| 1 | Excavation in trenches (soft & loose soil) n.exc. 1.5 mtr wide and n.exc.1.5m in depth for laying of UG Cable including getting out all as specified & directed by Engr-in-Charge |
| 2 | Returning filling in and includingspreading, leveling, watering and well ramming in layers not exceeding 25 cm in soft /loose soil complete all as specified and directed by Engineer in Charge. |
| 3 | Removing excavated material n.exc. 50m and depositing where directed at a level n.exc 1.5 m above starting point all as directed by Engineer in Charge. |
| 4 | M&L for spreading & leveling dry clean \"Ganga sand\" in trenches for cushioning UG cable complete all as specified and directed. (Note: Punned thickness of sand shall be measured for payment purpose) |
| 5 | M&L for sub class \"B\" old size of Brick laid with width equal to its length of birick in trenches for cable protection of LT Cables complete all as specified and directed. |
| 6 | M& L for boring through existing road with trench less method for passing of UG cable all as specified and directed. |
| 7 | Supply and replacement of unserviceable XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional 400 sq mm 3.5 core ,laid in trenches/ducts /encased in GI pipe /fixed to pole including taking out of existing unserviceable cable all as specified and directed. |
| 8 | Supply and replacement of unserviceable XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional 240 sq mm 3.5 core ,laid in trenches/ducts /encased in GI pipe /fixed to pole including taking out of existing unserviceable cable all as specified and directed. |
| 9 | Supply and replacement of unserviceable XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional 185 sq mm 3.5 core ,laid in trenches/ducts /encased in GI pipe /fixed to pole including taking out of existing unserviceable cable all as specified and directed. |
| 10 | Supply and replacement of unserviceable XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional 150 sq mm 3.5 core ,laid in trenches/ducts /encased in GI pipe /fixed to pole including taking out of existing unserviceable cable all as specified and directed. |
| 11 | Supply and replacement of unserviceable XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional 120 sq mm 3.5 core ,laid in trenches/ducts /encased in GI pipe /fixed to pole including taking out of existing unserviceable cable all as specified and directed. |
| 12 | Supply and replacement of unserviceable XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional 95 sq mm 3.5 core ,laid in trenches/ducts /encased in GI pipe /fixed to pole including taking out of existing unserviceable cable all as specified and directed. |
| 13 | Supply and replacement of unserviceable XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional 70 sq mm 3.5 core ,laid in trenches/ducts /encased in GI pipe /fixed to pole including taking out of existing unserviceable cable all as specified and directed. |
| 14 | Supply and replacement of unserviceable XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional 50 sq mm 3.5 core ,laid in trenches/ducts /encased in GI pipe /fixed to pole including taking out of existing unserviceable cable all as specified and directed. |
| 15 | Supply and replacement of unserviceable XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional 35 sq mm 3.5 core ,laid in trenches/ducts /encased in GI pipe /fixed to pole including taking out of existing unserviceable cable all as specified and directed. |
| 16 | Supply and replacement of unserviceable XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional 25 sq mm 4 core ,laid in trenches/ducts /encased in GI pipe /fixed to pole including taking out of existing unserviceable cable all as specified and directed. |
| 17 | Taking down & relaying of serviceableUG cable obtained of any size and discription all as directed by Engineer in Charge. Note:-Excavation , earth work, sand cushionning, bricks etcshall be measured seperatly under respective item of Sch. |
| 18 | S&F in replacement from trenches /fixed on pole / wall GI pipe of 80 mm dialight grade,IS-1239 marked with required size of flat iron clamp complete withbolts, nuts and washers of sizes 80 mm bore complete all as specified and directed. |
| 19 | S&F in replacement from trenches /fixed on pole / wall GI pipe of 50 mm dialight grade,IS-1239 marked with required size of flat iron clamp complete withbolts, nuts and washers of sizes 50 mm bore complete all as specified and directed. |
| 20 | Supply, Joining , commissioning and testing in replacement ofHeat Shrinkable End Termination jointOut doortype and suitable for cable of size 120 to 185 sqmm 3 core complete with all fittings and jointing materials suitable for HT11 KV ( E ) XLPE cable all as specified and directed. |
| 21 | Supply Joining , commissioning and testingin replacement of Heat Shrinkable Straight though joint suitable for cable of size 120 to 185 sqmm 3 core complete with all fittings and jointing materials suitable for HT11 KV ( E ) XLPE cable all as specified and directed. |
| 22 | Supply Joinging , commissioning and testingin replacement of Heat Shrinkable End Termination jointOut doortype and suitable for cable of size 240 to 300 sq mm 3 core complete with all fittings and jointing materials suitable for HT11 KV ( E ) XLPE cable all as specified and directed. |
