| 1 | Providing and fixing Powder coated aluminium (minimum thickness of powder coating 50 micron) work for doors, windows, ventilators and partitions (Fixed portions) with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS:1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing/ paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-Charge. |
| 2 | Supply only 12 mm thick Prelaminatd particle board, exterior grade, prelaminated exterior grade on both sides with decorative choice lamination and fixed to aluminium frames complete all as specified and as directed by Engineer -in-Charge. |
| 3 | M&L for anodised aluminium snap grid frame work for ceiling 605mm x 605mm using aluminium anodised sections with 35 x 25 x 1.5 mm main tee and 25 x 25 x 1.4 mm cross tee and wall angleincluding cutting, drilling, jointing etc complete including provn of 3.15mm dia GI wire suspenders fixed with adjustable connectors complete all as specified. |
| 4 | Supply and fix PVC insulation panels for false ceiling not less than 10mm thick with EPS stuck to 1mm printed PVC sheet suitably placed in false ceiling grid made of Aluminium/G.I./M.S. including fixtures and strips etc as per specification and drawing complete all as specified and directed. |
| 5 | M&L Point wiring complete with 1.5 sqmm single core FRLS PVC insulated andunsheathed cable 1100 volts grade with multistranded copper conductor drawn through and including PVC casing and caping and all accessories fixed to walls / roofs / floors / ceiling etc. and including provision of 1.5 sqmm copper cable green in colour as earth continuity conductor and connected to common earth dolly, including fabricated steel terminal box made out of 1.60mm thick MS sheet concealed in walls, with 3mm thick laminated sheet top cover for housing the switches, socket outlets,fan regulators etc, all as specified and as directed for the following:- |
| 6 | One light/ fan point controlled by one switch |
| 7 | One 3 pin switch socket outlet point 5 amps on independent board |
| 8 | All as per item No 5 here-in-before but for 3 pin 15 Amps switch socket combination on independent board with 4 sq mm copper cable and provision of 4 sq mm FRLS PVC insulated stranded copper conductor cable for earth continuity conductor connected to common earth dolly connecting upto fittings complete all as specified and as directed. |
| 9 | Supply and fix switch piano flush button single pole oneway 5 amp complete all as specified and as directed. |
| 10 | Supply and fix switch socket combination 3 & 2 pin (multi pin) 5 amp flush type complete all as specified and as directed. |
| 11 | Supply and fix switch socket outlet multipurpose 3 pin 15 and 5 amp controlled by one switch, flush type complete all as specified and as directed. |
| 12 | Supply and fixceiling rose surface baklite 65 x 50 mm 3 terminal, complete all as specfified and as directed by Engineer-in-Charge |
| 13 | Supply and fix aluminium housing LED batten 22 watt fitting 4ft in length nano diffuser technology to ensure minimum loss in light transmitted, long life of over 30000 hours includinglamp and connecting with twin core shethed cable from fitting to ceiling rose all as specified and as diected. |
| 14 | Supply and fix metal enclosure distribution board SPN, 8 way 240 volts, with 200 amps rated bus bar, with IP 43 protection and double door, suitable for mounting MCBs complete all as as specified and as directed by Engineer-in-Charge |
| 15 | Supply and fix MCB single pole, 240 volts, 5 to 32 Amps,B series all as specified and as directed. |
| 16 | Supply and fix MCB SPN 240 volts, 40 Amps,B series, all as specified and as directed. |
| 17 | M & L for sub main wiring complete with two runs of 6 Sqmm FRLS single core PVC insulated unsheathed single core cable 1100 volts grade, multistranded with copper conductor (ISI Marked) drawn through and including PVC Casing and caping and all accessoriesfixed to wall/ roofs/ floors etc with one run of 6 sqmm FRLSsingle core multistranded copper conductor as earth continuity conductor complete all as specified and as directed by Engineer-in-Charge. Note : (1) Two runs of cable one run of casing and caping & one run of earth continuity conductor shall be measured as one running metre. |
| 18 | All as per above item Sr No 15.00 but of size 2.5 sqmm complete all as specified and as directed. |
| 19 | All as per above item Sr No 15.00 but of size 1.5 sqmm complete all as specified and as directed. |
| 20 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of cables, pipes, foundation for poles etc., and getting out in hard/dense soil all as specified and as directed. |
| 21 | Returning, filling in, including spreading, levelling, watering and well ramming in not exceeding 25 cm thick complete all as specified and as directed. |
| 22 | Removing surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point as directed. |
