| Sl. No. | Item Description |
| 1 | BUILDING INCLUDING INTERNAL SERVICES |
| 2 | SUB HEAD - I : EARTH WORK & EXCAVATION |
| 3 | Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 Sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. |
| 4 | All Kinds of soil |
| 5 | Extra for every additional lift of 1.5 m or part thereof in excavation I banking excavated or stacked materials. |
| 6 | All kinds of soil ( -1.5 to -3m) |
| 7 | Extra for every additional lift of 1.5 m or part thereof in excavation I banking excavated or stacked materials. |
| 8 | All kinds of soil (-3mto -4.5 m) |
| 9 | Extra for every additional lift of 1.5 m or part thereof in excavation I banking excavated or stacked materials. |
| 10 | All kinds of soil ( -4.5 to -6.0m) |
| 11 | Extra for every additional lift of 1.5 m or part thereof in excavation I banking excavated or stacked materials. |
| 12 | All kinds of soil ( -6.0 to -7.5m) |
| 13 | Extra for every additional lift of 1.5 m or part thereof in excavation I banking excavated or stacked materials. |
| 14 | All kinds of soil ( -7.5 to -9.0m) |
| 15 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc.in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 and for all lift. |
| 16 | Excavating, supplying, stacking and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in foundation trenches, plinth, sides of foundation etc. complete for all lift. |
| 17 | Extra for Carriage of Earth By Mechanical Transport for following additional distance |
| 18 | Earth |
| 19 | Lead Upto 1km |
| 20 | Lead Upto 2km |
| 21 | Lead Upto 3km |
| 22 | Supplying and filling in plinth with sand (crushed sand ) under floors, including watering, ramming, consolidating and dressing complete. |
| 23 | SUB HEAD - II : ANTI-TERMITE TREATMENT : |
| 24 | Supplying chemical emulsion in sealed containers including delivery as specified. |
| 25 | Chlorpyriphos/ Lindane emulsifiable concentrate of 20% |
| 26 | Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) : |
| 27 | Along the external wall below concrete or masonry apron using chemical emulsion @ 2.25 litres per linear metre including drilling and plugging holes etc.: |
| 28 | With Chlorpyriphos/ Lindane E. C. 20% with 1% concentration |
| 29 | Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) : |
| 30 | Treatment of soil under existing floors using chemical emulsion@ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement: 2 M- M.sand) to match the existing floor |
| 31 | With Chlorpyriphos/Lindane E. C. 20% with 1%concentration |
| 32 | SUB HEAD - III : PLAIN & REINFORCED CEMENT CONCRETE |
| 33 | CONCRETE WORK |
| 34 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work upto plinth level. |
| 35 | 1:4:8 (1 Cement : 4 M- M.sand : 8 graded stone aggregate 40 mm nominal size) |
| 36 | 1:3:6 (1 cement :3M- M.sand :6 graded stone aggregate 40 mm nominal size) |
| 37 | 1:2:4 (1 cement : 2M. sand (zone-III) : 4 graded stoneaggregate 20 mm nominal size) M-15 – Grade concrete |
| 38 | Providing and laying damp-proof course 50mm thick with cement concrete 1:2:4 (1 cement : 2M.sand (zone-III) derived from natural sources : 4 graded stone aggregate 20mm nominal size derived from natural sources). |
| 39 | Extra for providing and mixing water proofing material in cement concrete work in doses by weight of cement as permanufacturer\"s specification. |
| 40 | Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 M.sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine M.sand, including necessary excavation, levelling & dressing & finishing the top smooth. |
| 41 | R.C.C WORK |
| 42 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 43 | Foundations, footings, bases of columns etc. for mass concrete. |
| 44 | Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 45 | Suspended floors, roofs, landings, balconies and access platform. |
| 46 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 47 | Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 48 | Stairs, (excluding landings) except spiral - staircases. |
| 49 | Edges of slabs and breaks in floors and walls |
| 50 | under 20 cm wide |
| 51 | Weather shade, Chajjas, corbels etc., including edges |
| 52 | Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 Metre or part thereof (Plan area to be measured). |
| 53 | Suspended floors, roofs, landing, beams and balconies (Plan area to be measured) |
| 54 | ITEM:Paschal Formwork |
| 55 | Supplying, Laying & Deshuttering of Paschal/ Equvalent type formwork for walls . As approved by Engineer-in-charge. |
| 56 | Steel Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.Upto plinth level |
| 57 | Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 58 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. |
| 59 | Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 60 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 61 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work;usingM- aggregate and fine aggregate derived from natural sources,Portland Pozzolana / Ordinary Portland /Portland Slagcement, admixtures in recommended proportions as per IS:9103 to accelerate /retard setting of concrete, to improve durability andworkability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge;for the following grades of concrete. |
| 62 | Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 10% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement.. (In fine aggregate M.sandis considered) |
| 63 | All work upto plinth level |
| 64 | Concrete of M35 grade with minimum cement content of 370 kg /cum |
| 65 | All work from plinth level upto floor V level. |
| 66 | Concrete of M35 grade with minimum cement content of 370 kg /cum |
| 67 | Providing and laying in position M-35 grade self compacting concrete for reinforced cement concrete work, using cement in required proportion and ground granulated blast furnace slag to the order of 25 to 50 % by mass of cement ,M- aggregate of maximum size 20 mm ,and having M- sand content more than 38% ,using high range water reducing (HRWR) admixture and viscosity modifying agent in appropriate dosage as recommended (approx. in the range of 0.2 to 2.0%) manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads , having continous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work, including pumping of concrete from transit mixer to site of laying , excluding the cost of centering ,shuttering finishing and reinforcement ,including cost of admixtures in recommended proportions as per IS:9103 to accelerrate / retard setting of concrete , improve workability without impairing strength and durability. The average slump to be maintained shall be 600 +/- 50mm, w/c ratio 0.32 and free water shall not exceed 160 kg/cum ,etccomplete asmper direction of Engineer-in-charge. |
| 68 | Note:- Cement content considered in this item is @350 kg/cum and GGBS 150 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately. |
| 69 | Self compacting Reinforced Cement Concrete -M-35 |
| 70 | Add or Deductfor cement used in M-35 Grade Self-compacting Cementas specified in mix design. |
