| 1 | Supply, installation, testing & commissioningin replacement of LT panel board, outdoor type, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system,outer body made out of 3.15 mm thick & inner shell made out of 2.00 mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated , The cubicle shall have frame work, bottom & 45 CM long four legs of size 50 x 50 x 6 mm Angle iron, aluminium main busbar duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 SQMM, complete comprisingwith following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder pillar box shall be mounted on PCC 1:2:4 type B-1 (with 20 mm graded stone aggregate) foundation block of suitable size upto 40 cm above ground level complete all as specified and directed.Note.: The cost of the PCC foundation, cable gland and Danger notice plate 02 Nos shall be deemed to be included in the unit rate quoted for the item.Note for Srl Item No 1 to 5:- (1) All type Test Certificates with switch gears ( ACB & MCCB) as per confirming to IS:61439/2011Part-1 andpart -2, to be submitted by the contractor alongwith GA drawing for approval before confirmation of order to the panel fabricator.(2) feeder identification tag as per site is inclusive in the quoted rate. Incoming: Aluminum busbar 4 Pole, of rating 400 Amps.- 01 Set(a)MCCB , 4 pole, 36 KA, 250A, adjustable type with spreader link - 01 No.(b) Digital type Amp meter &Vol meter,3 Phase with CT- 01 Set(c) LED indicating lamps three Nos (RYB)-01 Set Outgoing:-(a)MCCB , 4 pole, 36 KA, 200A, adjustable type with spreader link - 02 Nos.(b)MCCB , 4 pole, 16 KA, 63A, adjustable type with spreader link - 02 No. |
| 2 | All as per Item No 1.00 here-in-above but with followings:-Incoming:Aluminum busbar 4 Pole, of rating 400 Amps.- 01 Set(a)MCCB , 4 pole, 36 KA, 200A, adjustable type with spreader link - 01 No.(b) Digital type Amp meter &Vol meter,3 Phase with CT- 01 Set(c) LED indicating lamps three Nos (RYB)-01 SetOutgoing:(a)MCCB , 4 pole, 36 KA, 160A, adjustable type with spreader link - 02 Nos.(b)MCCB , 4 pole, 16 KA, 100A, adjustable type with spreader link - 01 No. |
| 3 | All as per Item No 1.00 here-in-above but with followings:-Incoming:Aluminum busbar 4 Pole, of rating 600 Amps.- 01 Set(a)MCCB , 4 pole, 36 KA, 400A, adjustable type with spreader link - 01 No.(b) Digital type Amp meter &Vol meter,3 Phase with CT- 01 Set(c) LED indicating lamps three Nos (RYB)-01 SetOutgoing:(a)MCCB , 4 pole, 36 KA, 200A, adjustable type with spreader link - 01 No.(b)MCCB , 4 pole, 16 KA, 100A, adjustable type with spreader link - 04 No.(c)MCCB , 4 pole, 16 KA, 63A, adjustable type with spreader link - 02 No. |
| 4 | All as per Item No 1.00 here-in-above but with followings:-Incoming:Aluminum busbar 4 Pole, of rating 400 Amps.- 01 Set(a)MCCB , 4 pole, 36 KA, 200A, adjustable type with spreader link - 01 No.(b) Digital type Amp meter &Vol meter,3 Phase with CT- 01 Set(c) LED indicating lamps three Nos (RYB)-01 SetOutgoing:(a)MCCB , 4 pole,16 KA, 160A, adjustable type with spreader link - 01 No.(b)MCCB , 4 pole,16 KA, 63A, adjustable type with spreader link - 03 No. |
| 5 | All as per Item No 1.00 here-in-above but with followings:-Incoming:Aluminum busbar 4 Pole, of rating 400 Amps.- 01 Set(a)MCCB , 4 pole, 36 KA, 200A, adjustable type with spreader link - 01 No.(b) Digital type Amp meter &Vol meter,3 Phase with CT- 01 Set(c) LED indicating lamps three Nos (RYB)-01 SetOutgoing:(a)MCCB , 4 pole, 16 KA, 100A, adjustable type with spreader link - 01 No.(b)MCCB , 4 pole, 16 KA, 63A, adjustable type with spreader link - 02 No. |
| 6 | S & F in replacement of adjustable thermal and fixed magnetic release 63 Amps 4 Pole MCCB Breaking capacity Icu 16KA complete all as specified and directed. |
| 7 | All as per Item No 6.00 here-in-above but for 100 Amps 4 Pole MCCB Breaking capacity Icu 16KA complete all as specified and directed. |
| 8 | All as per Item No 6.00 here-in-above but for 125 Amps 4 Pole MCCB Breaking capacity Icu 16KA complete all as specified and directed. |
| 9 | S & F in replacement of adjustable thermal and fixed magnetic release 160 Amps 4 PoleMCCB Breaking capacity Icu 35/36KA complete all as specified and directed. |
| 10 | All as per Item No 9.00 here-in-above but for 200 Amps 4 Pole MCCB Breaking capacity Icu 35/36KA complete all as specified and directed. |
| 11 | All as per Item No 9.00 here-in-above but for 250 Amps 4 Pole MCCB Breaking capacity Icu 35/36KA complete all as specified and directed. |
| 12 | All as per Item No 9.00 here-in-above but for 400 Amps 4 Pole MCCB Breaking capacity Icu 35/36KA complete all as specified and directed. |
