| 1 | Taking down carefully point wiring for one light, socket or power etc incl all fittings such as switches sockets, holders, light fittings, fan requlators etc and making good the disturbed surface of wall, ceiling etc includingseperating serviceabel light fittings, switches etc and keeping in safe custody for reuse and removal of unserviceable materials from site complete all as specified and directed. |
| 2 | Material & Labour forpoint wiringcomplete with 1.5 sq mm FRLSH, PVC insulated multi stranded copper conductor single core cable 1100 volts grade (Red Colour use for Phase & Black Colour use for Neutral),drawn into and including PVC casing- caping (double interlock type) ofnot less than 20mm width with accessories and fittingssuch as bends, elbows, tees, crosses, junction box etc, fixed on wall/ceiling with GI saddles, GI screws, rawl plugs etc. for one light/fan/ bell point controlled by one switch including pressed steel terminal box powder coatedof suitable size with 3 mm thick plastic laminated sheet cover of approved make for housing/mounting switches, sockets & regulators etc. and drawing1.5 sq. mm copper solid conductor PVC insulated, unsheated cable as earth continuity conductor, connected to common earth and earth dolly , all as specified and directed by Engineer-in-ChargeNote :- Cost of PVC casing & capping, making good disturbed wall surfaces including finishing with cement mortor 1:4, matching with existing colour/paint of surface are deemed to be included in the quoted rate.(ii) Length of point wiring up to 7.50 meter and to be measured from switches to ceiling rose or to the actual load. |
| 3 | All as per item No. 2.00 here-in- before but5 Amp socket on same boardwith other switches complete all as specified and directed. |
| 4 | Allas per ItemNo 2.00here-in- before but for onecalling bellpoint controlled by one one way Bell switches complete all as specified and directed. |
| 5 | All as per BOQ item No 2.00 here-in-beforebut for one power pointtusing by2.50 sq mm FRLSH,PVC insulated multi stranded copper conductor single core cable 1100 volts grade (Red Colour use for Phase & Black Colour use for Neutral), and with and including FRLSH,PVC insulated multi stranded copper conductor single core 2.50 sq mmconductor for earth continuity (Green Colour) , on independent board( but Not below the switch board of light points in the same vertical plane). |
| 6 | All as per BOQ item No 2.00 here-in-beforebut for one power pointtusing by4.00 sq mm FRLSH,PVC insulated multi stranded copper conductor single core cable 1100 volts grade (Red Colour use for Phase & Black Colour use for Neutral), and with and including FRLSH,PVC insulated multi stranded copper conductor single core 4.00 sq mmconductor for earth continuity (Green Colour) , on independent board( but Not below the switch board of light points in the same vertical plane). |
| 7 | Supply and fixed switch piano flush type, single pole , 5/6 Amps, one way complete all as specified. (Note : Item to be measured if executed under new point wiring) |
| 8 | Supply & Fixingsocketoutlets 2 in 1, 5/6 Amps, 230/240 V complete all as specified and as directed .(Note : Item to be measured if executed under new point wiring) |
| 9 | Supply and fix switch socket combination 2 in 1 multipurpose5 pin ,(6 Amps ) flush typecontrolled by one switch complete all as specified. (Note : Item to be measured if executed under new point wiring) |
| 10 | Supply and fixed switch socket combination5 in 1 , 6 pin ,(5/16 Amps ) flush typecontrolled by one switch complete all as specified. (Note : Item to be measured if executed under new point wiring) |
| 11 | Supply & fixed ceiling rose surface bakelite 65 mm x 50 mm two to three terminal suitable for 230 Volts AC 6 Amps complete all as specified. (Note : Item to be measured if executed under new point wiring) |
| 12 | Supply & fixed stepped type electronic fan regulator flush type 240 Volts ISI marked complete all as specified . (Note : Item to be measured if executed under new point wiring) |
| 13 | Supply & fixed Bell push , flush type , 5 amp complete all as specified. (Note : Item to be measured if executed under new point wiring) |
| 14 | Supply & fixed Buzzer, Ding dong, AC 230 Volts, single pole 230 volts all as specified and directed. (Note : Item to be measured if executed under new point wiring) |
