| 1 | Taking down carefully aluminium/Copper point wiring light, fan socket or power complete fitting such as switches, ceiling rose, fan regulator, socket including light fitting etc complete with /PVC /MS conduit and T/W battern / casing caping and all as specified and as directed by Engineer-in-Charge. |
| 2 | Taking out old unsv underground cable of any size/make/ type etc from excavted tranches/ on pole passing through pipes etc from different locations complete all as specified and directed by the engr in charge. |
| 3 | M&L for Wiring for circuit/submain wiring alongwith earth wire with the 2x10.0 sq. mm + 1x10.0 sq. mmearth wire of FR is PVC insulated copper conductor, single core cable in surface/ recessed as required in PVC Conduit all as specified and directed by Engineer in Charge. |
| 4 | M&L for point wiring with PVC FRLS insulated single core cable of stranded copper conductors of size 1.5 sqmm, 1100 volt grade drawn in and including rigid PVC casing caping accessories lain on wall/ceiling surface and fixed with PVC saddles and back-plate and GI screws, including PVC insulated single core cable of stranded copper conductor of size 1.5 sqmm as earth continuous wire connected to common earth and PVC Board for housing like switches, sockets, fan regulators etc all as directed by Engineer-in-Chargefor following :-(a) One light point/one fan point controlled by one switch |
| 5 | M&Lin repair for point wiring with PVC FRLS insulated single core cable of stranded copper conductors of size 1.5 sqmm, 1100 volt grade drawn in and including rigid PVC casing caping accessories lain on wall/ceiling surface and fixed with PVC saddles and back-plate and GI screws, including PVC insulated single core cable of stranded copper conductor of size 1.5 sqmm as earth continuous wire connected to common earth and PVC Board for housing like switches, sockets, fan regulators etc all as directed by Engineer-in-Chargefor following :-(b) One 3 pin 5 amps socket outlet independent with cables 2.5 sqmm size |
| 6 | M&Lin repair for point wiring with PVC FRLS insulated single core cable of stranded copper conductors of size 1.5 sqmm, 1100 volt grade drawn in and including rigid PVC casing caping accessories lain on wall/ceiling surface and fixed with PVC saddles and back-plate and GI screws, including PVC insulated single core cable of stranded copper conductor of size 1.5 sqmm as earth continuous wire connected to common earth and PVC Board for housing like switches, sockets, fan regulators etc all as directed by Engineer-in-Chargefor following :-(c) One 3 pin 5 Amp socket outlet on same board. |
| 7 | All same as per item No 5 above but with conductor of size 4 sqmm (Nominal area) for one 3 pin socket outlet 15 Amps on independent board complete and earth continuity wire with 4 sqmm PVC insulated stranded copper conductor Cable complete all as specified and directed by Engr in Charge. |
| 8 | S&F Socket 2 in 1, 5 pin 5 Amp flush type complete all as specified and directed by Engr In Charge. |
| 9 | S&F Switch piano flush type 5 Amp, single pole, one way complete all as specified and directed by Engr in Charge. |
| 10 | S&fSwitch socket combination 2 in 1, 3 pin, 5 Amp flush type complete all as specified and directed by Engr in Charge . |
| 11 | S&F Switch Socket Combination 2 in 1, 3 pin, 15/16 amp flush type Universal complete all as specified and directed by Engr in Charge . |
| 12 | M&Lfor ceiling rose surface Bakelite 65x50mm two to three terminal complete all as specified and as directed by Engr-in-Charge. |
| 13 | S & FLED light fitting 1x9W/1X10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size all as specified and directed by Engr in Charge. |
| 14 | S&Fbasic all purpose surface and wall mounted LED batten with polycarbonate housing and integreted electronic driver of cap 10 watt, 2 feet long,with all accessories complete all as per specified and as directed by Engr-in-Charge.(Havells Cat Pt No. - LHEXACP7IN1W010 or equivalent in Philips/Crompton) complete all as per specified and as directed by Engr-in-Charge. |
| 15 | S&F basic all purpose surface and wall mounted LED batten with polycarbonate housing and integreted electronic driver of cap 20 watt, 4 feet long,with all accessories complete all as per specified and as directed by Engr-in-Charge.(Havells Cat Pt No. - LHEXAXPNIN1W020 or equivalent in Philips/Crompton) complete all as per specified and as directed by Engr-in-Charge. |
| 16 | S&Fin repair sheet metal powder coated versatile Double door SPN distribution board,16 way suitable for MCB\"s fitted with copper bus bar rated 200amps, neutrallink , earth bar and din rail suitable for use on 240 Volt, 50Hz all as directed by Engr in Charge. |