| 71 | Constructing cast-in situ RCC diaphragm wall by providing and laying machine batched, machine mixed, self compacting, ready mix reinforced cement concrete, tramie controlled, of M 30 grade using minimum 400 kg cement per cum of concrete including providing and mixing required admixtures in recommended proportions as per IS : 9103, as approved by the Engineer-in-charge, for achieving 150- 200mm slump, for diaphragm wall having thickness as per approved structural design not exceeding 600 mm, in pannels of required depth and lengths as per approved drawing, including constructing necessary guide walls as required and as specified including boring in all kinds of soils and rocks, including working in or under water and / or liquid mud, in foul conditions and pumping or bailing out of water and removing slush, including disposal of earth/ rock / slush etc. for all leads and all lifts, including preparing, providing and re-circulating bentonite slurry in the trench as and when required for all depths, including agitating bentonite slurry during trenching etc., providing and fixing stop ends or form tubes, upto the required depth of diaphragm wall including extracting the same after casting, including chipping off the bentonite adulterated concrete or unsound concrete up to the cut off level for obtaining the sound concrete, dressing undulations on the exposed face of diaphragm wall after excavation by chipping / chiseling etc. including filling the depression/ cavities with sound concrete etc. complete and as directed by the Engineer-incharge, including providing recess for bearing plates and fixing insert boxes for inclined rock anchors etc. complete as per the specifications and approved design and as directed by the Engineer-in-charge, but excluding the cost of reinforcement and inserts. |
| 72 | (rates include cost of all inputs of labour, material and T & P, cost of handling, lifting & placing in position the reinforcement cage in the trench, including the additional cost of welding the reinforcement bars etc. involved in the work and all other incidental expenditure for completing the work as directed by the Engineer-in-charge), However, the actual area of the diaphragm wall, correct to two places of decimal, from design bottom level to the design cut off level (including portion anchored in the rock upto the design bottom level) only shall be measured for payment |
| 73 | Excess/less cement used for design mix including the extra cement required for under water concreting is payable / recoverable separately. |
| 74 | Add or deduct for using extra cement in the items of design mixconcrete over and above the specified cement content therein. |
| 75 | Extra for R.C.C./ B.M.C/ R.M.C. work above floor V level for each fourfloors or part thereof. |
| 76 | PILE WORKS |
| 77 | Providing, driving with hydraulic piling rigs with power units and installing driven cast-in-situ reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap, to carry safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of shoe and the length of pile to be embedded in the pile cap etc. all complete. (Length of pile for payment shall be measured from top of shoe to the bottom of pile cap) : |
| 78 | 500 mm dia piles ( M-25 grade of concrete with minimum cemengt content of 330 kg/cum) |
| 79 | Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. |
| 80 | Note: 1. Initial and Routine Load Test shall not be carried out by Dynamic method of testing. |
| 81 | Note: 2. Testing agency shall submit the design of loading platform for the approval of Engineer-in-charge |
| 82 | Group of two or more piles upto 50 tonne Safe capacity |
| 83 | Initial test (Test Load 2.5 times the Safe capacity) |
| 84 | Routine test (Test Load 1.5 times the Safe capacity) |
| 85 | Providing & Fixing of Expansion Joint system related with the Floor to Floor/ Floor to Wall Expansion Joint Cover for 100 to 150 mm Expansion Joints Aluminium Covers Profiles, having a Hard Wearing, Maintenance Free, long Lasting design. The surface of the Exp. Joint Covers should have Serrated Surface for Skid Resistance . The exposed surface minimum Aluminum.The design of the Exp. Joint Cover System should be such that it should avoid any accumulation of dirt. The Exp. Joint Cover should have an Articulated Telescope Design so as to accommodate the movements in 3 directions. The system should be in alloy 6063 T66 in Mill finish and the total exposed surface of the profile should not be more than The installation Height should be 35 mm. The system can be used for standard Rolling loads of private Cars or Cart wheel loads. The system should have ASTM1399 E certification. All test certificates are mandatory to submitted. The extrusion should be as ASTM 6063 T66 standards. The System shall be such that it will be flushed with the finish The System should be ASTM-E 1399. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by the Engineer-in- Charge. |
| 86 | Floor to Floor -75mm Gap Size |
| 87 | Providing & Fixing of the Exp. Covers, Model – WJC SERIES WALL to WALL / CORNER Model, Expansion Joints Aluminum Covers Profile. The design of the Joint Cover System should be such that the system should snap onto a 50mm wide, hook shaped aluminum clip. The system should have gasket seals on the edges to provide scratch protection to the wall finish and prevent accumulation of dust. The system will be water tight for Roof application. The system should be in 6063 alloy in clear anodized matt finish. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by the Engineer-in-Charge. |
| 88 | Wall to Wall -75mm Gap Size |
| 89 | Providing, levelling and fixing Inc EPDM Compression Seal of flexible wall plugging section is made of extruded EPDM and is suitable for Roof maintenance free, long lasting design. Goods workmanship free from surface defects and dimensional irregularities.The surface of the expansion joint covers should have a serrated surface for skid resistance at the top of joint and between the joint. The design of the expansion joint shall be such as to avoid any accumulation of dirt. Inc EPDM Compressor Seal 50mm is suitable for 90 to 100mm Gap size has an exposed surface of 100mm. The height of the model is 50 mm.- EPDM Compressor Seal 50 is glued with epoxy on both the side and inserted inside the gap.e surface of the expansion joint covers should have a serrated surface for skid resistance at the top of joint and between the joint. The design of the expansion joint shall be such as to avoid any accumulation of dirt. Inc EPDM Compressor Seal 50mm is suitable for 90 To100mm Gap size has an exposed surface of 100mm. The height of the model is 50 mm.- EPDM Compressor Seal 50 is glued with epoxy on both the side and inserted inside the gap.and fixing Inc EPDM Compression Seal of flexible wall plugging section is made of extruded EPDM and is suitable for Roof |
| 90 | Roof to Roof (75mm) |
| 91 | SUB HEAD -IV :MASONRY WORK |
| 92 | BRICK WORK |
| 93 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: |
| 94 | Cement mortar 1:4 (1 cement : 4 M- M.sand) |
| 95 | ProvidingandlayingAutoclavedAeratedconcreteblocks (AAC)masonry 150mm to 300mmthick AACwith Grade-1blocks of density 551-650 kg/cum conforming to IS:2185 (Part 3)in super structure above plinth level up to floor V level with RCC band at sill level and lintel level with approved block layingpolymermodifiedadhesivemortarallcompleteasperdirectionof Engineer-in-Charge. (The payment of RCC band and reinforcement shall be made for seperately). |
| 96 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. |
| 97 | Cement mortar 1 : 4 (1 cement : 4 M- M.sand) |
| 98 | Extra for providing and placing in position 2 Nos. 6 mm dia M.S. bars at every third course of half brick masonry (with F.P.S. bricks) |
| 99 | Extra for brick work / AAC block masonry / Tile brick masonryin superstructure above floor V level, for each four floors or part thereof by mechanical means. |
| 100 | Extra for half brick masonry in superstructure, above floor V level for every four floors or part thereof by mechanical means. |
| 101 | Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 M- sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with : Cement mortar 1:6 (1 cement : 6 M-sand) |
| 102 | GRC JALI |
