| 1 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 2 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 3 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm |
| 4 | Wiring for circuit/ submain wiring alongwith earth wire with thefollowing sizes of FRLS PVC insulated copper conductor, singlecore cable in surface/ recessed medium class PVC conduit asrequired.2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 5 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings). |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 7 | Supply & Fixing following modular switch/socket on the existing modular plate & switch box i/c connections but excluding modular plate etc.as reqd. (a)5/6 Amp.Switch |
| 8 | (b)15/16 Amp.Switch |
| 9 | (c)3 pin 5/6 Amp.Socket Outlet |
| 10 | (d)6 pin 15/16 Amp.Socket Outlet |
| 11 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required(a)4 Module (125mmX75mm) |
| 12 | (b ) 6 Module (200mmX75mm) |
| 13 | (c) 8 Module (125mmX125mm) |
| 14 | (d)12 Module (200mmX150mm) |
| 15 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator.6 way, Double door |
| 16 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 17 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 18 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps |
| 19 | Supply, Installation, Testing and Commissioning ofceiling fan with BrushLessDirectCurrent(BLDC)Motor,classofinsulation: B,3nos.metal ( Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit,safety rope, copper winding, steel/Al body Power Factor not less than 0.9,Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS :374-2019), THD (Total Harmonic Distortion) less than 10%,suitable foroperation withregulator for speed control and all remaining accessoriesincluding safety pin, nut bolts, washers, temperature rise=75 degree C(max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50Hz, single phase AC Ceiling Fan compliant to IS 374:2019fan Supply,earthing etc. complete as req 1200mm,service value≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min(Minimum) |
| 20 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 21 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Upto 35 sq. mm |
| 22 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 23 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 24 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. Group C |
| 25 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C |
| 26 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 32 mm |
| 27 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*10 sqmm |
| 28 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-4C*25 sqmm |
| 29 | P/FHot press sheet mouldedcompound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof polebox of innerdimension 200x160x98mm (NS) complete with suitable arrangement for fixing of 2 nosof 6 to 32 amp single pole MCB & 63 Amp. Doublepole isolator (MCB/Isolator excluded) withneutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plateof suitable size with danger monogram property printed on the coveretc asreqd. as reqd. |
| 30 | Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4- 5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP66,IK-10, CRI >80 , under voltage and over voltage protection, EMIEMC as per CISPR -15 , lenses for beam angle 30 deg-120deg as per the application and the project requirement deg., suitable tilt able fitting, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching)<5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connectionswith 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy 105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shallbe submitted. Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).100 watt |
| 31 | LED Batten light (System lumen efficacy≥120 <135 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirementwith Driver efficiency >85%, Operating voltage AC140-270 Volt,freq 50/60 hz, Operating temp range 15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20,CRI>80, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), ofminimum 50000BurningHourswith,70%ofinitial Lumenmaintained tilllife ends,CCT3000°K/ 4000°K / 5700°K/6000°K /6500°K(AsperANSIBin),SDCM(Standard Deviation Color Matching) <3,Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BISstandardandtrade markcertificate(T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own inhouseNABLlabsetupforalltestingfacilitiesforLEDfixtures.completeinallrespecti/cconnectionswith1.5sqmmFRLS,PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy≥120 <135lm/Watt output . LM79 & LM80 Test reportfromNABLlab foralltestingrequiredforLED fixtures as per BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermalmanagement:heatsinkofaluminiumhousing such that LED junction temperature shall not rise above 90°C). Powdercoated diecast/Extrudedaluminium Body(Thickness ≥ 1.20 mm) 18- 22 watt |
| 32 | Lifting the existing submersible pump set with its all accessories from well and Lowering the same along with all accessories for the depth upto 50 meter complete as reqd. |
| 33 | Rewinding of single / three phase A.C.motors of vertical type multi stage submersible pump set of following ratings:-(a)Single phase 1/1.5 HP |
| 34 | Repairing of the Pumping unit of 1/1.5/3 HP vertical type , multistage , submersible pump set by replacement of following accessories /parts etc. complete as reqd.(a)Gun Metal Bush / Bearing. |
| 35 | (b)Pump Shaft. |
| 36 | (c)Impeller |
| 37 | Supply , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% ofthe rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM)warranty both compressor andPrinted Circuit Board (PCB).Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operateup to 50 0C (out door ambient temperature). |
| 38 | S/I/T/C of stand for split AC |
| 39 | S/I/T/C of copper pipe for split AC |
| 40 | S/I/T/C of drain pipe |