| 13 | M & L for Straight through/endjoints heat shrinkable for XLPE/PVC insulated and sheathed aluminium conductor under ground cable 1100 Volts 3.5/ 4 core 06 sqmm to 16 sqmm and testing after jointing complete all as specified and directed. |
| 14 | All as per Item No 13.00 here-in-before but for cable of size 3.5/4 core 25 sqmm to 50 sqmm complete all as specified and directed. |
| 15 | All as per Item No 13.00 here-in-before but for cable of size 3.5/4 core 70 sqmm to 120 Sqmm complete all as specified and directed. |
| 16 | All as per Item No 13.00 here-in-before but for cable of size 3.5/4 core 150 sqmm to 185 Sqmm complete all as specified and directed. |
| 17 | Maintenance Free Conductive Concrete Grounding system comprising:Supply of Maintenance Free Earth electrode 1 nos. made of High Tensile low carbon steel circular rod, molecularly bonded copper, UL Certified Rod with Pre-welded clamp with25kg Milliohms Conductive Concrete Compound.* Copper bodning Thickness- above 254 micron on outer surface. * Copper boned Rod Dia- 17.2 mm UL listed 254 micron copper bonding * Copper purity is 99.9% * Copper grade is as per IS 191 * Length- 4.5 mtr, 14.76 feet. Concrete Encasing 80mm* UL Certified CBR with embrossed marking for genunity.* Meets the requirement as per IS 3043, IEC 60364-5-54, UL 467,IEEE STD 80Earth Enhancement Compound- * Product-Maintenance free Conductive Concrete compound of 25 kg Bag each * Standard - As per IS - 3043 and IEEE80- 2000, Test certificate from NABL Lab * Resistivity after compression- 0.12 ohms per meter * Chemical composition - As per IS Standard * PH should be neutral Contains corrosion inhibitors so that electrode will not get corroded Ultra low resistivity 0.001 ohm meter Resistance consistent Should not depend on moisture for functioning Life 50 years with warranty certificate ROHS Complying IEC 62561-7 Pit Chamber- Round Value Box:- Supply of Poly Plastic heavy duty U V resistant, weather proof environment friendly earth pit cover with cover of auto-locking facility with 2 knock-out openings are provided for the easy strips between the earth pits. • At Top (Dia)- 252 mm • At Bottom ( Dia )- 334 mm• Height - 260 mm |
| 18 | Cutting the worn out/unserviceable lugs from the cables upto 50 Sqmm size with and including supplying and fixing lugs after cutting the worn out /faulty cable end fromHT/LT side of transformer /LT pillar/panel box including necessary earth work for taking out the cable from loop, returning fillingetc and providing aluminium lugs lead including crimping with crimping tools in the existing LT cable and making necessary connections to make it functional complete all as specified and directed. |
| 19 | All as per Item No 18.00 here-in-above but for 70 Sqmm size complete all asspecified and as directed. |
| 20 | All as per Item No 18.00 here-in-above but for 95 Sqmm size complete all asspecified and as directed. |
| 21 | All as per Item No 18.00 here-in-above but for 120 Sqmm size complete all asspecified and as directed. |
| 22 | All as per Item No 18.00 here-in-above but for 150 Sqmm size complete all asspecified and as directed. |
| 23 | All as per Item No 18.00 here-in-above but for 185 Sqmm size complete all asspecified and as directed. |
| 24 | All as per Item No 18.00 here-in-above but for 240 Sqmm to 300 Sqmm size complete all asspecified and as directed. |
| 25 | Supplying, laying, jointing, testing and commisssioning in replacement underground XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cable (heavy duty) 1100 volt grade with size of 6 Sqmm 2 core confirming to IS: 7098 part-I ammended upto date, laid in trenches, along pole/wall/across road etc as per site condition including taking out old unsv cable complete all as specified and directed.Note: Exacavation/Earth work, brick & sand protection shall be measured and paid saperately. |
| 26 | All as per Item No 25.00 but cable of size 10 Sqmm 4 core complete all as specified and directed. |
| 27 | All as per Item No 25.00 but cable of size 16 Sqmm 4 core complete all as specified and directed. |
| 28 | All as per Item No 25.00 but cable of size 25 Sqmm 3.5 core complete all as specified and directed. |
| 29 | All as per Item No 25.00 but cable of size 35 Sqmm 3.5 core complete all as specified and directed. |
| 30 | All as per Item No 25.00 but cable of size 50 Sqmm 3.5 core complete all as specified and directed. |
| 31 | All as per Item No 25.00 but cable of size 70 Sqmm 3.5 core complete all as specified and directed. |
| 32 | All as per Item No 25.00 but cable of size 95 Sqmm 3.5 core complete all as specified and directed. |
| 33 | All as per Item No 25.00 but cable of size 120 Sqmm 3.5 core complete all as specified and directed. |
| 34 | All as per Item No 25.00 but cable of size 150 Sqmm 3.5 core complete all as specified and directed. |
