| 1 | PART A - ELECTRICAL (Item No:1 to 31) Supplying, Testing and Successful Commissioning of4 Core x 50.0 sq. mm PVC insulated and PVC sheathed / XLPE aluminium armoured conductor cable of 1.1 KV grade and fixing on the wall surface, clamped with suitable size GI Clamps, hardwares etc., as required. Make: Please refer Special Electrical Conditions under Tender Document File. |
| 2 | Supplying, Installation, Testing & Successful Commissioning of 16 PVC Modular Box along with Modular Base, Cover Plate etc., in recess / wall using suitable hardwares etc., as per directions of Engineer In-Charge and consisting of following Modular items a) 5/6 Amp Switch - 2 Nos;b) 3 Pin 5/6 Amp Socket Outlet - 2 Nos; c) 15/16 Amp Switch - 2 Nos; d) 6 pin 15/16 Amp Socket Outlet - 2 Nos and e) 20 Amps, 2 Pole, \"C\" Curve, 10kA, 230V Mini MCB - 1 No. Internal wiring for 5 Amps Switch & Socket with 2.5 sq.mm FRLS Multistrand, Single Core Copper Wire; for 15 Amps Switch & Socket with 4.0 sq.mm FRLS/HFFR Multistrand, Single Core Copper Wire. Red and Black Colour for Phase and Neutral and Green Colour 4.0 sq.mm FRLS Multistrand, Single Core Copper Wire for Earthing Loop and terminate all the wires using suitable size Copper Lugs etc., as required. Make: Please refer Special Electrical Conditions under Tender Document File. |
| 3 | Supplying and fixing 63, 415V, TPN Industrial Type Metal Clad Plug & Socket outlet, with 4 pole and earth (5 Pin), Metal Enclosed 5 Pin Plug Top along with 63A \"C\" Curve, FP MCB, in sheet steel enclosure, on surface or in recess or in floor with suitable height stand made of Painted MS Angle, with chained metal cover for the socket outlet and complete with connections, testing and commissioing etc. as required. Make: Please refer Special Electrical Conditions under Tender Document File. |
| 4 | Supply, Installation, Testing and Commissioning of LT Double Door Indoor Panel Box of Size 1600mm (H) x 1400mm (W)x 300 (D) made out of 1.6mm thick CRCA sheet steel enclosure, powder coated with siemens gray colour and consisting of 4 x 250 Amps Capacity, Copper Bus-Bar strips with proper colour coding and insulation, covering the Bus-Bar with electrical grade sheet from inside. At the bottom, 1 x 250A, 50KA Range 4P MCCB has to provided. The output from the MCCB to be connected to the Bus-Bars with same size & range Copper Bus-Bar links. From the Bus-Bar, to tap input for the below listed MCCB & MCBs with rated copper wires. All plate cutting for fixing glands, entry and exit of UG cables are to be made available for minimum of 4 sets of UG Cables at the bottom. The Panel Box should have provision for mounting on the ground with total stand height of 1.5 Feet, doors on front side with locking arrangements, cable alley, RYB LED Indicating Lamps for Input and Output, Aluminium Earth Bus-Bar extended on either side of the box, water proof vents ( 6 Inch x 6 Inch) on both the sides covered with wire mesh from inside to avoid entry of any insects etc., a) 250 Amps capacity Copper Bus Bar insulated with fire proof tape, mounted on Bus Bar Insulators. - 04 Nos; b) 250A, 36KA, 4 Pole MCCB - 01 No; c) 125A, 36KA, 4 Pole MCCB - 02 Nos; d) 63A, 4 Pole RCCB 440V AC with 30mA sensitivity - 08 Nos; e) 32 A, 10kA, \"C\" Curve 2 Pole MCB - 02 Nos; f) 32 A, 10kA, \"C\" Curve 4 Pole MCB - 04 Nos; g) RYB LED Phase Indication Lamps with Fuse Unit for Input and Output - 2 Sets; h) Multifunctional 3 Phase, 4 Wire Electronic Trivector Energy Meter with Class 0.1 Accuracy - 01 No; i) Aluminium Earth Bus-Bar 50mm x 5mm - 01 No.The LT Panel is also included for Supply, Installation, Successfull Commissioning and Testing of 1 number of suitable range Multifunctional 3 Phase, 4 Wire Electronic Trivector Energy Meter with Class 0.1 accuracy, required range of CTs, to read and record upto 250 Amps. Important:All incoming / outgoing armoured cables / Sub-Main Circuits shall be terminated with suitable size copper / aluminiumlugs (for copper cables / wires, coppler lugs and for aluminium cables / wires, aluminium lugs). During connections, if any Incoming / Outgoing cables is / are need to be extended, part of the work (Cable/ Wires for extension of connection will be provided by CSIR-CFTRI). Make: Please refer Special Electrical Conditions under Tender Document File. Note: Labelling to be done for Input & Output Control in Paint / Acrylic Sticker.Panel Design: As per Engineer In-Charge. |
| 5 | Supplying, Installation, Testing & Successful Commissioning of Cassette Type Heavy Duty Exhaust Fan to work in 230V AC 50Hz Suppy, ready to use. The said item will be mounted on 2x2 Panel with required hardwares as requried. Make: Please refer Special Electrical Conditions under Tender Document File. |