| 103 | Providing and fixing Glass Reinforced Concrete (G.R.C) Screens casted with \"Spray Mix\" concrete design in approved size, pattern, thickness of 50mm on the outer Border & 25-30mm for Internal Member or overall thickness of 40mm and shade. The Screens should be made from ‘43 grade’Portland Cement manufactured by ‘JK Cement’ or \"Nuvoco\" or \"JK Lakshmi\" or Ultratech\". White Quartz fine graded seive Silica M.sand, Alkali Resistant Glass Fiber manufactured by \"NEG Japan, Owen Corning ‘Saint Gobain’ or equivalent, Super Plasticizers manufactured by ‘Karochem’ or equivalent, Polymers manufactured by ‘Nova Polychem’ or equivalent and U.V resistant Synthetic inorganic pigments should be used for pigmentation manufactured by ‘Phenochem industries or equivalent. The Screens casting shall take place with layering methodology using- Direct Power Spray machines.The GRC Screens flexural strength average L.O.P should be above or equivalent to 6 N/mm2 & M.O.R should be above or equivalent to 12 N/mm2 for tests done on 28 days cured samples. The fixing of Screens should be done using ‘Dry fixing’ method onto structural support members i.e. R.C.C, Brick work MS Framework. MS Galvanized CLAMPS & PINS also if required fasteners to be used of Wurth, Hilti & Fischer or equivalent. All cast in Socket to be epoxy primer coated, electrodes to be used of advani, mangalam, esab or victor brand or equivalent,. Vendor shall submit shop drawings of same, the drawings to be dully approved from Engineer in charge at site. |
| 104 | SUB HEAD -V :FLOORING WORK |
| 105 | FLOORING WORK |
| 106 | 52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 M- sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer’s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete |
| 107 | Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement : 3 M- M.sand), finished with a floating coat of neat cement. |
| 108 | 18 mm thick |
| 109 | Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : |
| 110 | Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. |
| 111 | Providing and laying Anti-Skid Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1 :4 (1 Cement : 4 M- M.sand), jointing with grey cement slurry@ 3.3 kg/ sqm including pointing the joints with white cement and matching pigments etc., complete. |
| 112 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 M- M.sand), jointing with grey cement slurry @ 3.3 Kg/ Sqmincluding grouting the joints with white cement and matching pigments etc., The tile must be cut with zero chipping diamond cutter only, laying of tile will be done with the notch trowel, plier, wedge, clips of required thickness, Levelling system and rubber mallet for placing the tiles gently and easily. |
| 113 | Double Charge Vitrified Tile of Polished finish of size |
| 114 | Size of Tile600 x 1200 mm Vitero of Aparna Make/ Marbunite of Johnson make /(SAPPHIRE SERIESof Kajaria Make or Equvalent |
| 115 | Glazed Vitrified tiles Matt/Antiskid finish of size |
| 116 | Size of Tile600 x 600 mm Vitero of Aparna Make/ Marbunite of Johnson make /(SAPPHIRE SERIESof Kajaria Make or Equvalent |
| 117 | Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0. 70 kg of organic coated filler of desired shade (0.1 0 kg of hardener and 0.20 kg of resin per kg), including filling I grouting and finishing complete as per direction of Engineer-in-charge. |
| 118 | Size of Tile 600/1200 |
| 119 | Deduct for not grouting the joints with white cement and matching pigmentin the items of fixing of vitrified tiles. |
| 120 | Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 M- M.sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge : |
| 121 | Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent. |
| 122 | Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 M- M.sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge |
| 123 | Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent |
| 124 | Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator , vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-in-charge. (The panel shuttering work shall be paid for separately).(Note:- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/ recoverable separately). |
| 125 | Making provision for contraction, expansion, construction and longitudinal joints (size 5x20mm) by groove cutting machine. |
| 126 | Providing and filling in position at expansion joints with poly sulphate sealants of approved brand. (size 5x20mm) |
| 127 | Abrasion Resistant Flooring- Surface Preparation:Preparing the existing surface of floor by diamond wheel grinding and cleaning by wire brushing etc, to remove all dirt, dust, oil etc to expose clean sound base concrete. Cost shall include treatment of construction and control joints filling as per manufacturer\"s specification and direction of Engineer In Charge. Any imperfections in the concrete shall be treated with suitable epoxy / polyurethane system as per manufacturer specification which shall be paid separately. |
| 128 | Abrasion Resistant Topping-2 mm:Providing and applying hybrid floor topping system at a thickness of 2mm Fosroc/MYK Arment/Pidilite a four-component product. A forced-action rotary paddle mixer is recommended for mixing the product. Topping applied at 1.5 mm thickness over a scratch coat with Nitoflor SL7 HD 0.5mm of Fosroc or equvalentto the designated area using serrated trowel and spike roller and shall have smooth matt finish, on cured shall exhibits the following Properties |
| 129 | 1) Compressive Strength (BS6319-2)52 MPa at 7 days 2) Tensile Strength(ASTM D 638) 12 MPa 3) Flexural Strength(ASTM D 790) 22 MPa4) Slip Resistance (ASTM E303) Dry, S96- 37.4(low slip risk)5) Abrasion resistance-(ASTM D4060)- 1kg CS17 Wheels, 39mg/1000 cycle6) Scratch Resistance (ISO 1518) - 7kg pass7) Shore D (ASTM D2240) @ 1day - 76 8) Bond Strength (ASTM D7234) > 2.5 MPaEnsure that the construction, control joint and other anchorage grooves of 4mm x 4mm are fully wetted out with material at the edges, day joints, up-stands, drains, doorways and at regular points across the floor and all debris removed.Note: -The work shall be carried out by the approved specialized waterproofing agency who has a minimum of 10 years experience in the proposed waterproofing system and covered by a written guarantee by Manufacturer and Applicator for their treatment for a minimum period of 10 years. |
| 130 | Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar refractive index) > 78, solar reflection > 0.70 and initial emittance > 0.75 on waterproof and sloped surface of terrace, laid on 20 mm thick cement M.sand mortar in the ratio of 1 :4 (1 cement : 4 M- M.sand) and grouting the joints with mix of white cement & marble powder in ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm height along the parapet walls in the same manner. |
| 131 | CLADDING WORK |
| 132 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 M- M.sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. |
| 133 | Granite of any colour and shade |
| 134 | Area of slab upto 0.50 sqm |
| 135 | Area of slab over 0.50 Sqm |
| 136 | Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. |
| 137 | Granite work |
| 138 | Extra for fixing marble /granite stone, over and above corresponding basic item, in facia and drops of width upto 150 mm with epoxy resin based adhesive, including cleaning etc. complete. |
| 139 | Extra for providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity counter and similar location in marble/ Granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete. |
| 140 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 M- M.sand) and jointing with grey cement slurry @ 3.3Kg per Sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 141 | Providing and fixing glazed screen printed border tile 75mm wide having thickness 5mm, of approved quality & make, in all shades, design and prints, in dado, over 12mm thick bed of cement mortar 1:3 (1 Cement : 3 M- M.sand) and jointing with grey cement slurry @ 3.3 kg/sqm including pointing with white cement mixed with pigment of matching shade, all complete as approved by Engineer - in - Charge |