| 35 | All as per Item No 25.00 but cable of size 185 Sqmm 3.5 core complete all as specified and directed. |
| 36 | All as per Item No 25.00 but cable of size 300 Sqmm 3.5 core complete all as specified and directed. |
| 37 | Excavation in trenches in soft/loose soil not exc 1.50 mtrs wide and not exc. 1.5 mtr deep and getting out for taking out/laying cable pole & stay etc complete all as specified and directed. |
| 38 | Returning, filling in, including spreading levelling, watering and well ramming in layers not exc. 25 cm thickcomplete all as specified and directed. |
| 39 | Removal of excavated surplus soil to a distance not exc. 50 mtr away and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed. |
| 40 | M & L for sand cushioning to under ground cable provided with layer of sand (8cm deep before laying the cable and 15 cm deep after laying the cable ie total 23 cm and after punning down sand cushioning will be 18 cm complete all as specified and directed.Note: 18 cm thick only will be considered for payment purpose. |
| 41 | M & L for common burnt clay bricks, sub class \"B\" grade laid in trenches for protection of UG cables perpendicular to the direction of the cables complete all as specified and as directed. |
| 42 | S & F in replacement multi stranded copper cable PVCinsulated unsheathed 1100 volts grade of size 1.5 sqmm 3 core,drawing through tubular pole and GI brackets etc upto choke/lamp and making connections and testing for functioning of light fittings complete all as specified and directed. |
| 43 | S & F in replacement ofonload changeover 4 pole, 100 Amps, 415 volts in sheet metal enclosure including taking down old unsv changeover complete all as specified and directed. |
| 44 | All as per Item No 43.00 here-in-above but for 4 pole, 125 Amps, 415 volts complete all as specified and directed. |
| 45 | All as per Item No 43.00 here-in-above but for 4 pole, 200 Amps, 415 volts complete all as specified and directed. |
| 46 | All as per Item No 43.00 here-in-above but for 4 pole, 400 Amps, 415 volts complete all as specified and directed. |
| 47 | S & F in replacement rectangular type earth pit cover made out of heavy duty cast iron of size 12\"x12\" with MS frame of suitable size incl all necessary masonary work for fixing of earth pit cover incl replacement of wire mesh (jali) funnel complete all as specified and directed. |
| 48 | S & F PVC/Porcelain insulator on wall/MS sheet incl removing of existing earth strip of any type and refixing the same on insulators, complete all as specified and directed. |
| 49 | M & L for brazing/welding on joints of any type of earth strip complete all as specified and directed |
| 50 | Repair and maintenace of APFC Panel of any capacity by disconnecting /taking down unserviceable parts like contractor capacitor bank, CT, selector switch, push botton, indicator, relay, internal wiring, lugs MCB, MCCB, etc and make the APFC panel in serviceable condition complete all as specified and directed by Engr-in-charge at site.Note: (a) Internal wiring of multi strandard copper conductor is deerned to be included in the quoted rate. (b) Replacement of spare parts/ items are paid seperately under appropriate items of sch, complete all as specified and directed. |
| 51 | S & F in replacement of Cylindrical Capacitor, Phase Cap Super Heavy Duty, of capacity 25 KVAR complete all as specified and directed. |
| 52 | All as per Item No 51.00 here-in-above but for capacity of 20 KVAR complete all as specified and directed. |
| 53 | All as per Item No 51.00 here-in-above but for capacity of 5 KVAR complete all as specified and directed. |
| 54 | S & F in replacement of PFC Controller, 3 Phase, 8 Stage relay 415 Voltage as per existing make complete all as specified and directed. |
| 55 | S & F in replacement of Contactor AC 140 Amp complete all as specified and directed. |
| 56 | S & F in replacement of Contactor AC 200 Amp complete all as specified and directed |
| 57 | S & F in replacement of Contactor AC of rating 18 to 60 Amp complete all as specified and directed. |
| 58 | S & F in replacement of 60 watt LED security light fitting with LM80 certified high power LED and lens suitable for secondary integrated IP for better light distribuition, front cover of polycarbonate lens with silicon gasket duly enclosed in powder coated pressure die cast aluminium housing IP66, lumen efficiency not less than 100 lumen/watt, operating temp -10 degree to 50 degree celcius , THD less than 10 % , input voltage range 140-270 volts and PF more than 0.95, sealed potted driver and having protection against open and short circuit, reverse polarity, surge protection 5KV inbuilt and 10KV SPD external complete including taking down unserviceable existing light fitting complete all as specified and directed. |