| 23 | Supplying, installation of7 Mtr high hot dip galvanized iron Octogonal pole 3.0mm wall thickness, with bottom size 130 mm diameter, top size 70mm diameter with 3mm thick base plate of size 200x200x12 mm, pole fabricating out of medium grade tapered pole octagonal cross section and shall be continuosly tapered with single longitudinal conforming to BSEN 100 25/100 27 with base plate Fe 410 conforming to IS 2062 of suitable thickness with provision of 4 Nos foundation bolts. The pole shall be galvanized as per IS 4759/BSEN1461 standards/housing with aluminum busbar, inbuilt junction box, complete end termination, including single luminary hallowarm 42mm diameter, 2.6mm thick, 1 Meter long, with grouting of base plate in concrete foundation 1:2:4 concrete including excavation, earth work, refilling etc RCC foundation as recommended by OEM,pole Nos shall be marked on each pole with synthetic enamel paint with black backroundcomplete all as specified and directed. Note:-(i) Every pole shall be prewired from Junction box to fixture with 1.5 Sqmm 3 core copper conductor sheathed wirefor Phase, neutral and Earth and necessary suitable arrangement for mounting fitting on pole).(ii) Quoted rate shall include including 1A MCB SP B series,3core 1.5sqmm cable, Earth work and nessaryexcavation i.e reinforcement,holding down bolts, nuts, washer of suitable size etc complete as per manufactures instructions.(iii) Provision of light fittingsshall be measured and paid seperately here-in-after. (iv) Contractor shall submit Drawings of Octoganal Poles&its foundationfor approval of GE. (v) Rate of RCC foundation shall deemed to be inluded in quated rate . |
| 24 | Supply and fixLED street light of70W, not less than 120lm/watt with pressure die-cast aluminiumhousing along with prismatic polycarbonate modular secondary lens optics for street lightapplication with IP66 ingress protection and impact resistance of IK08/IK07. 4kV inbuiltsurge and 10kV external surge protection with Top /bottom opening driver cover for easy maintenance and soft illumination effect and powder coated complete on existing GI OctogonalPole pole of 6 mtr heightall as specified and as directed.Make:Cromptoncat No: CRP-409-70-57-HL2-GL-NSG andMake Havels Cat no ENDURASUNDOWNSL70WLED 765PASYBOTG or equivalentapproved from makes as specified in PS |
| 25 | Supply and fix in repairs 6kw ASTRONOMICAL timer panel RangeConforms to IS/IEC 60947-4-1, with 32amps contactor, 40amps MCBand Timer,Provided with Protection Degree IP 54,Extended wide band (150 Vac - 300 Vac) coil,FRLS (Fire retardant low smoke) Internal wiring,In-built Short-Circuit Protection, Class H Insulation complete all as specified and as directed. |
| 26 | Supply, install, testing and commisioning of junction boxes in repairs, weather/vermin proof made out of 3.15mm thick CRCA sheet(CPRI approved) duly powder coated ofsize 60cm X 60cm x 60cm(depth), floor mounted free standing type, aluminium bus bar 200 Amps current carrying capacity for 3 Nos phase & neutralwith colour coded heat shrinkable insulated sleevesand insulated support, mounting the junction box with PCC (1:3:6) type C1, bedding upto height of 30cm above ground level complete all as specified and directed. |
| 27 | Material and Labour for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6mm thick buried directly in ground ( earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less thab 1.5 Meter below normal ground level connected to GI wire of dia 4mm as main earthing lead (upto 7.5 m length from earth electrode to test point) by means of galvanised iron or steel bolts, nuts, check nuts & GI washersand GI tubing 15 mm bore medium grade for earth lead protection up to main earth test point and including concrete pit in PCC (1:3:6) type C1, pre cast RCC (1:2:4) type B1 as in cover slab 54 x 54 x 5 cm including 8mm dia MS TMT bars @ 150 mm c/c as in reinforcement with one handle for lifting made out of 8 mm dia MS bar, wire mesh, 20 mm bore GI tubing (Light Grade) for watering and funnel, charcoal or coal and salt in alternate layers including excavation earth work in any type of soil, RFR and removal of surplus soil complete all as specified and directed electrical plate No. 3 of SSR part - I complete all as specified and as directed. |
| 28 | Material and Labour for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6mm thick buried directly in ground ( earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less thab 1.5 Meter below normal ground level connected to by using galvanised iron strip of size 32X6 mmas main earthing lead (upto 7.5 m length from earth electrode to test point) by means of galvanised iron or steel bolts, nuts, check nuts & GI washersand GI tubing 15 mm bore medium grade for earth lead protection up to main earth test point and including concrete pit in PCC (1:3:6) type C1, pre cast RCC (1:2:4) type B1 as in cover slab 54 x 54 x 5 cm including 8mm dia MS TMT bars @ 150 mm c/c as in reinforcement with one handle for lifting made out of 8 mm dia MS bar, wire mesh, 20 mm bore GI tubing (Light Grade) for watering and funnel, charcoal or coal and salt in alternate layers including excavation earth work in any type of soil, RFR and removal of surplus soil complete all as specified and directed electrical plate No. 3 of SSR part - I complete all as specified and as directed. |