| 15 | S & Fin repair LED street/security lights nominal power 35 Watt, LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumenefficacy of minimum 110 lumens per watt, built-in integrated electronic LED driver, output open /short circuit protection, phase to phase protection, over voltage protection, surge voltage protection upto 4 KVs, protection grade IP 66, CRI greater than 80%, CW available CCT of 5700K, power factor of minimum 0.95, pressure die-cast aluminium alloy housing with epoxy powder coated metallic silver finish after phosphochromate treatment, life span of minimum 50000 working hoursincluding fixing at any height and including wiring using three core PVC insulated, PVC sheathed, flexible stranded copper conductor FR-LSH cables suitable for outdoor use, 1.5 sqmm as per IS 694: 2010 complete all as specified and as directed. |
| 16 | S&F in repairs LED 20 Watt tube light fittingintregatedtype, includingLED retrofit tubelamp 20 W , LED tube light nominal power 20 Watt, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, , lumen efficacy of minimum 110 lumens per watt, , integrated electronic driver (SMP based constant current supply) with output short circuit protection and surge protection upto 2.5 KV, protection grade IP 20, CRI greater than 80%, bema angle of 120 clear, THD below or less than 20%, CW available CCT of 6500K, power factor of minimum 0.95 life span of minimum 50000 working hours and LED batten with polycarbonate housing and polycarbonate diffuser complete fittingincluding connecting with PVC insulated multistranded copper flexible cable 1.0 sqmm three core, and PVC round/ square box white colour x 2 Nos for mounting of fittingcomplete all as specified & directed..Note (i) Make of batten and LED tube lamp should be of same make. |
| 17 | S&F in repairs LED 9/10 Watt tube light fitting mirrorintregatedtype, includingLED retrofit tubelamp 9/10 W , LED tube light nominal power 9/10 Watt, L LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, , lumen efficacy of minimum 115 lumens per watt, , integrated electronic driver (SMP based constant current supply) with output short circuit protection and surge protection upto 2.5 KV, protection grade IP 20, CRI greater than 80%, bema angle of 120 clear, THD below or less than 20%, CW available CCT of 6500K, power factor of minimum 0.95 extruded aluminium LED battenslife span of minimum 50000 working hours complete fittingincluding connecting with PVC insulated multistranded copper flexible cable 1.0 sqmm three core, and PVC round/ square box white colour x 2 Nos for mounting of fittingincluding taking down old unserviceable complete all as specified & directed.. Note : Make of batten and LED tube lamp should be of same make. |
| 18 | Hanging only ceiling fan (M.D.supply) and connecting up including provision of cable from ceiling rose or connector to fan including Taking down fan, sealing cable end, dismantling blades and removing fan and blades to store complete all as specified and as directed. Note : Ceiling fan including blade, rod and canopy will be issued under Sch B free for hanging/fixing only |
| 19 | Fixing only in repairs exhaust fan (M.D. supply) made of sturdy Engineering plasticwith necessary bolts including making necessary electric connectionfromceiling rose to the fan with PVC insulated flexible cord copper of size 0.75 sqmm and removing fan and blades to store complete all as specified and as directed. Note : Exhaust fan including louvers will be issued under Sch B free for hanging/fixing only |
| 20 | Supply and fixing in repairs for surfacetype sub main wiring/circuit wiring with two run of 4.00 Sqmm single core PVC FRLSH, PVC insulated unsheathed stranded copper conductor (Red/yellow/blue wires for phases and black wire for neutral) drawn in and including drawn into and including PVC casing- caping (double interlock type) ofnot less than 25mm width with accessories and fittingssuch as bends, elbows, tees, crosses, junction box etc, fixed on wall/ceiling with GI saddles, GI screws, rawl plugs etc. including one run of 4.00 Sqmm single core PVC FRLSH, PVC insulated unsheathed stranded copper conductor as earth wire (green in colour) complete all as specified.Note : (i) Note : 2 runs of line conductor,one run of earth continuity conductor, one run of PVCcasing caping shall be measured as unit length. (ii)Cost of PVC casing caping, conductors,making good disturbed wall surfaces including finishing with cement mortor 1:4, matching with existing colour/paint of surface are deemed to be included in the quoted rate. |