| 59 | All as per Item No 58.00 here-in-above but for 45 watt LED complete all as specified and directed. |
| 60 | S & F in replacement of 100 watt LED Flood Light fitting with not less than 100 lumen / watt delivered lumen efficacy , cast aluminium alloy housing IP 66 protection, input voltage range 140-270 volts, auto cut off at voltage exceeding 300 volts, auto power on after cut off with time delay of less than 60 seconds, power factor more than 0.95, having name of manufacturer and logo embossed on housing of each light fitting, including taking down existing light fittings complete all as specified and directed. |
| 61 | All as per Item No 60.00 here-in-above but for 120 watt LED flood light complete all as specified and directed. |
| 62 | All as per Item No 60.00 here-in-above but for 150 watt LED flood light complete all as specified and directed. |
| 63 | S & F in replacement of 200 watt LED Flood Light fitting with not less than 100 lumen / watt delivered lumen efficacy, cast aluminium alloy housing IP 66 protection, input voltage range 140-270 volts, auto cut off at voltage exceeding 300 volts, auto power on after cut off with time delay of less than 60 seconds, power factor more than 0.95,driver electrical efficiency not less than 85 % at constant current delivery, with secondary optic lense for energy LED, having name of manufacturer and logo embossed on housing of each light fitting, including taking down existing light fittings all as specified and directed. |
| 64 | All as per Item No 63.00 here-in-above but for 250 watt LED flood light complete all as specified and directed. |
| 65 | S & F Decorative type LED Post Top Lantern light fitting with max. system wattage 40 watt and system lumen output not less than 100 lumen per watt, total system lumens not lessthan 3600 lumens, PF not less than 0.95, THDless than 10%, CRI not less than 70, CCT 5700 TO 6500k,input voltage range 140V to 270V AC 50 Hz, 50000 burning hours,IP 65 class 1 protection with aluminium die casthousing cum heat sinkcircular canopy and clear acrylic cover for 360 degree indirect, uniform, glare free light distribution complete all as specified and directed. |
| 66 | S & F 10 wattled bollard light system lumen output not less than 80 lumen per watt, total system lumens not lessthan 3200 lumens, PF not less than 0.90, THDless than 10%, CRI not less than 70, CCT 5700 TO 6500k, ,input voltage range 140V to 270V AC 50 Hz, 50000 burning hours,IP 65 class 1 protection with aluminium die casthousing cum heat sinkcircular canopy and clear acrylic cover for 360 degree indirect, uniform, glare free light distributionincluding taking out old any type light complete all as specified and directed. |
| 67 | S & F in replacement of LED aviation obstruction light yellow painted die cast aluminium alloy housing with 12W max consumption with all accessories complete all as specified and directed. |
| 68 | S & F in replacement flameproof LED light fitting 60W CMRI certified recommended for Gas/Vapour Group IIAand IIB and zone 1 & 2 IP65 protection made aluminium alloy LM6 complete with all accessories prewired and including connecting up with three core flexible copper cable of suitable size complete all as specified and directed.Note: (a) All fitting shall be ISI marked (b) Lumen efficiency of fitting shall be minimum 100 lumen/watt. (c) PF shall be minimum 0.9(d) THD shall be below 10%. |
| 69 | Repair and maintenance of street light/security lights/flood lights installed at various locations of domestic area by removing the lights from pole/bldg or any other place where ever is installed, throughly checking, cleaning of the glass/ acrylic covers and make them serviceable by removing/repair of unsv parts and refixing the same at original place complete all as specified and directed.Note :- (i) Replacement of the parts shall be measured and paid seperately.(ii) Contractor will provide 20 mtr height ladder/hydra to make hanger LED light servicable. |
| 70 | S & F in replacement of RCBOs of rating 10A to 32A, Double Pole, 100 mA for earth leakage, overlaod and short circuit protection complete all as specified and directed. |
| 71 | S & F in replacement of RCBO of rating 16A, Double Pole, 300 mA for earth leakage, overlaod and short circuit protection complete all as specified and directed. |
| 72 | S & F 240V, 10 KA \"B\" curve miniature circuit breaker (MCB) of single poles and current carrying capacity 6 to 32 AMP complete with connection testing and commissioningcomplete all as specified and directed. |
| 73 | S & F in replacement of 32 Amp HRC fuse complete all as specified and directed. |