| 6 | Labour charges for digging 8 feet of depth below ground level, including hard soil, rocks, cement surface etc.,if any encountered, fixing the Item No:24, refilling of soil etc., as required. (along with charcoal / coke and salt from S.No:24 as required, already estimated under S.No.24). |
| 7 | Supply, Installation, Testing and Successful Commissioning of 1.5 Tr Nominal Cooling Capacity (Tonnage); 5 Star Rating; 5 or above ISEER; Inverter Air Conditioner Technology; Cooling Capacity: Approximately 18,000 BTU/hour (5275 Watts); Compressor: inverter or non- inverter, with rotary or BLDC(Brushless DC) options; Refrigerant: Commonly uses R32 refrigerant; Condenser and Evaporator: Typically made of copper; Power Supply: Single-phase, 230V, 50Hz AC; Voltage Tolerance: Typically ±10% of the rated voltage; Indoor Unit Noise Level: Ranges from 34dB to 51dB depending on fan speed; Outdoor Unit NoiseLevel: Typically around 54dB; Moisture Removal: About 1.2 to 1.44 Liters per hour; Airflow Volume (High/Medium/Low): Can vary, but examples include 760/644/611/493 CFM (Wet CFM); Other Features: Auto Restart, Sleep Mode, Energy Saver Mode, Wide Voltage Range, Copper Condenser: 100% copper condenser for efficient heat transfer, Stabilizer Free Operation and Anti-Fungal Filter and consisting of 1 each of Indoor Unit, Outdoor Unit, upto 20 Metre Copper Tube, Rated Inter Connecting FRLS Copper Wires inside steel reinforced hose pipe (upto 20 m), LCD Remote with Battery, rated Stablizer, MS Painted Stand for Outdoor unit and User Manual. Make: Please refer Special Electrical Conditions under Tender Document File. |
| 8 | Group A Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Make: Please refer Special Electrical Conditions under Tender Document File. |
| 9 | Group C Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Make for all: Same as Item No: 8 |
| 10 | Wiring for circuit/ submain wiring along with earth wire with 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire of FRLS/HFFR PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required. Make for all: Same as Item No: 8. Note: All start, loop & end point of the wires are to be terminated with \"Cu\" Lugs of suitable type and size and individual pipes for wiring. |
| 11 | Wiring for circuit/ submain wiring along with earth wire with 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire of FRLS/HFFR PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required. Make for all: Same as Item No: 8. Note: All start, loop & end point of the wires are to be terminated with \"Cu\" Lugs of suitable type and size and individual pipes for wiring. |
| 12 | Wiring for circuit / submain wiring alongwith earth wire with 2 X 4 sq. mm + 1 X 4 sq. mm earth wire of FRLS/HFFR PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required. Make for all: Same as Item No: 8. Note: All start, loop & end point of the wires are to be terminated with \"Cu\" Lugs of suitable type and size and individual pipes for wiring. |
| 13 | Wiring for circuit / submain wiring alongwith earth wire with 2 X 6 sq. mm + 1 X 6 sq. mm earth wire earth wire of FRLS/HFFR PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required. Make for all: Same as Item No: 8. Note: All start, loop & end point of the wires are to be terminated with \"Cu\" Lugs of suitable type and size and individual pipes for wiring. |
| 14 | Wiring for circuit / submain wiring alongwith earth wire with 4 X 6 sq. mm + 2 X 6 sq. mm earth wire earth wire of FRLS/HFFR PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required. Make for all: Same as Item No: 8. Note: All start, loop & end point of the wires are to be terminated with \"Cu\" Lugs of suitable type and size and individual pipes for wiring. |
| 15 | Wiring for circuit / submain wiring alongwith earth wire with 4 X 10 sq. mm + 2 X 6 sq. mm earth wire earth wire of FRLS/HFFR PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required. Make for all: Same as Item No: 8. Note: All start, loop & end point of the wires are to be terminated with \"Cu\" Lugs of suitable type and size and individual pipes for wiring. |
| 16 | Wiring for circuit / submain wiring alongwith earth wire with 4 X 16 sq. mm + 2 X 6 sq. mm earth wire earth wire of FRLS/HFFR PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required. Make for all: Same as Item No: 8. Note: All start, loop & end point of the wires are to be terminated with \"Cu\" Lugs of suitable type and size and individual pipes for wiring. |
| 17 | Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \"C\" curve including connections, painting etc. as required. |