| 21 | S & F in repairs sheet metal enclosure for MCB, DB, SPN, 240 Volts, 100 Amps rated busbar, Confirming to IS as per IEC 61439-3, 8 way Double door enclosure made up of CRCA sheet steel, RAL 9003 powder coated, IP 43 , IK 09 including fixing the DB box flush in wall of any type and making good the distrubed surface to match asthe existing withall as specified and directed by Engr-in-charge. |
| 22 | S & F in repairs sheet metal enclosure for MCB, DB, SPN, 240 Volts, 100 Amps rated busbar, Confirming to IS as per IEC 61439-3, 4 way Double door enclosure made up of CRCA sheet steel, RAL 9003 powder coated, IP 43 , IK 09 including fixing the DB box flush in wall of any type and making good the distrubed surface to match asthe existing withall as specified and directed by Engr-in-charge. |
| 23 | Supply and fixing in repair 240V, 10 KA \"C\" curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB Complete with connection testing and commissioning |
| 24 | Supply and fixed in repairs MCB SPN 32 Amps,\"C\" series 10kA, 240 Volts and to be housed in DBscomplete including necessry connectionall as specified and directed. (Note :- Proper and suitable size cable lugs to be fixed with MCB are included in unit rate of each MCB of any rating) |
| 25 | Supply and fixed in repairs MCB TPN 25-63 Amps,\"C\" series 10kA, 415 Volts and to be housed in DBscomplete including necessry connectionall as specified and directed. (Note :- Proper and suitable size cable lugs to be fixed with MCB are included in unit rate of each MCB of any rating) |
| 26 | Taking down oldceiling fan of any capacity/sweep after disconnecting the electric supplyfromany site, checking for its electrical defect and opening fans for checking of mechanical defect afterdismantling of fan, carry out repair/over hauling including removing dust and grease, and cleaning of internal mechanical parts of fan with kerosene oil, checking of alignment of shaft, oiling and greasing,preparing SurfacesCleaning Dust and Oil using Steel Brush and Soap Water, filling Cavities with Filler and applying One Coat DUCO Paint with Spray Machine including Writing MES No. in Black Paint, and re-assembling, and connecting/refixing of fans in its original position by providing newGI nut bolt, lock washer and lock/split pin complete all as specified and directed by Engr-in-charge.NOTE:(i) Replacement of defective parts like rubber bush, split pin, nuts, bolts, sprng washers, check nuts etc as required are deemed to be included in the item rate. |
| 27 | Material andlabour for earthing complete with Galvanised steel earth plate electrode 600x600x6 mmmm buried directly in ground (Earthpit not less than2.25m below ground level) with top edge of theplate not less than 1.5m below normal groundlevel, connected to GI wire 4 mmasearth lead by means of bolt, nuts, check nutsandwashers of galvanised iron or steel, upto 7.5mlength, earth strip protected by andincluding 15 mm diaGI pipe (medium grade) andconnected to main test point or body of pole/pannel or lightening arrester of main controlling switch as directed including concrete pit in PCC(1:3:6)type C1 , Precast RCC(1:2:4)TypeB1 coverslab of size 54x54x5 cm reinforced with 8 mm dia TMT bars @ 100mm C/C bothwayswith onehandle for lifting made out of 10 mm dia TMT bar embedded in precast cover slab, funnel, wire mesh, 20 mm boreGI Pipe (Medium Grade) for watering, Charcoal andsalt in alternate layers of 15 cm (Compacted Thickness) around the earth electrode including necessary excavation, earth work in any typeof soil anddisposal of spoil to a distance n.exc50 m andnecessary testing complete all asshown in Electrical Plate No 3 of SSRPart-I.NOTE : 1. The unit rare includes for protectionh GI pipe of 15mm and watering pipe of 20mm bore including excavation for earth pit in any type of soil/disintegrate rock. 2. Contractor has to bring agriculture soil from outside of defence land and fill in earth pit to acheive desired result as the soil resisitivity is very high. 3. The cost of GI wireincluding protection pipe,from top of earth plate upto 7.5 meter above/below ground level is deemed to be included in the unit rate. 4. All the joints in GI wire and connectgion with earth plate to be welded through brazing and in addition by providing double brass nut bolt and washer. 5.Costing of welding and nut bolts are deemed to be included in the unit rate |