| 29 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4 core including taking out oldcompleted all as specied as directed. |
| 30 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core including taking out old completed all as specied as directed. |
| 31 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95sq mm 3.5 core including taking out old completed all as specied as directed. |
| 32 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3.5 coreincluding taking out old completed all as specied as directed. |
| 33 | Supply and lay HDPE double wall corrugated pipes and including fittings such as couplers, bends, end caps etc., ISI marked of outer dia of 50mm and inner dia of 38mm polyethylene with smooth internal and profile external surface for non pressure under ground cable complete all as speciedd and as directed by Engineer-in-Charge. |
| 34 | Supply and lay HDPE double wall corrugated pipes and including fittings such as couplers, bends, end caps etc., ISI marked of outer dia of 77mm and inner dia of 63 mm polyethylene with smooth internal and profile external surface for non pressure under ground cable complete all as speciedd and as directed by Engineer-in-Charge. |
| 35 | Supply and lay HDPE double wall corrugated pipes and including fittings such as couplers, bends, end caps etc., ISI marked of outer dia of 110mm and inner dia of 95mm polyethylene with smooth internal and profile external surface for non pressure under ground cable complete all as speciedd and as directed by Engineer-in-Charge. |
| 36 | Supply, laying and fixing in repairs 50mm bore GI light grade for necessary road crossing, culverts etc for cable protection all as specified and as directed. |
| 37 | M&L for PCC 1:3:6 type C2 using 40mm graded stone aggregate as in foundations of pole/ stay assembly complete all as specified and directed by Engineer-in-Charge. |
| 38 | M&L for PCC 1:2:4 type B1 using 20mm graded stone aggregate as in coping of pole including necessary form work complete all as specified and directed by Engineer-in-Charge. |
| 39 | M & L for Taking down old Light fitting with Bracket and Arm complete all as specied and as directed. |
| 40 | Fixing only Serviceable LED lights on newOctogonal poles obtained from above complete all as specied and as directedby Engr -in -Charge. |
| 41 | M & L for excavation and Demolition the old Existing RCC polescomplete with Pcc foundation and removal of all debiries to outside MOD land and making good disturbed surfacesallasspecified and asdirected . |
| 42 | Supply, installation, testing and commissioning weather and vermin proof L.T. feeder pillar box factory fabricated out door cubicle/KIOSK typetotally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and aluminium bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including connecting the following including dismantling existing damaged LT Panel (a) Aluminium Bus bar,400 amps TPN -01 set(b) MCCB 4 Pole thermal magnetic release 415 volts 200A 36 KA-01 (incoming)(c) MCCB 4 pole thermal magnetic release 415 Volts 100A 25 KA - 04(d) MCCB 4 pole thermal magnetic release 415 Volts63 A, 25 KA - 02(e)MCBDP230Volts 40 Amps, -04 (f) Voltmeter digital type 0-500 V with inbuilt selector switch-01 No(g) Ammeter digital type 0-500 A with in built selector switchand CTs-01 No(h) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three) |
| 43 | Supply, lay, test and commissioning under ground XLPE insulated and PVC sheathed, armoured heavy duty under ground cable, suitable for earthed system, laying in trenches/duct sleeving through pipe in duct, ISI marked with aluminiumstranded conductor 1100 volt grade of cross section area 70 sq mm 3.5 core |
| 44 | Supply & lay cable protection pipe of HDPE double wall corrugated (DWC) incl couplers,bends etc of size 63 mm OD and ID 50mm confirming to IS 14930 -II and ISI Marked all specified and directed. |
| 45 | Material and Labour for cutting existing BT / PCCroad of size 45cm x 60cmfor taking out/laying of underground cable/pipe and including necessary earth work and refilling the same in layers well ramming including watering as required and matching with the existing surface with 200mm thick PCC 1:2:4 type B1 and curing the same with wet gunny bagsand removing debris to a distance not less than 50m complete all as specified and as directed . |
| 46 | Supply, Laying,GI tubing light grade for encasing LT cables for mechanical protection, laide in trench /floor/under road or along the pole by means of M.S.F.I. clamps with necessary bolts nuts and washers etc of size 80 mm dia, complete all as specified. |