| 142 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 M- M.sand), jointing with grey cement slurry @ 3.3 Kg/ Sqm including grouting the joint with white cement & matching pigments etc. complete. |
| 143 | Size of Tile 600 x 600 mm |
| 144 | Providing & fixing on roof pressed clay tile (Mangalore tile) of 20 mm nominal thickness and of approved size and as per approved pattern on steel frame work complete (steel frame work to be paid separately). |
| 145 | SUB HEAD -V I :FINISHING WORK |
| 146 | FINISHING WORK |
| 147 | 6 mm cement plaster to ceiling of mix : |
| 148 | 1:3 (1 Cement : 3 M.sand) |
| 149 | 12 mm cement plaster of mix : |
| 150 | 1:4 (1 cement: 4 M- sand) |
| 151 | 1:6 (1 cement: 6 M.sand) |
| 152 | 15 mm cement plaster on the rough side of single or half brick wall of mix : |
| 153 | 1:6 (1 cement: 6M.sand) |
| 154 | 18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) and a top layer 6 mm thick cement plaster 1:3 (1 cement : 3 coarse sand) finished rough with sponge. |
| 155 | Neat cement punning. |
| 156 | Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers. |
| 157 | Extra for plastering exterior walls of height more than 10 m from groundlevel for every additional height of 3 m or part thereof. |
| 158 | White washing with lime to give an even shade : |
| 159 | New work (three or more coats) |
| 160 | Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour. |
| 161 | Two coats |
| 162 | Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound ) content |
| 163 | With water thinnable cement primer on wall surface having VOC content less than 50 grams/ litre |
| 164 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 165 | Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade(Company Depot Tinted) with silicon additives. |
| 166 | New work (Two or more coats applied @ 1.43 litre/ 10 sqm. Over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm. |
| 167 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade : |
| 168 | New work (two or more coats) over and including water tinnable priming coat with cement primer |
| 169 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications : |
| 170 | Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 Sqm over an under coat of primer applied @ 0.80 ltr/10 Sqm of approved brand and manufacture |
| 171 | Applying priming coat: |
| 172 | With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/ steel works |
| 173 | SUB HEAD -V I I :STEEL ,WOOD WORK & JOINERY |
| 174 | WOOD WORK |
| 175 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters |
| 176 | 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 177 | Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross-section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminate shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame. |
| 178 | Providing and fixing to door frames |
| 179 | 30 mm thick Fiberglass Reinforced Plastic (F.R.P.) flush door shutter in different plain and wood finish made with fire retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate all around, with suitable wooden blocks inside at required places for fixing of fittings and polyurethane foam (PUF)/Polystyrene foam to be used as filler material throughout the hollow panel, casted monolithically with testing parameters of F.R.P. laminate conforming to table - 3 of IS: 14856, complete as per direction of Engineer-in-charge. |
| 180 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. |
| 181 | Fixed to steel windows by welding |
| 182 | Providing and fixing fly proof stainless steel grade 304 wire gauge, to windows and clerestory windows using wire gauge with average width of aperture 1.4 mm in both directions with wire of dia. 0.50 mm all complete. |
| 183 | With 12 mm mild steel U beading |
| 184 | Providing and fixing frame work for partitions/ wall lining etc. made of 50x50x1.6 mm hollow MS tube, placed along the walls, ceiling and floor in a grid pattern with spacing @ 60 cm centre to centre both ways (vertically & horizontally) or at required spacing near opening, with necessary welding at junctions and fixing the frame to wall/ ceiling/ floors with steel dash fasteners of 8 mm dia, 75 mm long bolt, including making provision for opening for doors, windows, electrical conduits, switch boards etc., including providing with two coats of approved steel primer etc. complete, all as per direction of Engineer-in-charge. |
| 185 | Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double acting hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge (Door handle, lock and stopper etc.to be paid separately). |
| 186 | Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISi, IS : 3564, embossed on the body, door weight upto 36 Kg to 80 Kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete. |
| 187 | Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete : |
| 188 | 250x16 mm |
| 189 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : |
| 190 | 250x10 mm |
| 191 | 150x10 mm |
| 192 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete : |
| 193 | 125 mm |
| 194 | 100 mm |
| 195 | Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete. |
| 196 | Twin rubber stopper |
| 197 | SS universal hydraulic door closer |
| 198 | Providing and fixing SS universal hydraulic door closer (having brand logo with ISi, IS : 3564, embossed on the body, door weight upto 36 Kg to 80 Kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete. |
| 199 | Providing and fixing Corner Patch Look with 6 levers without pair of handles of approved quality for aluminium door, with necessary screws etc complete as per direction of Engineer- in-charge. |
| 200 | Providing and fixing , lSI Pull Handle H type 32 mm Dia 600 mm marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyedto required colour or shade, with necessary screws etc. complete : |
| 201 | Providing & Fixing partially insulated fire rated GI Sheet doors conforming to FD 120-PI classification of IS 3614 :2021 with fire rating of 120 minutes integrity and 30 minutes insulation. The factory manufactured door frame and shutter assembly shall be made out of minimum 1.50 mm thick GI Sheet with minimum 120 g/m2 coating as per IS: 277.The Door should be finished with powder coating in standard RAL shade finish having DFT of minimum 50 microns. The door should carry a minimum 500 Hrs of salt spray test. All accressesories like hardware, vision panel, fire & smoke seal etc to be supplied by Fire door manufacturer only as per the guidelines laid down in IS 3614:2021. Every door must be ISI labeled confirming to type of door & its fire rating.The offered door must carry a prior valid test evidence of 5 years from CBRI-Roorkee. No fresh testing is required within the validity of test report from CBRI Roorkee. |
| 202 | The Door frame shall be single rebate grooved profile to accomodate 10x4mm Fire Seal, Size of Frame to beminimum125mm x 75mm made out of minimum 1.50mm thick galvanized steel sheet. Frames shall be butt / mitered joint and field assembeled with bolting system. The frame should also be provided with fire rated smoke seal as per IS: 3614:2021 or as per test evidence. It shall be pasted on surface and perimeter of main frame. All provisions should be mortised & provided with necessary inbuilt reinforcement to receieve appropriate hardware. Frames should be provided with back plate bracket for anchor fastner with 8-10 mm dia and minimum 80 mm long HDG fasteners, with Polyamide sleevesfor installation of frame in finished plastered masonary wall opening. |
