accessories of approved make :- Incoming :- (i) Aluminium busbar rating 250 Amps rating 4 Nos. (ii) MCCB 160 Amps 4 pole breaking capacity 25 KA thermal mag protection with ICS = ISU100% & rated impulse with stand voltage (Vimp) 8 KV with over current & short circuitpro-tection having positive insulation, Spreader Link -01 No.Outgoing :-(i) MCCB 100 Amp 4 pole 03 Nos, breaking capacity 16 KA,thermal mag protection with Icu = 100% & rated impulse withstand voltage (Vimp) 8 KV with over current & short circuitprotection having double insulation & positive insulation. (ii) MCB TPN 63 Amps-02 Nos.(iii) MCB SP 20 Amps-04 Nos.(iv) Current transformer 100/5Amps class-1 15 VA - 2 Nos, Digital Ammeter with inbuilt selector switch -02 Nos, Digital Voltmeter with in built selector switch -02 No and Modular Indication lamp for main incomer LED type RYB (set of 3)-2 Sets (at both incomer MCCB) |
| 51 | Taking down existing serviceable LT UG cable 1100V of any size from existing location and relaying the same after necessary repair work all as specified and as directed(Note: Items if required for repair and excavation works will be measured and paid separately under relevant items) |
| 52 | Taking out old bricks and relaying after cable repair workcomplete all as specified and as directed. |
| 53 | Supply and fixing bracket for street light of 40mm dia of 1.50 mtr length with 02 x clamps of existing size and shape and 04 Nut bolts inclusive of one coat of primer followed by one coat of aluminium paint with finishing complete all as specified and as directed. |
| 54 | Supply and fixing in repair stainless steel 2 way Fire Brigade Inlet connection ISI marked with inbuilt Check Valve including taking down and removed from site complete all as specified and as directed. |
| 55 | Supply and fixingin repair stainless steel 63 mm bore Heavy Duty Single Headed Fire Hydrant Landing valve As per IS:5290 type \"A\" ISI marked with ABS Blank capincluding taking down unserviceablve valve and removing from site complete all as specified and as directed. |
| 56 | Supply and fixingin repair Hose reinforced rubber lined fire Pipe ofSize 63 mm bore ( 15 Mtr Length ) WithBoth Side SS coupling ISI marked Male & Female connection type including taking down complete all as specified and as directed. |
| 57 | Supply and fixingin repair Branch Pipe with SS Nozzle as per IS 903 ISI marked including taking and removing from site down complete all as specified and as directed. |
| 58 | Supply and fixingin repair of Hosebox made of 18 gange MS sheet 800 mm x 600mm x 250 mm with double door with 4 mm thick glasses and door fram made of 16 gauge MS sheet painted fire red out side and brilliant white inside yard complete including taking out old unservicebale Hose box and removing from site compelte all on specified and directed. |
| 59 | Supply and fixingin repairHose reel Drum ( Wall Mounted) swingingtype as per IS : 884 includingHose pipe Length 30 Mtr Long of Size:- 20 mm bore thermo plastic hose as per IS 12585, ISI markedwith PVC ¾ “ Shutoff Nozzle (Hydraulically Crimped) including taking down and removing from site complete all as specified and as directed. |
| 60 | Supply and fixingin repair PVC Shut off Nozzle Size 20 mmbore ISI marked including taking down complete all as specified and as directed and removing from site. |
| 61 | Supply and fixing in repair Hose Clamp including taking down and removing from site complete all as specified and as directed. |
| 62 | Supply & Refilling of Carbon di Oxide Fire Extinguisher 4.5 Kg each complete all as specified and as directed. |
| 63 | Supply & Refilling of ABC Powder Fire Extinguisher 6 Kg Each complete all as specified and as directed. |
| 64 | Supply & Refilling of D-Fire Mechanical Foam Extinguisher 9 Ltr capacity each complete all as specified and as directed. |
| 65 | Supply & Refilling of Watermist baseFire Extinguisher 9 Ltr capacity each complete all as specified and as directed. |
| 66 | Supply only following Items: |
| 67 | Fire Extinguisher Hose Pipe ABC Type |
| 68 | Fire Extinguisher Hose Pipe CO2 Type |
| 69 | valve kit for Fire ExtinguisherABC Type |
| 70 | Fire Extinguisher valve for foam type |
| 71 | Fire Extinguisher valve forWatertype |
| 72 | Pressure Meter |
| 73 | Hanging Clip ( Hooke ) for Fire Extinguisher |
| 74 | Carbon di Oxide Fire Extinguisher 4.5 Kg each |
| 75 | ABC Powder Fire Extinguisher 6 Kg Each |
| 76 | D-Fire Mechanical Foam Extinguisher 9 Ltr capacity each |
| 77 | Watermist baseFire Extinguisher 9 Ltr capacity each |
| 78 | Labour only for Control Panel Fault Detection & Rectification by changing Necessary defective Components along with necessary copper wire, Lugs, Terminal etc. including testing complete all as specified and as directed.Note: Spare parts will be measured and paid separately under approprite item |
| 79 | Supply only following Items: |
| 80 | 3 Pole 32 A Power Contactor |
| 81 | Thermal Overload Relay ,Relay Range 14-23 A |
| 82 | Setof 3 Phase Indicating Lamps (Red Yellow & Blue ) |
| 83 | Push Button Assembly with auxiliary contact BlockStart & Stop |
| 84 | 63 Amp TPN MCB10 KA |
| 85 | 1 Pole 2 Way Rotary Cum Switch for Auto & Manual selection |
| 86 | Single Phase Preventer |
| 87 | Danfoss Make KP35 Pressure Switch |
| 88 | Ball Valve 15 mm |
| 89 | PVC Insulated & PVC Shethed Multi core bright Annealed bare Copper Conductor flexible Round Cables Size 1 Sq mm 2 core FRLSH |
| 90 | Servicing of motor pump set of capacity 7.5/10 HP by disassembling, (i)Motor Front over and back cover part by part dismantling, Internal Coil Heat Varnish, Insulation Testing & refixing. (ii) Pump Part by part Dismantling, ThroughServicing, replacement ofbearing & Gland Packing /Mechanical seal,re assembly with proper alignment complete all as specified and as directed. |
| 91 | Materials and labour for re-winding of motor with superior quality copper winding wire of existing size including varnishing and drying cable jointing and repair replacement of worn at parts of motor/pump reassembling , re-installing at site and testing the same complete all as specified and as directed. |
| 92 | Materials and labour for painting of motor pump set complete all as specified and as directed |
| 93 | Materials and labour for painting of fire fighting water MS pipeline by red colour synthetic enamelled paint by suitable safety arrangement upto height of 20 mtrs heightcomplete all as specified and as directed. |
| 94 | Materials and labour for repairing of fire fighting alarm control panel & rectification by changing necessary defective components alongwith necessary copper wire , PCB repairing work including testing on completioncomplete all as specified and as directed. |
| 95 | Supply and fixing in replacement fire alarm metalic body ISI marked complete all as specified and directed. |
| 96 | Supply and fixing manual call point ISI marked PVC/ABS body wall mounting type including grouting of MCP on wall using 1:3:6 plastercomplete all as specified and directed. |
| 97 | Supply, laying, jointing & testing MS tubing heavy grade 100mm tubing medium grade with all fittings such as bends, elbow, tee, socket, reducers, unions etc as required at site laid in trenches or fixing complete with clips, wall hooks etc. complete all as specified and directed. |