| 17 | M&Lin repair for MCB SPN 63 Amp, 240V with 10KA breaking capacity of \"C\" series in distribution boards all as specified and directed. |
| 18 | S&Fto MCB SP 6-32 Amp with 10KA breaking capacity of \"C\" series in distribution boardswith all accessories complete all as per specified and as directed by Engr-in-Charge. |
| 19 | Dismantling and Taking down old u/s street / building sequrity Light fittingsfrom poles, flood lights, post top lantern lights and garden lights forreplacementwith LED fittings all as specified and as directed by Engr in Charge. |
| 20 | Supply and fix in Repair LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete Specified and directed by Engr in charge. |
| 21 | M&L for GI bracket 1.5 mtr long made out of GI pipe 40mm dia bend to suitable radius incl clamps nuts bolts washersincl painting with aluminum paint etc complete all as specified and directed by Engr in charge. |
| 22 | Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as per specified and as directed by Engr-in-Charge. |
| 23 | Supply and fix in replacement exhaust fan, engineering plasticbody complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 300mm AC single phase with, blades, and frame and louvers of size 300 mm sweepall as per specified and as directed by Engr-in-Charge. |
| 24 | M & L in repair for Earthing complete with galvanised steel earth plate electrode of size (600 x 600 x 6) mm thick buried directly into ground vertically to depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, surrounded on all sides by alternate layers of 150 mm thick charcoal and common salt,connected to MS galvanized earh stripof size 25 x 4 mm by means of lugs, bolts, nuts, washer, check nuts of galvanised iron or steel all as shown in Electrical plate No. 3, GI strip laid in dia 40 mm bore light grade GI Pipe laid in floor and fixed to wall with proper size of clamps and watering pipe of bore 20 mm dia GI light grade including wire mesh funnel, PCC, earth chamber pit (30X30X30cm) with PCC 1:2:4 type B-1 using 20 mm grade stone aggreate including form work cement mortar including CI Pit cover with frame necessary excavation and earth work in any type of soil including testing on completion for desired result all as specified. |
| 25 | S&Fin repair sheet metal powder coated versatile Double door SPN distribution board,8 way suitable for MCB\"s fitted with copper bus bar rated 200amps, neutrallink , earth bar and din rail suitable for use on 240 Volt, 50Hz all as directed by Engr in Charge. |
| 26 | Supply and fix in repair exhaust fan, steel body AC single Phase. 230V of size 300mm sweep heavy duty with, blades, and frame and louvers voltage 230V, 50 Hz, RPM 1200, Copper winding all as specified and directed by Engr in Charge. |
| 27 | Supply and fix in repair exhaust fan, steel body AC single Phase. 230V of size 450mm sweep heavy duty with, blades, and frame and louvers voltage 230V, 50 Hz, RPM 1200, Copper winding all as specified and directed by Engr in Charge. |
| 28 | Wiring for circuit/submain wiring alongwith earth wire with the 2x6.0 sq. mm + 1x6.0 sq. mmearth wire of FR is PVC insulated copper conductor, single core cable in surface/ recessed as required in PVC Conduit all as specified and directed by Engeneer in Charge. |
| 29 | Dismantling old U/S Lt feeder piller box / Busbar chamber incl all outgoing and incoming connection and making good the disturbed area from site all as specified and directed by Engr in Charge. |
| 30 | M&L for Busbar chambers with 4 aluminium busbar strip of rating 400 Amp 6 Way fixed on angle iron of size 40mm x 40mm x 5mm complete all as specified and directed by Engineer in Charge. |
| 31 | Supply and laying or fixingin repairpassing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed 2 core, 10 sq. mm nominal cross section in service connections all as specified and directed by Engr in Charge. |
| 32 | M&L in repair Earthing complete with galvanised steel earth plate electrode of size (600 x 600 x 6.3) mm thick buried directly into ground vertically to depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, surrounded on all sides by alternate layers of 150 mm thick charcoal and common salt,connected to galvanized earh lead wire of size 4.0 mm dia by means of lugs, bolts, nuts, washer, check nuts of galvanised iron or steel all as shown in Electrical plate No. 3, wire protected by dia 15 mm bore light grade GI Pipe laid in floor and fixed to wall with proper size of clamps and watering pipe of bore 20 mm dia GI light grade including wire mesh funnel, PCC, earth chamber pit with PCC 1:2:4 type B-1 using 20 mm grade stone aggreate including form work cement mortar including CI Pit cover with frame necessary excavation and earth work in any type of soil including testing on completion for desired result all as specified. |