| 41 | S/I/T/C of 4 KVA Voltage Stabilizer having input voltage 150V-270V and output voltage 195-245V |
| 42 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.250Amp, 36 KA, FPMCCB |
| 43 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.100Amp, 30 KA, FPMCCB |
| 44 | Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,metal enclosed plug top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. asrequired. |
| 45 | Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) ON LINE Uninterrupted Power Supply (UPS) system suitable for Single Phase input, Single Phase output AC Supply. The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up(Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc.The UPSsystems shall be Microprocessor based DigitalControl, using Insulated Gate Bipolar Transistor (IGBT)\"s both for the rectifier & inverter with PWM (PulseWidth Modulation) Technology. The quality ofdesign,manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >95% at 100% non-linear loads.Current total harmonic distortion (THD)/ total demand distortion (TDD) on th input grid shall be < 5% at 100 %load. (The required LC filters shall be included in UPS cost), extreme power factor kit to be include to limit the input pf to 0.99 and output power factor shall be unity (i.e.kw rating of the UPS shall be kva rating x1)however UPS shall be suitable to take load at0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC single phase 160-270V 50 Hz and delivering output AC supply true sine wave single phase 220/230/240 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins and 150% for 1 minute.Operating temperature 0 to 40 deg C, Relative humidity 0-95% noncondensing, noise level less than 60db at 1 meter distance, Protection for Under voltage, over voltage, abnormal output voltage, battery over charging,output over current, short circuit, battery deep discharge , 10 KV surge.Display for watt/VA,Amp and Voltage power parameters etc. UPS shall comply with low voltage electromagnetic compatibility (EMC) achieved asper EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI) type UPS (as per standard IEC 62040-1, 2&3.TheUPSshould be with IGBT Based Inverter Technology, Communication RS232/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge.Required battery racks,DC breaker suitable rating and interconnecting copper conductor cable of suitable size and connectors and all required accoseries are inclusive in the cost.The UPS should have QR code which should contain drawing test report OEM manual, Geo-Tag of manufacturing location etc.3KVA |
| 46 | SITC of 4MP varifocal lens Bullet IP Camera with following specifications:-Image Sensor: 1/3 4MP CMOSMinimum Illumination: 0.05 lux color, 0 lux with IR or better **Shutter Speed:1/3 – 1/100,000 sFrame Rate: 20 fps or better **Lens: 3.6 to 10mm Varifocal lensVideo Compression: H.265 or better **S/N Ratio: >45dBResolution: (2650x1440) or better **Protocol: should comply to IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNS, IEEE802.1XIR Range: Minimum:30mOperating Temperature: -20 to 55 deg CentWeatherproof Standard: IP66 or better **Safety standard: UL |
| 47 | SITC of 4MP varifocal lens Dome IP Camera with following specifications:-Image Sensor: 1/3 4MP CMOSMinimum Illumination: 0.05 lux color, 0 lux with IR or better **Shutter Speed:1/3 – 1/100,000 sFrame Rate: 20 fps or better **Lens: 3.6 to 10mm Varifocal lensVideo Compression: H.265 or better **S/N Ratio: >45dBResolution: (2650x1440) or better **Protocol: should comply to IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNS, IEEE802.1XIR Range: Minimum 30mOperating Temperature: -20 to 50 deg CentWeatherproof Standard:IP66 or better **Safety standard: UL |
| 48 | SITC of 08 channel NVR with the following specifications:Camera resolution:upto8MPInterface: 1 HDMI, 1VGA minimumCompression :H.265or betterNetwork Throughput :80Mbps or better**USB Port: 2 USB port (USB2.0)minimumHard disk interface: 1 SATA port suitable for 6TB eachProtocol: IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNSOperating temp: -10 to 55 deg CentSafety standard: UL |
| 49 | SITC of 4 TB surveillance HDD |
| 50 | SITC of 8 port Giga PoE switch, 8(PoE 10/100) + 2(10/100) port long distance switch |
| 51 | SITC of following rack capacity with glass front door, steel rear door, power supply, MCB, cable manager, drawer shelves and wiring channels to accommodate CCTV systems equipment and complete with accessories as reqd.8 U |
| 52 | S/I/T/C offull HD LED Monitor,32INCHES complying with the following specifications:Resolution : Full HD : 1920 x 1080 or betterBacklight : LEDBrightness : 300 NITS min.Contrast : 1200 : 1 or better Power supply : 230v + / - 10%, 50 Hz at sitewith connections andalong with all accessories etc.complete as required. |
| 53 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable |
| 54 | 2 run of cable |
| 55 | SITC of wall mounted fan 400mm sweep rated voltage 220-230 AC rated frequency 50HZ speed 1280-1350 RPM with desired color |
| 56 | SITCIP65 box(without PoE switches)of dimention 310mmX160mmX140 mm onpole or wall with suitable arrangement for support/installation of 8 port Giga PoE switch and 1 nos. 15/16 amp modular switch socket set |
| 57 | Providing and fixing of 4.5 KG CO2 type fire extinguisher squeeze grip type, trolly wheelas well mounted type complete in all respect with ISI mark i/c fixing arrangement etc as required. |
| 58 | Providing and fixing ABC (Aluminium Phosphate) power type fire extinguisher of 6kgs capacity complete in all respect with isi mark i/c fixing arrangement etc as required. |
| 59 | Supplying AND Installation of Reverse Osmosis (RO) water purifier of capacity 50 ltr/hr complete as required. |
| 60 | Supplying and fixing of full stainless steel body self-contained drinking water cooler with cooling capacity 150ltr per hr, storage capacity 150ltr and suitable for 230V supply as required. |