| 203 | Door leaf should be minimum 60mm thick fully flush double skin door. Door leaf must be manufactured from 1.2mm(18gauge) thick galvanised steel sheet.The infill material shall be mineral wool of minimum density 96 kg/cum. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For double leaf doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. The shutters shall be mounted to the frame with SS 304 grade ball bearing type hinges of size 100x89x3 mm alongwith all suitable hardware(Payable in extra item).Vision lite glass size 200mm x 300mm (max area upto 0.06sqm) wherever applicable should be provided with single layered clear fire rated glass panes as per guidelines laid down under IS 3614 : 2021 vide clause no. 7.2.7 table no. 2 with a clipon arrangement.The glass will be provided with fire rated ceramic tape of suitable size alround on either face. Every Glass pane must carry a permanent marking of SAINT GOBAIN. Door must be tested with vision panel- 6mm thick pyroswiss glass. |
| 204 | Double leaf partially Insulated metal fire rated doorset of FD 120 PI classification with 120 minutes integrity and 30 minutes insulation as per IS 3614:2021 for Staircase/ Exit pathway / Refuge area etc |
| 205 | Providing and fixing fire rated GI Sheet doors conforming to FD 120-UD classification of IS 3614 :2021 with fire rating of 120 minutes integrity only. The factory manufactured door frame and shutter assembly shall be made out of minimum 1.50 mm thick GI Sheet with minimum 120 g/m2 coating as per IS: 277.The Door should be finished with powder coating in standard RAL shade finish having DFT of minimum 50 microns. The door should carry a minimum 500 Hrs of salt spray test. All accressesories like hardware, vision panel, fire & smoke seal etc to be supplied by Fire door manufacturer only as per the guidelines laid down in IS 3614:2021. Every door must be ISI labeled confirming to type of door & its fire rating.The offered door must carry a prior valid test evidence of 5 years from CBRI-Roorkee. No fresh testing is required within the validity of test report from CBRI Roorkee. |
| 206 | The Door frame shall be single rebate grooved profile to accomodate 10x4mm Fire Seal, Size of Frame to beminimum125mm x 55mm made out of minimum 1.50mm thick galvanized steel sheet. Frames shall be butt / mitered joint and field assembeled with bolting system. The frame should also be provided with fire rated smoke seal as per IS: 3614:2021 or as per test evidence. It shall be pasted on surface and perimeter of main frame. All provisions should be mortised & provided with necessary inbuilt reinforcement to receieve appropriate hardware. Frames should be provided with back plate bracket for anchor fastner with 8-10 mm dia and minimum 80 mm long HDG fasteners, with Polyamide sleevesfor installation of frame in finished plastered masonary wall opening. |
| 207 | Door leaf should be minimum 60mm thick fully flush double skin door. Door leaf must be manufactured from 1.2mm(18gauge) thick galvanised steel sheet.The infill material shall be honeycomb craft paper insulation. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For double leaf doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf.The shutters shall be mounted to the frame with SS 304 grade ball bearing type hinges of size 100x89x3 mm alongwith all suitable hardware(Payable in extra item).Vision lite glass size 200mm x 300mm (max area upto 0.12sqm) wherever applicable should be provided with single layered clear fire rated glass panes as per guidelines laid down under IS 3614 : 2021 vide clause no. 7.2.7 table no. 2 with a clipon arrangement. The glass will be provided with fire rated ceramic tape of suitable size alround on either face. Every Glass pane must carry a permanent marking of SAINT GOBAIN. Door must be tested with vision panel- 6mm thick pyroswiss glass of Saint Gobain make. |
| 208 | Double leaf un-insulated metal fire rated doorset of FD 120 classification with 120 minutes integrity only as per IS 3614:2021-For egress application like utility and service area. |
| 209 | 24mm DGU (6mm Edge Natura Toughened Glass+ 12mm Air Gap+ 6mm AIS Clear Toughened Glass |
| 210 | 24mm DGU (6mm Toughened Glass+ 12mm Air Gap+ 6mm AIS Clear Toughened Glass having properties of visible Light transmittance (VLT) 25%, ER 28%, IR 16%, Solar Heat Gain Coefficient (SHGC) 0.24 and U-value 2.0 W/m2 degree-K etc. The performance values declared should be tested by third party as well. The thickness/ combination of the glass can vary as per the architects/consultants’ suggestions after checking structural stability of the finalized glass panel. |
| 211 | 6mm thick Heat strengthened performance glass with reflective soft coating at face # 2 of silver shade on Clear Substrate of approved make having properties as visible Light transmittance (VLT) of 20 %, Light reflection internal 26%, light reflection external 31 %, Solar heat gain coefficient (.28), shading coefficient (0.33) and U value of 3.5 W/m2 degree K ,CRI value 92ra(d65). (VLT) of 20 %, Light reflection internal 26%, light reflection external 31 %, Solar heat gain coefficient (.28), shading coefficient (0.33) and U value of 3.5 W/m2 degree K ,CRI value 92ra(d65) |
| 212 | STEEL WORK |
| 213 | Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 214 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 215 | Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer. |
| 216 | Using M.S. angels 40x40x6 mm for diagonal braces |
| 217 | Providing and fixing heavy-duty industrial 50mm thik metal doors fabricated from 1.2 mm thick MS/GI sheet shutter with internal MS square tube stiffeners to prevent bending and ensure structural stability for large openings, complete with heavy-duty MS fabricated frame MS pipe with proper anchoring arrangements. The door shall be suitable for manual sliding / hinged operation (as applicable) and shall include all required industrial-grade hardware such as heavy-duty rollers/hinges, locking arrangement, tower bolts and stoppers. The surface finish shall be powder coating . ( make : Gandhi Automation , Nirmal Automation, Efaflex, Madhu industries,etc others with equilvalent specifications) |
| 218 | 4500X5400 mm |
| 219 | 3000 x3500 mm |
| 220 | Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge: |
| 221 | Profile C |
| 222 | Fixing with adjustable lugs with split end tail to each jamb |
| 223 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. |
| 224 | Hot finished seamless type tubes |
| 225 | Providing and fixing bolts including nuts and washers complete. |
| 226 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. |
| 227 | In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 228 | Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approved steel primer |
| 229 | M.S. tube |
| 230 | Providing and fixing carbon steel galvanised ( minimum coating 5 micron) dash fastener of 10 mm dia double threaded 6.8 grade (yield strength 480 N/mm2), counter sunk head, comprising of 10 m dia polyamide PA 6 grade sleeve, including drilling of hole in frame , concrete/ masonry, etc. as per direction of Engineer-in-charge. |
| 231 | 10x 160 mm |
| 232 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 233 | ALUMINIUM WORK |
| 234 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : |
| 235 | For fixed portion |
| 236 | Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 237 | For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) |
| 238 | Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 239 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): |
| 240 | With float glass panes of 5 mm thickness (weight not less than 12.50 kg/sqm) |
| 241 | Filling the gap in between aluminium/ stone/ wood frame and adjacent RCC/ Brick/ Stone/ wood/ Ceramic/ Gypsum work by providing weather/structural non sag elastomeric PU sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete, complying to ASTM C920, DIN 18540-F & ISO 11600 |
| 242 | Upto 10 mm depth and 10 mm width |
| 243 | ITEM: Louvers |