| 18 | Supplying & Fixing DP sheet steel enclosure on surface / recess along with 25/32 A 240 V \"C\" curve DP MCB complete with connections, testing and commissioning etc. as required. Make: Please refer Special ElectricalConditions under Tender Document File. |
| 19 | Supplying and installaton 300 mm width X 50 mm depth X 1.6 mm thickness perforated painted with powder coating M.S. cabletrays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 20 | Supplying and installaton 300 mm width X 50 mm depth X 1.6 mm thickness perforated painted with powder coating M.S. cabletrays bends with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 21 | Supplying and installaton 300 mm width X 50 mm depth X 1.6 mm thickness perforated painted with powder coating M.S. cabletrays Tees with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 22 | Supplying and installaton 300 mm width X 50 mm depth X 1.6 mm thickness perforated painted with powder coating M.S. cabletrays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 23 | Supplying and installaton 300 mm width X 50 mm depth X 1.6 mm thickness perforated painted with powder coating M.S. cabletrays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 24 | Earthing with copper earth plate 600 mm x 600 mm x 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal / coke and salt as required. Note: Masonry enclosure size is 1.5 Feet x 1.5 Feet x 1.5 Feet.As per IS 3043, charcoal/ coke and salt should be refilled with 50 Kg each per earthpit. The connected copper flats have to be brazed and only SS nut, bolts and washers to be used. |
| 25 | Providing and laying earth connection from earth electrode with 4.00mm dia copper wire in 15mm G.I. pipefrom earth electrode including connection with copper thimble excavation and refilling as required. |
| 26 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface / recessed conduit / submain wiring / cable as required. |
| 27 | Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required. |
| 28 | Supplying, Installation, Testing & Commissioning of 36 Watt Panel Light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy ≥105 <120 lm/Watt output LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 29 | Supplying, Installation, Testing & Commissioning of LED surface mounted Batten 40 Watt light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 Deg C to 40 Deg C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P.F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm). LED Batten light (System lumen efficacy >135 lm/Watt). |
| 30 | Supplying, Installation, Testing & Commissioning of 100 Watt Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 Deg C to 50 Deg C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy >135 lm/Watt) |
| 31 | Supplying and making end termination with brass compression gland and aluminium lugs for 4 X 50 sq. mm (35mm) size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. Note: Each means all 4 terminals of one end. |
| 32 | PART B - CIVIL (Item No:32 to 56)Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead. For thickness of tiles 10 mm to 25 mm |
| 33 | Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - chargeNominal concrete 1:3:6 or richer mix (including equivalent design mix) |
| 34 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil. |
| 35 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 M sand derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 36 | Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers,abutments, pillars, posts, struts, buttresses, string or lacing courses,parapets, coping, bed blocks, anchor blocks, plain window sills, fillets,sunken floor etc., up to floor five level, excludingthe cost of centering,shuttering and finishing: 1:3:6 (1 cement : 3 M sand : 6 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 37 | Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only.Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. Double charge vitrified tile polished finish of size. Size of Tile 800 x 800 mm. Make: SOMANY/ RAK/ NITCO/ Naveen |
| 38 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes |
| 39 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately): For fixed portion Powder coated aluminium (minimum thickness of powder coating 50 micron) Make: JINDAL or its equivalent |
| 40 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) Powder coated aluminium (minimum thickness of powder coating 50 micron) Make: JINDAL or its equivalent |
| 41 | Providing and fixing 9mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade I type II, in panelling fixed in aluminium doors, windows shutters and partition frames with C.P brass/ stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on both sides. Make: NOVAPANor its equivalent |