| 23 | Supply Joinging , commissioning and testingin replacement of Heat Shrinkable Straight through joint suitable for cable of size 240 to 300 sq mm 3 core complete with all fittings and jointing materials suitable for HT11 KV ( E ) XLPE cable all as specified and directed. |
| 24 | M&L for replacement heat shrinkable type straight through joint suitable for cable of size 25 to 50 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 25 | M&L for replacement heat shrinkable type straight through joint suitable for cable of size 70 to 120 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 26 | M&L for replacement heat shrinkable type straight through joint suitable for cable of size 150 to 185 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 27 | M&L for replacement heat shrinkable type straight through joint suitable for cable of size 240 to 300 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 28 | M&L for replacement heat shrinkable type straight through joint suitable for cable of size 400 to 500 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 29 | M&L for replacement heat shrinkable type end joint suitable for cable of size 25 to 50 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 30 | M&L for replacement heat shrinkable type End joint suitable for cable of size 70 to 120 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 31 | M&L for replacement heat shrinkable type End joint suitable for cable of size 150 to 185 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 32 | M&L for replacement heat shrinkable type End joint suitable for cable of size 240 to 300 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 33 | M&L for replacement heat shrinkable type End joint suitable for cable of size 400 to 500 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 34 | M& L for earthing complete with galvanized steel earth plate electrode 60cm x60 cm x6.0 mm thick buried directly in ground (earth pit not less than 2.25 Mtrs deep below ground level) with top edge of the plate not less than 1.50 Mtr below normal ground level connected to galvanized earth lead strip 25x4mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.5 connected to ear thing test point all as specified or indicated including testing on completion including PCC pit in (1:3:6) type C-2 cement concrete .RCC 1:2:4 Mix type B-0, reinforced with 6mm dia MS bars @ 150mm RCC cover slab 40mm thick with two no’s fitting handle, GI pipe 20mm dia light grade with funnel & wire mesh for watering and 40mm dia light grade GI pipe for earth strip 25x4mm protection etc complete all as specified and directed by Engr-in-Charge. (Note:- GI earth strip up to 7.5 mtr shall be includind in quoted unit rate) |
| 35 | M&L forin replacement of Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size complete all as directed by Engineer in Charge. |
| 36 | Supplying and laying in replacement synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m all as directed by Engineer in Charge. |
| 37 | S& Fin replacement insulator pin type porcelain vitreous white brown or green including galvanized MS spindle two GI Washers and one GI Nut 150 mm height 150 mm dia for 11000 volts grade complete all as specified and directed . |
| 38 | Supply, installation, commissioning and testing in replacementpowdercoated factory made panel board outdoor type CPRI approved confirming to IP 64 protaction, of suitable size made of Robust steel sheet construction made from min 2.10 mm steel sheet with countersunk holes at bottom for base mounting brackets and sheet steel gland plates for cable entry, formed gasket arround doors, with provision of Lock inserts, earthing straps, door stay and grouted in ground by using angle iron frame of size 50mm x 50mm x 6mm, PCC (1:2:4) type C-1 with 20mm graded stone aggregate.(Note :- Old unserviceable Panel Board along with its accessories is property of department and deposited in MES store yard 7 AFH.)The panel will be prewired with suitable size PVC insulated copper conductor cable, multistranded housed with the following accessories:- |
| 39 | (a) Aluminium bus bar of capacity 1000 Amp for phase and 500 Amps for neutral. |
| 40 | (b) Incoming MCCB 4 pole 630 Amp 50 KA alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU)– 02 Nos |
| 41 | (c) Outgoing MCCB 4 pole 400 Amp 36KA alongwith Spreader terminals with adjustable thermal settingICS= 100% ICU)– 01 Nos |
| 42 | (d) Outgoing MCCB 4 pole 350 Amp 35KA alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU)– 01 Nos |
| 43 | (e) Outgoing MCCB 4 pole 250 Amp 35KA alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU)– 02 Nos |
| 44 | (f) Outgoing MCCB 4 pole 200 Amp 25 KA alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) – 03 Nos |
| 45 | (f) Outgoing MCCB 4 pole 100 Amp 25 KA alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) – 04 Nos |
| 46 | (g) On load change over switch of capacity 630 Amp– 01 Nos |
| 47 | (h)Digital volt meter 0 to 500 volt with selector switch – 02 No |
| 48 | (f)Digital Amp meter 0 to 400 Amp with CT of suitable ratio and selector switch – 02 No |
| 49 | (g) Phase Indicator Lamp RYB with sheds LED Type - 01 Set of three |
| 50 | (r) Digital timer switch (Astronomical) along with contractor/MCB and suitable accessories. |