| 244 | Providing and fixing of Pre Fabricated Aluminum Louvers |
| 245 | Providing and fixing aluminium work for Louver with appropriate Z sections of size 63.5 x 35 and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions. All complete as per architectural drawings and the directions of Engineer-in-charge. (Including dash fasteners & necessary fixtures etc.)Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 246 | STRUCTURAL GLAZING ALUMINIUM COMPOSITE PANEL |
| 247 | Providing and supplying aluminium extruded tubular and other aluminium sections as per the architectural drawings and approved shop drawings , the aluminium quality as per grade 6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade as approved by the Engineer-in-Charge. ( The item includes cost of material such as cleats, sleeves, screws etc. necessary for fabrication of extruded aluminium frame work. Nothing extra shall be paid on this account). The weight of aluminium extruded section shall be taken for purpose of payment. |
| 248 | Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of structural glazing (with open joints) for linear as well as curvilinear portions of the building for all heights and all levels, including: |
| 249 | Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)-cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including: |
| 250 | Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers. |
| 251 | Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment, including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass. |
| 252 | Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight. |
| 253 | Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer- in-Charge. |
| 254 | Note:- 1. The cost of providing extruded aluminium frames, shadow boxes, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this subhead. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves) on the external face shall be measured in sqm. up to two decimal places. |
| 255 | Note:-2. The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 Sqm from the certified laboratories accreditated by NABL(National Accreditation Board for Testing and Calibration Laboratories), Department of Science & Technologies, India. Cost of testing is payable separately. |
| 256 | The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and importance of the work. Performance Testing of Structural glazing system Tests to be conducted in the NABL accredited lab or by any other accreditation body which operates in accordance with ISO / IEC 17011 and accredits labs as per ISO/ IEC 17025. |
| 257 | 1. Performance Laboratory Test for Air Leakage Test (-50pa to - 300pa) & (+50pa to +300pa) as per ASTM E-283-04 testing method for a range of testing limit 1 to 200 mVhr2. Static Water Penetration Test. (50pa to 1500p) as per ASTME- 331-09 testing method for a range up to 2000 ml.3. Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01- 05 testing method for a range upto 2000 ml4. Structural Performance Deflection and deformation by static air pressure test (1.5 times design wind pressure without any failure) as per ASTME-330-10 testing method for a range upto 50 mm5. Seismic Movement Test (upto 30 mm) as per AAMA 501.4- 09 testing method for Qualitative test, Tests to beconducted on site.6. Onsite Test for Water Leakage for a pressure range 50kpa to 240 kpa (35psi) upto 2000 ml |
| 258 | Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panel units of size and shape as required and specified, comprising of an outer heat strengthened float glass 6 mm thick, of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade, an inner Heat strengthned clear float glass 6 mm thick, spacer tube 12 mm wide, dessicants, including primary seal and secondary seal (structural silicone sealant) etc. all complete for the required performances, as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineerin- Charge. The IGUs shall be assembled in the factory/ workshop of the glass processor |
| 259 | (Payment for fixing of IGU Panels in the curtain glazing is included in costof item No.25.2) |
| 260 | For payment, only the actual area of glass on face # 1 of the glass panels(excluding the areas of the grooves and weather silicone sealant) providedand fixed in position, shall be measured in sqm. |
| 261 | (i) Coloured tinted float glass 6 mm thick substrate with reflective soft coating on face # 2, + 12 mm Airgap + 6 mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement |
| 262 | Extra for openable side / top hung vision glass panels (IGUs) including providing and supplying at site all accessories and hardwares for the openable panels as specified and of the approved make such as heavy duty stainless steel friction hinges, min 4 -point cremone locking sets with stainless steel plates, handles, buffers etc. including necessary stainless steel screws/ fasteners, nuts, bolts, washers etc. all complete as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer- in-Charge. |
| 263 | SUB HEAD -V I I I:WATERPROOFING & ROOFING WORK |
| 264 | ROOFING WORK |
| 265 | Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 M- M.sand : 4 stone aggregate 10 mm and down gauge), including finishing with cement mortar 1:3 (1 cement : 3 fine M.sand) as per standard design : |
| 266 | In 75x75 mm deep chase |
| 267 | Providing and fixing mineral fibre false ceiling tiles at all heights of size 595X595mm of approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflectance > 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt - 6 &7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33 mmthick (galvanized @120 gsm) comprising of main T runners of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200 mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600 mm suspended from ceiling using galvanized mild steel item (galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of 0.40 mm thicksheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-incharge. |
| 268 | With 20 mm thick beveled tegular mineral fibre false ceilingtile (NRC 0.7) |
| 269 | Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer\"s specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : |
| 270 | 12.5 mm thick tapered edge gypsum moisture resistant board |
| 271 | Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main \"T\" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross \"T\" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main \"T\" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross \"T\" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main \"T\" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge. |
| 272 | GI Metal Ceiling Lay in plain Tegular edge Global white color tiles of size 595x595 mm, and 0.5 mm thick with 8 mm drop; made of G I sheet having galvanizing of 100 gms/sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending. |
| 273 | ITEM:LINEAR METAL FALSE CEILING |
| 274 | Providing & Fixing of 300C Perf+ NWT (0.7 NRC) 2.0 mm diameter 5mm c/c pasted with aproved color NWT corrosion resistant Alluminium Magnesium Alloy metal ceilingconsisting of panel 300m wide x 30 mm deep x 0.7 mm thick with bevel edge having panel length upto 6 mtrs. coil coated on a continuous paintlien, Double baked and roll formed for higher straight and good roll forming characteristics with 21% perforation. The panel ends are raised upto 29 mm. The panel about each other with a narrow V groove. Panel shall be clipped to a backed enamelled aluminium panel carrier of 41.5 mm wide x 62 mm deep x 0.95 mm thick in standard length of 5 mtrs. made of double baked enamelled aluminium a mgnesium alloy AA3005 black with cut outs to hold panels module of 300 mm and at distance of 2.4 mtrs. the carrier shall be suspended by means of GI suspension rod 4mm diameter and suspension clip at 1.3 mtr.distancePaint finish:Alluminium panels shall be chromatised for maximum bond between metal and paint,enamelled twice under hgih temperatuve one side with full primer and Luxacote finish,the other side (Inner side) with a primer coat and skin coat on a Continous paint line. Seismic Zone V compliance - Metal facade should be Tested for Seismic Zone V compliance as per IS 1893 part 1-2016\" Mode of measurement: Measurements shall be wall to wall without deductions for lights, diffusers, columns etc |
