| 1 | Dismantling & taking down ACSR/AAC conductor of any size from LT over head line and removing from site complete all as specified |
| 2 | Dismantling & taking down shackle/pin insulators of any size and type complete and removal from site complete all as specified |
| 3 | Dismantling & taking down cross arm, channel, angles, flat ironvarious size/shape incl nut, bolt and washers etc complete and removal from site complete all as specified and as directed. |
| 4 | Dismantling & taking down GI guard wire of any size from LT over head line and removing from site complete all as specified and directed |
| 5 | M&L for XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheather laying in trenches/cable ducts, fixed to wall/pole and including taking down old unserviceable cable complete all as specified and directed of following sizes Note:- (i) Excavation & earth work, new sand, new bricks for cable protection shall be measured & paid seperatly in respective items here- in- before. |
| 6 | LT cable of size 150 Sqmm 3 ½ core |
| 7 | LT cable of size95 Sqmm 3 ½ core |
| 8 | LT cable of size70 Sqmm 3 ½ core |
| 9 | LT cable of size50 Sqmm 3 ½ core |
| 10 | LT cable of size35 Sqmm 3 ½ core |
| 11 | LT cable of size16 Sqmm 4 core |
| 12 | LT cable of size10 Sqmm 4 core |
| 13 | LT cable of size6 Sqmm 4 core |
| 14 | LT cable of size4 Sqmm 2 core |
| 15 | Excavating in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for laying of cable, foundation etc, and getting out in soft /loose soil all as directed.Note - Excavation/earth work shall be done by manually manner with the safety of Data/OFC/telephone cable. If any cable damaged during the excavation to be repair same time and cost to be included in qouted rates. |
| 16 | Returning filling in including spreading, leveling Watering and well ramming in layers not exceeding 25cm all as directed. |
| 17 | Removing excavated surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as directed. |
| 18 | Supply and laying sand river for cushioning with layers of sand 8 cm before lying of cable and 15 cm after lying of cable (total 23 cm) in trenches complete all as specified & directed.(Note: Thickness after punning shall be measured for payment ) all as specified and directed. |
| 19 | M&L for laying bricks \"B\" class over a cable (Width wise) old liad dried complete all as specified and directed. |
| 20 | Material and labour for cutting of metallic road/ hard standing/hard rock/wall up to a size not exceeding 20cm widthand not exceeding 60cm in depth for laying ofprotection pipe for cable including making good the disturbed road/hard standing by providing PCC (1:2:4) type B1, 40 mm grade crushed stone aggregate upto existing surface level or removing the any type of tiles carefully and refixing properly as per existing surface including suitable size of GI pipe (if necessary)complete all as specified and as directed by Engineer-in-charge.Note: 1. If damaged/broken the any type of tiles while removing, the contractor shall replace the broken tiles with new one.2. The Quoted rate is included for all materials/T&P/Machinery used in this item, no material can paid/measured separately.3. All the removable tiles/re fixable material shall kept carefully at a safe place for refixing with in this quoted rate.4. GI Pipe shall measured and paid separately under relevant item. |
| 21 | Boring of holes under road, pavement, hard standing by adopting horizontal boring including supply and inserting of HDPE pipe of 100 mm dia not less than 6kg/cmworking pressure confirming to IS allas specified and directed. Note: Depth will not be less than 1.00 M below the road pavement and hard standing boring shall be carried out without damaging the road and hard standing. |