| 51 | M&L for replacement of LT panel board outdoor type factory made and tested (CPRI approved) 415 volts 3 phase 4 wire 50 HZ AC supply having busbar chamber 800 Amps Aluminium strip TPN, installed on porcelain insulators, and copper conductor wiring , the panel shall be dust and vermin proof and made up of 3.15 mm CRCA mild steel sheet and 40x40x6 mm thick angle iron frame work , powder coated finish over one coat of red oxide primer out side and in side, front and rear opening type, with aprons for cable entry with double door shutter and locking arrangement, internal wiring with PVC insulated solid copper conductor FRLS cables, IS -694 marked of adequate size but not less than 4 sq mm and suitable to accomodate and including the following acessories:- (Note :- Old unserviceable Panel Board along with its accessories is property of department and submitted to store yard) |
| 52 | (a) INCOMING :- |
| 53 | (i) MCCB 4 Pole 630 Amps 50 KA alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) -02 Nos. |
| 54 | (ii)Volts meter digital type 0-500 Volts complete with salector switch -02 Nos. |
| 55 | (iii) Ampsmeter digital type complete with CT and selector switch -02 Nos. |
| 56 | (b) Change over switch 630 Amps - 01 No. |
| 57 | (c) Out going ;- |
| 58 | (i) MCCB 500 Amps 4 Pole 36 KA alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU)-02 Nos. |
| 59 | (ii) MCCB 250 Amps 4 Pole 36 KA alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) -02 Nos |
| 60 | (iii) Indicating lamps RYB on each out going and incomingfeeders |
| 61 | Note for item no. 38 & 39 : (i)Panel shall be mounted on brick work plate form duly plastered and PCC copping work on top surface , height shall be 0.60 m above the GL and 0.40 M all around the FPB all as per direction of Engr-in-Charge. |
| 62 | (ii) All incoming and out going cables shall be connected with suitable size of cable luggs and cable galands etc. |
| 63 | Disconnecting cable connection of LT panel /Feeder Pillor Box of any size and capacity cleaning thoroughly with vaccum cleaner and CRCand shifting care fullyto new location , making cable connection for incoming and out going cables along with required cable glands and lugs and foundation work at new location all as specified and directed. |
| 64 | S & F in replacement of PVC insulated heavy duty electric weather proof flat twin core cable with aluminium conductor 1100 Volts grade, cross sectional area 6 Sqmm all as specified and directed by Engineer in Charge. |
| 65 | S & F in replacement of PVC insulated heavy duty electric weather proof flat twin core cable with aluminium conductor 1100 Volts grade, cross sectional area 10 Sqmm all as specified and directed by Engineer in Charge. |
| 66 | S & F in replacement of PVC insulated heavy duty electric weather proof flat twin core cable with aluminium conductor 1100 Volts grade, cross sectional area 16 Sqmm all as specified and directed by Engineer in Charge. |
| 67 | S & F in replacement of initiallycharged battery 12 volts, 150 AH, having minimum 36 month guarrentee, including filling with necessary electrolyte solution all as specified & directed by Engineer-in-charge. Note: Guarrentee card shall be submitted along with purchase voucher and serial number of battery shall be recoreded in MB |
| 68 | S & F in replacement on load change over switch, 800 Amps, 4 pole with sheet metal enclosure, panel mounted type with fixing arragement in existing wall angle iron frame 50x50x4mm with welding work and PCC works etc including making electrical connections complete all as specified and directed. |
| 69 | S & F in replacement on load change over switch, 630 Amps, 4 pole with sheet metal enclosure, panel mounted type with fixing arragement in existing wall angle iron frame 50x50x4mm with welding work and PCC works etc including making electrical connections complete all as specified and directed. |
| 70 | S & F in replacement on load change over switch, 400 Amps, 4 pole with sheet metal enclosure, panel mounted type with fixing arragement in existing wall angle iron frame 50x50x4mm with welding work and PCC works etc including making electrical connections complete all as specified and directed. |
| 71 | S & F in replacement on load change over switch, 315 Amps, 4 pole with sheet metal enclosure, panel mounted type with fixing arragement in existing wall angle iron frame 50x50x4mm with welding work and PCC works etc including making electrical connections complete all as specified and directed. |
| 72 | S & F in replacement on load change over switch, 200 Amps, 4 pole with sheet metal enclosure, panel mounted type with fixing arragement in existing wall angle iron frame 50x50x4mm with welding work and PCC works etc including making electrical connections complete all as specified and directed. |
| 73 | M&L for detection of HT/LT fault by using fault locator machine highering from Civil authority complete all as specified and directed by Engr-in -Charge. Note :- In one length of cable from Panel/DB/Transformer to Panel/ Transformer all faults considered as single job complete all as specified and directed. |