| 275 | WATER PROOFING |
| 276 | Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : |
| 277 | First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. This layer will be allowed to air cure for 4 hours. |
| 278 | Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. |
| 279 | (The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry.) |
| 280 | Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guarantee for 10 years against any leakage. |
| 281 | For vertical surface two coats @ 0.70 kg per sqm per coat |
| 282 | For horizontal surface one coat @1.10 kg per sqm. |
| 283 | ITEM:Waterproofing of Terrace with Single Component Pure PU Waterproofing Membrane |
| 284 | Preparation of the concrete surface by mechanical means (mechanical grinding) to ensure a good bond between the coating and the substrate. Supplying and applying High Build Elastomeric waterproofing membrane Nitoproof 600PF based on pitch free polyurethane, cold applied of spray / brush applied single component membrane which is root resistant with minimum elongation of 500% to 700% as per ASTM D 412 and the system includes final base preparation, application of Nitoproof WB primer followed by applying Nitoproof 600 PF in two coats with solid content not less than 85% applied at minimum of 2.25 kgs / sqm to the required thickness and the mixing, composition, proposition etc shall be as per manufacturer specifications and approved by consultants. The cracks / construction joints / honey combs / leaking spots in the slab shall be provided with pressure grouting using cementitious system by admixing Cebex 100 - 225 grams to 50 kg bag of cement. The junctions shall be chamfered using Nitobond SBR admixed polymer mortar prior to application of waterproof coating. |
| 285 | On completion of waterproofing application, providing and fix 150gsm non woven Polypropylene geo textile membrane with over lap of minimum 50mm as protective medium before screed concrete or landscaping works. |
| 286 | Screed Concrete to Slope:Fixing 3mm diameter, 75mm square weld mesh over the geo textile surface followed by providing and laying screed concrete of M20 grade of average thickness and slope as per the direction of Engineer In Charge or Consultant incorporating necessary admixtures like Conplast WL Xtra @ 200ml per bag of cement as per manufacturer\"s specifications. Treatment to continue along the vertical surface for 300mm height in shape of round Chamfering, curing etc. The concrete shall be provided with groove cutting of 6mm x 10mm at every 5m x 5m area, the joints shall be treated with elastomeric sealants Nitoseal PU 50(Fosroc/BASF/Sika). Note: Cost of cement screed shall be paid under relevant item. |
| 287 | ITEM:BORE PACKING GROUT |
| 288 | Filling the annular space between concrete surface and plumbing pipe using non shrink grout after preparing the surface using sand paper and application of Nitobond SBR as a priming coat on the concrete walls. Mixing and pouring Conbextra GP2, high strength grout with clean and cool water at ratio of 0.16 on the prepared surface to make the bore packing water tight and apply two coats of approved Elastomeric coating water proofing overlapping the undisturbed area by minimum 150mm over the patch area properly. The rate shall include necessary materials, fixing back up foam cord on the bottom, tools and application procedure as per manufacturer\"s specification. |
| 289 | Core Cutting for 200mm/150mm for 160mm pipe dia |
| 290 | ITEM:Waterproofing Works - Below Raft Slab |
| 291 | Surface Preparation:Preparation of the PCC which should be free from cavities and projecting nibs. This shall include cleaning and removal of all the dust, dirt, oil, grease, cement laitance, contamination, loose particle for laying of waterproofing system. All surfaces shall be dry and free from frost. |
| 292 | Waterproofing Membrane: Supplying and laying a pre-applied, flexible, fully bonded CE made,HDPE - PW weldable grade pure HDPE membrane of 1.5 mm thick make over P.C.C conforming to IS 16471:2017 & BS 8102:2022 Type A requirements of Underground waterproofing structures.The system should be fully bonded to the RCC and consists of highly resilient HDPE film, self adhesive polymer layer and a particulate layer. The membrane shall bond integrally to poured concrete designed with Laplock Technology of raft slab to prevent the water migration between raft and membrane. The membrane shall be of 2.4m x 20m with minimum of factory made selvedge 100mm side and end laps which shall be welded together by HOT AIR welding with double seam welding machine. In case of minor damages in HDPE Membrane, the area shall be marked and sealed with another oversized patch (100 mm extended from the centre of the damage) by using HDPE tape with dual adhesive or by welding the oversized patch with single side hand welding machine. The membrane shall be taken in tappered manner as per the design slope of the consultant over PCC and terminated in the diaphragm wall by using Lokfix E77 and aluminium flashing over it. The membrane shall conforms to BS 8102:2022 & IS 16471:2017 & shall exhibit following properties: i. Tensile Strength: 26MPa ASTM D412ii. Elongation: 600% ASTM D412iii. Peel Adhesion to Concrete: 1200N/m ASTM D903iv. Puncture Resistance: 900N ASTM E 154v. Resistance to Hydrostatic Head: 71m ASTM D5385vi. Low Temperature Flexibility at (-)25°C: Pass ASTM D1970vii. Lap Peel Adhesion(Welded Joints): 12000N/m ASTM D6392The membrane shall be chemically resistant in all types of soil or water, has a zero permeance to moisture, solar reflective to reduce heat gain while exposed, does not activate prematurely due to wet conditions and is unaffected by ground settlement beneath slabs. |
| 293 | Supply and laying of Geo Textile:Protection layer of Geo textile with 120 GSm thick for waterproofing membrane protection. |
| 294 | ITEM:Waterproofing Works - Wall Outer Side |
| 295 | Waterproofing Membrane:Providing and spray applying the outer side wall of the simulation tank with two component 100% solids VOC free, rapid curing polyurea WH200 designed as a waterproofing and protective coating at 1.5mm thickness as per material specification. The first part includes surface preparation, application of epoxy primer Nitoprime 31 as per material specification, using roller/brush coat @ 250gms/sq.m. Silica sand to be spread over the primed surface. The application shall be done by using high pressure, heated two component spray proportioning equipment to attain a minimum thickness of 1.5 mm with tensile strength 13 MPa (ASTM D412), shore A hardness is 80(ASTM D2240) and an elongation greater than 450% (ASTM D412).Pin holes/blow holes are repaired using either Nitmortar FC/Nitomortar S. The junctions shall be chamfered using Nitobond SBR admixed polymer mortar prior to application of waterproof coating.( Refer sketch enclosed for reference) |
| 296 | ITEM:Waterproofing Works - Wall Inner Side |
