| 1 | Supplying, Erection and Commissioning of HOT Dip galvanized octagonal steel pole of 10 mtr height made out of 3 mm thick sheet having bottom 210 mm A/F & top 90 mm A/Fwith built in connector control box with flush cover on height of 1000 mm from the bottom of pole, PCD 320 mm, MS base plate of size 320 mm x 320 mm x 20 mm thick with 250 mm strip in octagonal shape, the pole is to be fixed on existing RCC foundation with bolt and nuts making connection, interconnection with thimble/ lugs in the connector box, earthing, making/ numbering of pole etc as required with following accessories with mounted in built in control box. a) 6 mm thick laminated sheet along with 2 nos. 6 Amp, 10KA, SPMCB, \"C\" charcteristic on the din channel, 2 no. 63 Amp terminal block suitable for 25 sq.mm Aluminumcondr. cable and din channel for MCB\"s.b) Earth stud weld at suitable heighti/c washer, spring washers and nuts.c) Cable support clamps suitable for 2 nos. of 2x 10 sqmm Cable.d) Hot dipped galvanized channel type bracket suitable for mounting upto 4 nos fixture lightings with nut bolt and suitable canopy.e) Drawing of pole andbracket shall be approved from the engineer incharge as per manufacturer before use at site.f) With suitable provisions of anti theft arrangement. |
| 2 | Providing and laying in position M 20 (1:2:4) reinforced cement concrete foundation of size 500 mm long x 500 mm wide and 1600 mm deep i/c excavation of earth, providing cutting, bending and placing in position reinforcement of cold twisted bar of 12 mm dia 1650mm long (approx.) -8 Nos. and reinforcement ring of cold twisted bar of 8 mm dia 1800 mm long (approx.)-10 Nos. (with 150 mm spacing) i/c supplying of 4 Nos. M-24 x 750 mm long (150 mm top threaded portion) GI foundation bolt (EN- 8 grade) with 3 Nos. nuts and 2 Nos. washer, bolt along with 2 Nos. templates/ Anchor plate of size 320 mm x 320 mm x 4 mm thick having 4 Nos. 26 mm dia holes to match with PCD of poles base plate with positioning of foundation bolts and providing 63 mm (OD) 2 Nos DWC pipe for cable entry and exit as required. (Drawing to be approved by Engineer in charge.) |
| 3 | Supplying and drawing following sizes of PVC insulated PVCsheathed/ XLPEcopper conductorunarmoured multicore cable in the existing poles and bracket from cable termination connector to the fitting i/c providing suitable copper lugs connections etc. as reqd. |
| 4 | 3 x 2.5 sq.mm |
| 5 | Supply of PVC insulated and PVC sheathed / XLPE armoured aluminium conductor power cable (As per IS 7098 (Part-1) of 1.1 KV grade i/c connection testing etc.as required. |
| 6 | 2 x 10 sq. mm |
| 7 | 4x16 sq mm |
| 8 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required |
| 9 | Up to 35 Sq mm |
| 10 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 11 | 63 mm dia (OD-63mm & ID-51 mm nominal) |
| 12 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 13 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required |
| 14 | 2 X 10sq. mm (19mm) |
| 15 | Supplyingof feeder pillar with floor mounted Light control LT feeder pillar cubical type double door outdoor type ofSuitable size duly compartmentalized and with general arrangement made out of 2mm thick CRCA sheet having hinged gasket cover and screwed knobs with double locking arrangement and rain protection covers 100 mm and supported with of MS angle iron legs and bottom frame of size 40mm x 40mm x 6mm x 1mtr & inter connections with suitable size of FRLS PVC insulated copper conductor using thimbles wherever required, painting, numbering including supply and fixing of following accessories complete etc. as required.(a)63 Amps. Four Pole MCB (\"C\"-Series), 10kA----1 No.(b)16 Amps. SP MCB (\"C\"-Series), 10 kA------ 10Nos(c) 30 Ampere 4 way neutral link/connector ------2 Nos. (d) Voltmeter(0-500 Volt) 96mm X 96mm square type with selector switch---1 No (e) Phase Indicating Lamp Set with fuses ----1 Set (f) Danger notice plate -----1 No (g) AI. Bus Bar 100 amp. 4 strip, 300 mm long with sleeve and nut bolts-----1 Set.(h)Ammeter (0-30Amp) 96mm X 96mm square type ----1No.(i)Lifting hook on the top of panel board and lighting arrangement inside the feeder pillar---- 1 No. (j) 32 Amps. TP MCB (\"C\" Series), 10KA- 2 Nos. |
| 16 | Supplyingofcubical type Single doorpanel ofSuitable size & made out of 2mm thick CRCA sheet having hinged gasket cover and screwed knobs with single locking arrangement and rain protection covers 50 mm and supported with of MS angle iron legs and bottom frame of size 35mm x 35mm x 5mm x .5mtr includingpainting and fixing of Single Phase sub.Pump controllersuitable up to 3 HP single PH Sub. Pump set with ammeter, and voltmeter and all accessories required for operation of Pump Complete as required.(a)20 Amps. FP MCB (\"C\"~Series), 10kA.-1 No.(b )16 Amps. TP \"MCB (\"C\"-Series), 10kA-1 No.(c)18 Amps. Contactor 220V AC - lNo.(d) 6-l0A overload relay-1 No.(e) Start Stop Push Button with Blook-1 eachf) Auto Manual selector Switch --1 no(g) ON Off Indicating Lamp - 1 each(h) Phase Indicating Lamp set with fuses -1 set(i) Daneer notice plate-1 No(j) Ammeter (0-30Amp) 96mm X 96mm square type-1 No |
| 17 | Supplying, Installation, Testing & Commissioning 200W of LED Flood Light, powder coated pressure die castaluminium body with built in or separate driver asper the requirement with Driverefficiency >85%,Input voltage: Input voltage: 140-270 Volt AC,frequency 50/60 hz, Operating temp range -5 0C to52 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10%as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI>70, under voltage and over voltage protection,EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80extrapolation IES TM-21-11 report, CCT 3000°K /4000°K / 5700°K /6500°K (As per ANSI Bin) SDCM(Standard Deviation Color Matching) <5,Maximum power consumption should not morethan the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/cexternal connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management:heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) DSR.8.15.5 |
| 18 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.DSR 5.2 |
| 19 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. DSR 5.15 |