| 74 | M&L for repairs to phase sequence controler of any capacity & of any make by removing out the burnt wiring from the panel after taking proper electric shut down & disconnecting the cable, checking it thoroughly for working atauto & manual modeand rectifing them, including overhauling of the contractor, replacement of wornout connector,wiring, nuts & bolts,minor part of contactor etcreassembling , re-installation ,testing & commissioning complete all as directed by Engineer-in- charge. |
| 75 | Supply and fixing in replacement of single phase preventer for phase controler all as specified & directed by Engr-in-charge. |
| 76 | Supply and fixing in replacement of contactor MNX 110 all as specified & directed by Engr-in-charge. |
| 77 | Supply and fixing in replacement of contactor MNX 250 all as specified & directed by Engr-in-charge. |
| 78 | Supply and fixing in replacement of phase sequence relay suitable up to 200 Amp phase sequence corrector all as specified & directed by Engr-in-charge. |
| 79 | M&L for replacement of Air Circuit Breaker (ACB) of capacity 800 Amps 4 pole with breaking capacity 50 kA with micro processor release (Mannual drawout type) complete all as specified and directed by Engr-in-Charge. Note : 1. Necessary addition /altration required to adjust ACB in the existing slot of panel shall be done by the contractor and no extra payment will be made to the contractor.2. Serial Number of ACB shall be recorded in MB |
| 80 | M & L for replacement of MCCB, 4 pole adjustable type 50 KA, 630 Amps.alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) all as specified and directed by Engineer in Charge. Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 81 | M & L for replacement of MCCB, 4 pole adjustable type 36 KA, 500 Amps alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) all as specified and directed by Engineer in Charge..Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 82 | M & L for replacement of MCCB, 4 pole adjustable type 36 KA, 400 Amps alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) all as specified and directed by Engineer in Charge.. Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 83 | M & L for replacement of MCCB, 4 pole adjustable type 36 KA, 350 Amps alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) all as specified and directed by Engineer in Charge.. Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor.. |
| 84 | M & L for replacement of MCCB, 4 pole adjustable type 25 KA, 250 Amps alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) all as specified and directed by Engineer in Charge.. Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 85 | M & L for replacement of MCCB, 4 pole adjustable type 25 KA, 200 Amps alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) all as specified and directed by Engineer in Charge.. Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor.. |
| 86 | M & L for replacement of MCCB, 4 pole adjustable type 25 KA, 160 Amps alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) all as specified and directed by Engineer in Charge..Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 87 | M & L for replacement of MCCB, 4 pole adjustable type 25 KA, 100 Amps alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) all as specified and directed by Engineer in Charge..Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 88 | M & L for replacement of MCCB, 4 pole adjustable type 16 KA, 63 Amps alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) all as specified and directed by Engineer in Charge..Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 89 | M & L for replacement of MCCB, 3 pole adjustable type 36 KA, 250 Amps alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) all as specified and directed by Engineer in Charge.. Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 90 | M & L for replacement of MCCB, 3 pole adjustable type 36 KA, 200 Amps alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) all as specified and directed by Engineer in Charge.. Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor.. |
| 91 | M & L for replacement of MCCB, 3 pole adjustable type 36 KA, 160 Amps alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) all as specified and directed by Engineer in Charge..Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 92 | M & L for replacement of MCCB, 3 pole adjustable type 16 KA, 125 Amps alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) all as specified and directed by Engineer in Charge..Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 93 | Clearing away all grass vegetation ,saplings, shrubs, brush wood undergrowth roots and trees not exceeding 30 CM girth (measured one metre above ground level) and removing rubbish upto a distance of 50 metres outside the periphery of the area under clearancesoft/loose soiland getting out including sprinkling anti vegitation chemical for complete area with spray machinecomplete all as specified & directed. |
| 94 | M&L for in replacement of bus bar chamber, fixed on wall, 8 ways, 250 Amps ,415 V powder coated, water & vermin proof , IP-66 protection duly provided with front openable door incl provision of TPN copper bus bar heat shrinkable colored PVC sleeve coated for phase and neutralcomplete all as specified and directed. (Note:- Old unserviceable enclosure along with its accessories is property of department and submitted to store yard.) |