| 1 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty with stranded aluminium conductor, 11KV(Earthed) grade of size 3 Core 240 Sqmm, complete all as specified and directed. |
| 2 | Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth including taking down old cable as in soft/loose soil, complete all as specified and directed. |
| 3 | M&L for dry sand cushioning to under ground cable in trenches including spreading, levelling and hand punning, complete all as specified and directed.Note Punned thickness of sand cushioning shall be measured and paid. |
| 4 | Supply and laying un-reinforced precast cement concrete cable covers of class HV Type-1, size 300mm x 180mm x 40mm(ISI marked), complete all as specified and directed. |
| 5 | M&L for plain cement concrete (1:2:4) Type B-1 (using 20mm graded crushed stone aggregate) as in foundations, filling and mass concrete, complete all as specified and directed. |
| 6 | Cutting trench of width 30cm and depth not exceeding 60cm through road / hard standing for laying cable through GI pipe and returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm after laying the cable, complete all as specified and directed. |
| 7 | M&L for 150 mm dia GI Tubing light grade for cable protection, laid under plinths / floors / roads / culverts or fixed on walls or concealed in walls or along the steel poles by means of MS FI clamps with necessary bolts, nuts, washers etc,complete all as specified and directed. |
| 8 | Returning filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm in thick, complete all as specified and directed. |
| 9 | Removing excavated material to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point, complete all as specified and directed. |
| 10 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink pipe joint complete with jointing material and accessories suitable for size for 3 core XLPE, armoured, aluminium conductor cable of size 240 Sqmm to 300 Sqmm, complete all as specified and directed. |
| 11 | Supply and fix cable jointing kit for 11KV grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, aluminium conductor cable of size 240 Sqmm to 400 Sqmm, complete all as specified and directed. |
| 12 | M&L for precast cement concrete (1:2:4) Type B1(Using20mm graded crushed stone aggregate) route marker and existing HT cable of size 800mm x 300mm x 200mm (with 8mm dia CRS steel stirrups) fixed in position with 450mm x 270mm x 200mm PCC base 1:4:8 type D2 (using 40mm graded crushed stone aggregate) including painting, necessary marking / engraving, excavation and earthwork and removal, complete all as specified and directed. |