| 1 | Providing & Fixing of Suspended mounting IP66 IK08 rated Integrated High power LED Wellglass light fixture made from Pressure Die Cast Aluminium housing, potted driver, Eye bolt for mounting, PC clear / Opal Diffuser, system lumen efficacy ≥120 lm/Watt output , THD < 10% ,p.f.≥0.95,CRI >70 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , Supply and erection of Conical Reinforced polymer composite pole made of orthophthalic unsaturated polyester resin and reinforced by fiberglass rovings, mats or fabrics in position including excavation of the pit and filling the same with C.C. of M-20 grade (1:1.5:3) from bottom to ground level, with the help of steel frame not less than 40 cm dia up to 176 mm outer dia and 50 cm beyond 176 mm outer dia around the pole, grouting of foundation bolts for base bracket , cable entry, GI cable sleeve, base bracket , the pole shall have internal junction box with cover, |
| 2 | Providing & Fixing of IP20, 2\"x2\" LED Surface/ Recessed mounting Mid power SMD type LED Light fixture not less than 50mm housing depth made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non -yellowish diffuser for uniform light distribution. High efficiency with 4 KV internal/external surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection (Integral with light fixture). System lumen efficacy of ≥ 120 lm/Watt ,THD < 10 % , p.f.≥0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen P&F of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16- 20 amperes including making connection, programming etc. as required One day reserve (mechanical type ) |
| 3 | SITC of Single Stage, water cooled, High Speed (2880 RPM), Horizontal, Centrifugal, Openwell Submersible pumps set pre filled with coolent water and fitted with mechanical seal - T/C Vs T/C, Thrust bearing shall be of carbon + S.S.The stator body of single phase pump shall be of SS and rest of all shall be of cast iron. All casting parts should be cathod electro deposition (CED) coated and other construction material should be confirming to IS : 14220: 2018 . The overall performance of pump shall confirm to BEE energy efficiency level of 3 star. Valid BEE certificate from OEM must be submitted for the same. Motor should be IE2 class as per IEC 60034-2-1: 2007, IEC 60034-30: 2008, &IS12615:2011, including making connection etc as required complete in all respect. OEM shall have submit P & F of ac operated heavy duty 230 /440 Volt power contactor conforming to IS:13947-4-1/IEC:947-4-1 having provision of mechanical interlocking, auuxilary contacts, Din rail mounting type including making connections, testing etc. as required. 40-63 amp |
| 4 | SITC of Single Stage, water cooled, High Speed (2880 RPM), Horizontal, Centrifugal, Openwell Submersible pumps set pre filled with coolent water and fitted with mechanical seal - T/C Vs T/C, Thrust bearing shall be of carbon + S.S.The stator body of single phase pump shall be of SS and rest of all shall be of cast iron. All casting parts should be cathod electro deposition (CED) coated and other construction material should be confirming to IS : 14220: 2018 . The overall performance of pump shall confirm to BEE energy efficiency level of 3 star. Valid BEE certificate from OEM must be submitted for the same. Motor should be IE2 class as per IEC 60034-2-1: 2007, IEC 60034-30: 2008, &IS12615:2011, including making connection etc as required complete in all respect. OEM shall have submit P & F of ac operated heavy duty 230 /440 Volt power contactor conforming to IS:13947-4-1/IEC:947-4-1 having provision of mechanical interlocking, auuxilary contacts, Din rail mounting type including making connections, testing etc. as required. 40-63 amp and ETC |
| 5 | P/Laying P.V.C. / XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand,IInd classbricks covering, refilling earth,compaction of earth, making necessary |
| 6 | P & F of IP 66 protected LED Flood Light luminaire made of single piece powder coated pressure die cast aluminum housing with heat dissipation fins on housing touhened glass cover with suitable lens on LED\"s to achieve various beam angles input power (including drivers loss ) not more then 40 W/60W with luminous efficacy> 80 Lumens/W(As per 1,M79)Appropriate beam angle lens 45o/60o/80o/70oHx140 (High mast ) to be used as per requirement LEDs of cree /Nichia/Osram/Philips/make is to be used at 1W/2W CRI?70 and CCT 2700 K-6500 K. RGB LED to be used. The |
| 7 | P & F of aviation obstruction light luminaire comprising of yellow painted die cast aluminium alloy housing, built in 75 VA step up transformer, heat resistant clear glass cover, neon spiral lamp / 2x100W GLS Lamp / LED Lamps complete in all respectaviation obstruction LED light luminaire |
| 8 | P/Laying P.V.C. / XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with Copper conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required of size. |
| 9 | Supply & Erection of M S lattice structure of height 12.8 mtr as per DISCOMs approved design & details in alignment, including excavation of pit and Providing and laying of cement concrete in ratio 1:3:6 using 43 grade cement, river sand and 12 mm to 20 graded blast crusher broken in pit/ found cement plaster upto 0.50mtr. from top to bottom in 1:3:6 ratio and paint of tower of approved make two coat of red oxide paint and one coat of aluminium paint before installation and one coat of paint after erection work completed as per technical specifications & drawing of DISCOM. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . Please Enable Macros to View BoQ information |