| 42 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 5 mm thickness (weight not less than 12.50 kg/sqm) (Plain /Pin Headed / acid etche glass)Make: SAINT GOBIAN OR MODI |
| 43 | Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete. Make: Godrej or its equivalent |
| 44 | Providing and fixing aluminium handles with SS screws etc. complete as per direction of Engineer-in-charge. Powder coated minimum thickness 50 micron aluminium. Size 100mm x 10mm length |
| 45 | Filling the gap in between aluminium frame & adjacent RCC/ Brick/ Stone work by providing weather silicon sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete.Upto 5mm depth and 5 mm width |
| 46 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade: Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture. Make: Asian - Apcolite Gloss Enamel or Nerolac – Synthetic Enamel or Dulux - Gloss Enamel |
| 47 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:Stainless Steel AISI-304(18/8) Wash basin 530x345 mm with single 15 mm C.P. brass pillar tap |
| 48 | Cutting holes up to 30x30 cm in walls for connection including making good the same:With common burnt clay F.P.S. (non modular) bricks / blocks |
| 49 | Providing, laying and jointing SWR pipes of 6 kgf/ sq.cm pressure capacity including testing of joints etc., complete. 75 mm diameter. Make: ASHIRWAD/ FINOLEX |
| 50 | Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 Msand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 M sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 M sand : 10 graded stone aggregate 40mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 M sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design:With common burnt clay F.P.S.(non modular) bricks of class designation 5.00 |
| 51 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931: 15 mm nominal bore |
| 52 | Providing and fixing tiled False Ceiling of approved materials of size 600x600 mm in true horizontal level suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanized @ 170 gsm/sqm) consisting of main \"T\" runner with suitably spaced joints to get required length and of size 24x32mm made from 0.30mm thick (minimum) sheet spaced at 1200mm center to center and cross \"T\" of size 24x25mm made of 0.30mm thick (minimum) sheet, 1200mm long spaced between main \"T\"at 600mm center to centerto form a grid of 1200x600 mm and secondary cross \"T\" of length 600mm and size 24x25mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600mm panel to form grids of 600x600mm and wall angle of size 24x24x0.3mm and laying false ceiling tiles of approved texture in the grid including, required, cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main \"T\" runners to be suspended from ceiling using GI slotted cleats of size 27x37x25x1.6 mm fixed to ceiling with 12.5 mm dia and 50mm long dash fasteners, 4mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200mm center to center along main T, bottom exposed width of 24mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications drawings and as directed by Engineer-in-Charge. 9 mm thick square edge PVC Laminated Gypsum Tile of size 600x600 mm, made of Gypsum plasterboard, manufactured from natural gypsum as per IS 2095 part I and laminated with white 0.16 mm thick fire retardant PVC film on the face side and 12 micron metalized polyester on the back side with all edges sealed with the face side PVC film which goes around and wraps the edges and is bonded to the edges and the back side metalized polyester film so as to make the tile a completely sealed unit. The tiles should have Thermal Conductivity k = 0.24 w/m k, Colour white, Fire performance Class 0/Class1 (BS 476 Part 6&7) in module size of 600 x 600 x 9 mm. Make: ARMGYP SAND (ARMSTRONG) |
| 53 | Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead for all lead upto 10 kms including all lifts involved. |
| 54 | Providing and fixing 220mm H-Type long tubular / square (25mm to 40mm dia) SS handle (Set of 2 nos), on glass / wood door shutter including necessary SS screws, bushes etc as instructed by engineer incharge |
| 55 | Supply, Installation and Successful Commissioning of Pre-Fabricated \"A\" Type 7 Feet Heavy Duty Aluminium Ladder with Cross Arm Support and Broader Steps with locking arrangement and , Flourescent Painted on the both sides of the Ladder, for Street Light Maintenance made out of any ISI make material. |
| 56 | Supply, Installation and Successful Commissioning of Pre-Fabricated \"A\" Type 10 Feet Heavy Duty Aluminium Ladder with Cross Arm Support and Broader Steps with locking arrangement and , Flourescent Painted on the both sides of the Ladder, for Street Light Maintenance made out of any ISI make material. |