| 22 | Earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of plate not less than 1.5 m below ground level connected to and including galvanised earth strip of size 25x4 mm (up or 7.5 mtr length) and GI pipe 40 mm light grade for protection of GI earth strip by means of bolts, nuts, checknuts and washers made out of galvanised iron and connected to earth test point as shown in electrical plate No. 3 of SSR Part-1-2009 and as specified or indicated and testing on completion including excavation and earth work any in type of strata available at site, PCC (1:3:6) type C-1 for earth chamber, precast RCC slab 50 mm thick in cement concrete (1:2:4) type B-1 reinforced with welded steel wire fabric (xpm) weight not less the (4kg/sqm) funnel with GI watering pipe of 20mm bore medium grade, wire nuts and lugs complete all as speified and directed by Engr-in-charge. |
| 23 | Supply, fabricating, installation, testing and commisioning LT panelBox (KIOSK) out door type weather proof, dust & vermine proof CPRIapproved test type make LT panel made out of 3.15 mm thick CRCA sheet front and back door openable type and suitable for operation on 415V, 50Hz, AC supply, conforming to IP-54 and fixed on angle iron frame/chanel of suitable size complete, aluminium bus bar chamber cable alley, cable glands brass crommium plated of diffrent sizes suitable for incoming and out going cable panel, painted with powder coated paint incuding necessary PCC (1:3:6) foundation extending 300mm above GL and 60cm wide platform in front of the panel complete all specified and directed by Engineer-in-Charge withthe following accessories :-(Note: The Contractor Shall submit the drawing with sample of accessories and CPRI certificate for approval before executing the work.)INCOMING(a) Aluminiumbusbar of capacity 300 Amps with eppoxy insulated supports 3 phase and neutral -1 set(b) MCCB 250 Amps 4 pole 36 KA adjustable type with ICU=100%ICS - 01 No (c ) Volt meter digital type 96 sqmm with in built selector switch - 01 set(d) Amps meter digital type 96 sqmm with suitable CT\"s-03 Nos and in built selector switch - 01 Set(e) Indicating lamp RYB LED type - 01 setOUTGOING(a) MCCB 100 Amps, 4 Pole 36KAfixed typewith ICU=100%ICS- 03 Nos (b) MCCB 63 Amps, 4 Pole 36KAfixed type with ICU=100%ICS - 02 Nos (c) MCB TPN 32 Amps - 01 Nos |
| 24 | Supply, fabricating, installation, commissioning of Bus bar box out door typetotally enclosed dust and vermin proof floor mounting with hinged doors and locking arrangement front and back fabricated out of 3.15 mm thick CRCA sheet CPRIapproved test type make including powder coated paint finish including all accessories, provision independent removevable MS plates for fixing cable glands for all incomming and out going cables and complete control wiring with 2.5 sqmm copper conductor incuding necessary PCC foundation complete all specified.Note:- (1)Rates deemed to be included for suitable lugs and glands for incoming and out going of LT UG cable.(2) The Contractor Shall submit the drawing with sample of accessories and CPRI certificate for approval before executing the work.(a)Main incoming 315 Amps MCCB04 pole, 36 KA with ICU=100%ICS - 01 Nos.(b) Electrolytic grade aluminium bus bar 600A rating for 3 phase and neutral including PVC colour coded sleves. - 01 Set(c) LED lamps for R,Y,B Phase indicationwith control fuse/MCB- 01Set(d ) Volt meter digital type 96 sqmm with selector switch - 01 set(e)Amps meter digital type 96 sqmm with suitable CT\"s-03 Nos and in built selector switch - 01 Set (f) Insulators, wiring, bus bar sleeves, lugs, gland,sheet metal enclosure etc including complete wiring with suitable size of copper wire |
| 25 | All as per item No.15 here-in-before but Main incoming MCCB 160 Amps 4 pole 36KA with ICU=100%ICSand bus bar of rating 300A. |
| 26 | All as per item No.15 here-in-before but Main incoming MCCB 100 Amps 4 pole 25 KA with ICU=100%ICS and bus bar of rating 200A. |
| 27 | All as per item No.15 here-in-before but Main incoming MCCB 63 Amps 4 pole 25 KA with ICU=100%ICSand bus bar of rating 200A. |
| 28 | All as per item No.15 here-in-before but Main incoming MCCB 32 Amps 4 pole 16 KA with ICU=100%ICS and bus bar of rating 100A. |
