| 1 | Electric Items |
| 2 | Supply,installation,testing & commissioning of Outdoor type compact substation ( CSS) comprising of (Kirloskar/ ABB/L&T /Schnieder/ Siemens/Hitachi makes): (i)HT side RMU :11KV, 50Hz, 350 MVA,630 Amps VCB, -01 No. , LBS -02 Nos, ( Kirloskar/ ABB/ L&T/Schnieder /Siemens/Hitachi makes) (ii) 160 KVA distribution transformer ,11KV/0.433 KV, 50 Hz, 3 phase, cast resindry type , vector group DYN-11,copper wound( HT and LT) , with +5% to -5% tappings in steps 2.5% with , changeable by off circuit tap links and conforming to IS:11171 , IS:2026 & IEC :76 and CPWD General specifications ( Part-IV substation) as ammended up to date. ( Kirloskar/ ABB/L&T /Schnieder/ Siemens/ Hitachi make) (iii) LT side : 320 Amp, 4 -pole , 50 KA ( MTX1.0 - L&T/ or equivalent Kirloskar/ ABB/Schnieder/Siemens/Hitachi make)The work includes carrying of pre commissioning tests , and charging of transformeretc in all respect.All test reports and OEM certificates must be submitted to engineer in charge. |
| 3 | Providing and Laying of one number PVC insulated and PVC sheathed / HT XLPE power cable of 11 KV grade of3x185 sq. mmsize conf to IS: 7098 (Part-II)in 90 mm Dia(OD-90 mm & ID 76 mm nominal) DWC HDPE pipeISI marked along with all accessorieslike socket bend couplers etc conforming to IS-14930 part II complete with fitting and cutting , jointing etc as required. |
| 4 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 95 sq. mm and upto 185 sq. mm |
| 5 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 6 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required . Upto 240 sq.mm |
| 7 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 3.5X 300 sq mm size conf to IS: 7098 (Part-I) in120 mm Dia(OD-120 mm & ID 103 mm nominal) DWC HDPE pipeISI marked along with all accessories like socket bend couplers etc conforming to IS-14930 part II complete with fitting and cutting , jointing etc as required including providing of DWC HDPE pipe as above. |
| 8 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 185 sq. mm and upto 400 sq. mm ( For laying of above cable alongwith pipe underground). |
| 9 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)(For laying of above cable alongwith pipe on wall) |
| 10 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Above 185 sq. mm and upto 400 sq. mm (At road crossing) |
| 11 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 3.5X 240 sq mm size conf to IS: 7098 (Part-I) in120 mm Dia(OD-120 mm & ID 103 mm nominal) DWC HDPE pipeISI marked along with all accessories like socket bend couplers etc conforming to IS-14930 part II complete with fitting and cutting , jointing etc as required including providing of DWC HDPE pipe as above. |
| 12 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 185 sq. mm and upto 400 sq. mm |
| 13 | Excavation of the cable trenches in hard rock not exceeding 1.5 meters in width and lift upto 1.5 meters including getting out the excavated soil and disposal of excavated soil as directed within a lead of 50 meters. (For road crossing) |
| 14 | Providing, laying and fixing 150 mm dia G.I.pipe (medium class) in the existing trench complete with G.I. fitting etc as required. |
| 15 | Providing & Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 3.5X 120 sq mm size conf to IS: 7098 (Part-I) in 90 mm Dia(OD-90 mm & ID 76 mm nominal) DWC HDPE pipeISI marked along with all accessories like socket bend couplers etc conforming to IS-14930 part II complete with fitting and cutting , jointing etc as required. |
| 16 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct masonry open duct as required. Above 95 sq. mm and upto 185 sq. mm |
| 17 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. (i) 3.5 x 300 sq.mm(70 mm) |
| 18 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. (i) 3.5 x 240 sq.mm(62 mm) |
| 19 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. (i) 3.5 x 120 sq.mm(45 mm) |
| 20 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. |
| 21 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brassnut, bolt, spring, washer excavation and re-filling etc. as required. |
| 22 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connection etc as required. |
| 23 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry closure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 24 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 25 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 26 | SITC of various sizes water protected outdoor (Water proof)huttype compartmentalized type double door cubical panelboth side opening having600/300 mm depth suitable for 415 Volt, 3 phases, 50 Hz made out of 2mm thick CRCA sheet with required hardware duly painted with powder coated .Panel having separate detachable gland plate, angle iron base frame made out of 50mmx50mmx5mm angle iron of suitable size of the feeder pillar (minimum height 60cm), hinged door, both side opening with locking arrangement, earth bar/stud, led pilot light for phase indicator (R,Y,B) on top, 400A/415V 4 strip aluminum bus bar duly PVC sleeved, connection inter–connection with 25% extra current carrying capacity ofMCCBs and solid copper conductor cable 10 sqmm/ solid aluminium rod for MCBs (approved by Engg in charge) for incoming/Outgoing cables, links forspare MCCBs, heavy duty connectors/ terminals for three and single phase cable connections for MCBs where as required and marking of location for incoming and out going distribution i/c grouting the legs in existing floor with 1:3:6 cement concrete foundation and dismantling the existing panel, incoming/outgoing cable connections etc complete as required i/c dismantling the existing feeder pillar and UG cable if required. (Panel should beas per design &drawing approved by Engg in charge). |
| 27 | Providing and fixing of following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal preaders in existing cubicle panel includung drilling holes in cubicle panel making connections etc as required. |
| 28 | 250 Amp, 36kA ,4 Pole MCCB |
| 29 | 200 Amp, 36kA ,4 Pole MCCB |
| 30 | 100 Amp, 36kA ,4 Pole MCCB |
| 31 | 125 Amp, 36kA ,4 Pole MCCB |
| 32 | (Civil Items)Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. |
| 33 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources). |
| 34 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 35 | 15 mm cement plaster on the rough side of single or half brick wall of mix :1:6 (1 cement: 6 fine sand |
| 36 | Providing and placing in position 100 mm thick factory made machine batched & machine mixed Precast RCC Rectangular Covers on drains of footpath of various sizes, of M-25 grade cement concrete for RCC work, including cost of centering, shuttering, reinforcement of 8 mm dia TMT bars of Fe 500 grade @ maximum 100mm c/c on both ways , neat cement punning on finished surface, properly encased on all edges with 1.6 mm thick , 100 mm wide MS sheet duly painted over priming coat , reinforcement to be welded at edges with MS sheet and providing 2 Nos. 12 mm dia bar for hooks etc i/c cost of cartage, all leads & lift, handling at site etc. all complete as per direction of Engineer-in-Charge. |
| 37 | Centering and shuttering including strutting, propping etc. and removal of form for :Foundations, footings, bases of columns, etc. for mass concrete |
| 38 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 39 | Steelreinforcement forR.C.C.workincludingstraightening,cutting, bending, placing in position and binding all complete upto plinth level.Cold twisted bars |
| 40 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 41 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 42 | Modified total sum of Civil DSR items after using correction factor on Cof GST @ 0.973 on item No 29 to 38 (on amount 719949.50*0.973=700510.86) |
| 43 | Add cost index @ 36% on amount (700510.86) |
| 44 | Total of electrical item Sr No. 02 to 27.4 |
| 45 | Add cost index @ 32% on DSR items (expect market rate Item No 02, 03, 07,11, 14, 15 & 26) on amount 748111.01 |