| 29 | Supplying & fixing of terminal panel box ofsize 155 mm x 210 mm x 92mm of outdoor pole mountedfront operated cubical type Box as per IEC 60439-1 (IS:8623) & IEC 60439 -2dead back, free standing, dust and vermin proof, switchboard with IP 66 protection with suitable for use 440 volts, 3 phase 4 wire 50 Hz system. The Board/Panel shall be made out of modulerTHERMOPLASTIC ENCLOSURES. The gasket material shallbe Polyurethane; while the gasket shall be internally embedded. The manufacturer of board/panel shall submit a copy oftest report in accordance with IEC 60529. The Panel Should be assembled at manufactures factory.and Panel box having 1x 6 Amp MCB , 16 Sq.mm Terminal Block (04 Nos) , 6 Sq.mm Disconnected Terminal (01 No) ,4 Sq.mm Earth Terminal (01 No) including MS clamp flat 20 mm x3 mm in suitable fixed to polewith nut bolts Complete. |
| 30 | M& L for Rigid non-metallic PVC conduit of size 20 mm dia exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. to be fixed on pole with all fittings including mouth pieces for passing of sub main wiring three core of copper wire 2.5 sqmm to provide woth conduit and connection to LED light and control box complete.. |
| 31 | M&LCable PVC insulated PVC unsheathed un-armoured copper conductor (multi stranded) of cross sectional area 1.5 sq mm 3 core drawing in PVC conduit on Steel tubular/PCCpoleall as required for connections to light fittings complete. |
| 32 | M& LforGI tubing light grade of size 80 mm dia fixed on walls / laid in trenches as protection pipe for under ground cable including provisioning of specials and clamps etc including taking down of old unseviceable pipe any type and any sizecomplete all as speified and directed.Note - Excavation to be paid separately in respective items. |
| 33 | M& LforGI tubing light grade of size 50 mm dia fixed on walls / laid in trenches as protection pipe for under ground cable including provisioning of specials and clamps etc including taking down of old unseviceable pipe any type and any sizecomplete all as speified and directed.Note - Excavation to be paid separately in respective items. |
| 34 | M& LforGI tubing medium grade of size 40 mm dia fixed on walls / laid in trenches as protection pipe for under ground cable including provisioning of specials and clamps etc including taking down of old unseviceable pipe any type and any sizecomplete all as speified and directed.Note - Excavation/PCC cuttingto be paid separately in respective items. |
| 35 | Exavation over areas, n exc 1.5 m deep and getting out in soft/ loose soil. |
| 36 | M & L PCC 1 : 4 : 8 type D-2 using 40 mm stone aggregate as in foundation filling and mass concrete . |
| 37 | M&L for old size brick work with sub-class \"B\" bricks, straight or curved on plan exc 6m mean radius built in CM 1:6 . |
| 38 | M&L for Plain cement Concrete C2,1:3:6 (40mm graded aggregate) as in surface channels and drains. |
| 39 | M & L PCC 1:2:4 type B-1 using 20 mm graded store aggregate as in coping and channel including use and waste of form work where necessary. |
| 40 | M & L 15 mm thick rendering in cement mortar 1:4 on fair faces of brick work or concrete surfaces, surface finished even and smooth without using extra cement . |
| 41 | M&L for extra forming fair finished drain or channel over 30 cm inner girth in cement concrete, using extra, including forms, moulds, mitred/ stopped end etc. |
| 42 | M & L Mild steel bars 10mm diaTMT Bars and over,cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with theincluding mild steel wire (annealed) not less than 0.9mmdia or securing with clips quality conforming to |
| 43 | Description all as per ser item No 33 above but, 6mm to 8mm dia. |
| 44 | M & L for RCC (1:2:4) type B-1using 20 mm graded stone aggregateas in slab supported on wall ,Chajjas,deck slab Shelves/tank stagingetc. |
| 45 | Use & waste form workto soffits of suspended slab such as floor or roof slab, chajjas and similar work not exc 200 mm thick (Horizontal or sloping) for flat rough finished complete. |
| 46 | M&L for reinforced concrete pipes 450mm dia bore, class NP-2, laid and jointed complete. |
| 47 | Returning filling in soft/loose soil in trenches after laying pipes construction of manhole etc including spreading, leveling, watering and well ramming in layers not exceeding 25 Cm thick layer. |
| 48 | Removing surplus soil to a distance n exc 50M and depositing where directed at a level not exc 1.5M above the starting point . |