| 297 | Epoxy Polysulphide Elastomeric Coating:Providing and applying the inner side walls and floor of the simulation tank with two component chemical resistant, abrasion resistant epoxy polysulphide elastomeric coating of Nitocote EPS which forms as a tough and flexible seamless waterproofing and protective coating at 1.0mm dry film thickness at a coverage of 1.0 sqm/lit and as per material specification by using stiff nylon brush/short nap roller/airless spray. The first part includes surface preparation, application of epoxy primer Nitoprime 25 and as per material specification, using roller/brush coat @ 250gms/sq.m.Pin holes/blow holes are repaired using either Nitmortar FC. All the construction joints/kicker joints in the tank wall shall be provided with PVC waterstops of Supercast Watafoil of size 250mm and followed by pressure grouting using cementitious system by admixing Cebex 100 @ 225 grams to 50 kg bag of cement. The junctions shall be chamfered using Nitobond SBR admixed polymer mortar prior to application of waterproof coating. ( Refer sketch enclosed for reference) |
| 298 | ITEM:Construction Joint Treatment |
| 299 | Starter Joint / Construction Joint:Supercast SW20 based on advanced synthetic elastomer strips at all construction joints of retaining walls, lift walls, UG sump, STP, etc. Swell bars to be placed in between the reinforcement with adhesive or coir wire before placing of concrete. Thickness of water bar to be minimum 20mmX10mm or as per manufacturer\"s\" specification. The waterbar shall be formulated to exhibit low pre-mature swelling and increase in volume upto maximum of 200%. The waterbar shall have a minimum cover concrete of 70mm to accommodate the pressure developed during swelling process. The hydro-swelling water bar shall have the below properties:-Physical Properties Typical ValuesSize : 20mm x 10mmsolids content : 100%Shore A hardness : 70unrestrained volume expansion : upto 200%Application temperature : -20°C to 50°CService temperatures : 30°C to 50°CHydrostatic pressure resistance : 10 bar (100 metres head). |
| 300 | ITEM:Termination |
| 301 | Termination:The membrane shall be terminated by making a groove of 20mm x 10mm in the diaphragm wall inner side at a height of 1m from the raft top surface and on the top of the simulation tank wall outer side and sealing the grooves with polymer modified mortar/sealant as shown in the drawing. |
| 302 | ITEM:Protective Coating: |
| 303 | Protective Coating:Waterproof coating shall be coated with two component UV stable aliphatic Polyurethane coating Dekguard PU of approved colour shade at 90 microns thick as per manufacturer\"s specification. |
| 304 | ITEM:External Elevation Wall Coating |
| 305 | Providing and applying Dekguard E2000 or equivalent makes acrylic, breathable, elastomeric, water based, anti-carbonation coating to all masonry/concrete members primed with Dekguard Primer or Dekguard WB Primer above ground. Coating must be applied in two coats to achieve total dry film thickness of not less than 200 microns and shall have carbon dioxide diffusion resistance equivalent air layer thickness (DIN EN 1062 Part 6 & FTM276) > 50 m; carbon dioxide diffusion resistance equivalent air layer thickness (Taywood Method) = 240 m; carbon dioxide diffusion resistance equivalent thickness of 30N conc. (Taywood Method) >500 mm; Elongation of cured film shall be (ASTM D 412) > 200%; Chloride Ion Penetration (ASTM C 1202) = Very Low (100 to 1000 Coulombs); Tear Resistance (ASTM D 624) = 12 N/mm; Static Crack spanning capability (Modified ASTM C 836-76) = 2mm; UV Resistance (ASTM D 4587, Cycle 1 from ASTM G154) > 500 Hours; Reduction in Water Absorption (ASTM C642) > 82%; Adhesion (ASTM D 4541) > 1 N/mm2 and Solar Reflectove Index of 105 amd emissivity > 93% (ASTM E 1980-11) etc, complete. Product used shall have CE (CE-29842) marking and compliance according to Construction Products Directive 89/106/EEC (CPD)Note:1 Colour pigmentation is available in a selected range of RAL colours/shades.Note:2 Coating shall be continued to the full parapet wall height and overlapped to 100mm over the Terrace/Roof Slab PU coating. |
| 306 | ITEM:Tie Rod Holes |
| 307 | Providing & Installing thixotropic, cementitious gun grade, non-shrink grout Conbextra Tie Rod Grout(Fosroc/BASF/Sika) in tie rod hole fillings, that shall meet the following performance criteria only with air curing at 27°C, with no water curing necessary. It shall provide a fair finish which matches the concrete substrate shade with almost no wastage during applications.Conbextra Tie Rod Grout, when tested shall deliver the minimum parameters as below :(i) Fresh wet density - 1.97±0.1 g/cc(ii) Compressive Strength (ASTM C 109, for a 50 mm cube size) 1 days - >8 MPa 28 days - >30 MPa (iii) Pot life - 90 mins(iv) Water permeability (mL, IS 2645) - Nil (v) Pull out bond strength by LDM - 12 MPa @ 28 days (vi) Pull off bond strength - >0.5 MPa @ 3mm thickness, 28 days(vii) Tensile Strength (EN-196-1)7-days - >3 MPa28-days - >5 MPa |
| 308 | Designing, fabricating, testing, protection, installing and fixing in position PUF insulated sandwich panels for walls of total thickness not less than 100mm and width 1.0 m having tongue and groove edge finish with camlock arrangement. Panel shall have 0.5mm thick precoated GI sheet on both side of polyurethane foam confirming to IS 12436:1988. The Precoated sheet shall be of minimum 240 mpa steel grade confirming to IS 14246:1995 and shall have zinc coating of minimum 120 gsm as per IS:277:1992, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 20 micron. The PPGI sheet shall have plastic protective guard film of minimum 25 microns to avoid scratches while transportation. The PU foam shall be self-extinguishing, fire retardant type having minimum density of 40 Kg/cum(+,-2 Kgs) including CFC Free pannel should be GRIHA Certified. The panels shall be fixed to the steel frame structure with minimum 5 mm thick self-tapping GI screws of required length and nos. with minimum spacing of 300 mm c/c Including provision of G.I boxes/Conduits etc. fitting. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid window, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working PUF panel structure as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight PUF panel structure having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer- in-Charge. |
| 309 | Providing and fixing 15 cm wide, 45 cm overall semi-circular plain G.S. sheet gutter with iron brackets 40x3mm size, bolts, nuts and washers etc., including making necessary connections with rain water pipes complete. |
| 310 | 0.80 mm thick with zinc coating not less than 275 gm/m² |
| 311 | SUB HEAD -I X :INTERNAL SANITARY & WATER SUPPLY WORK |
| 312 | SANITARY FIXTURES & ACCESSORIES |
| 313 | Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required as per the sample approval & under the directions of Engineer-in-charge : |
| 314 | W.C. pan with ISI marked white solid plastic seat and lid |
| 315 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required as per the sample approval & under the directions of Engineer-in-charge : |
| 316 | One urinal basin with 5 litre white P.V.C. automatic flushing cistern |
| 317 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require as per the sample approval & under the directions of Engineer-in-charge. |
| 318 | Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required as per the sample approval & under the directions of Engineer-in-charge: |
| 319 | Kitchen sink with drain board |
| 320 | 510x1040 mm bowl depth 225 mm |
| 321 | Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1 metre long with S.S. triangular plate to Eureopean type W.C. of quality as per the sample approval & under the directions of Engineer-in-charge |
| 322 | Providing and fixing water closet squatting pan (Indian type W.C. pan) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: |
| 323 | White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests |
| 324 | Providing and fixing Counter Top wash basin with 15 mm dia CP Brass single hole basin mixer of approved quality and make. |
| 325 | Providing and fixing 8 mm dia S.S. Health Faucet with flexible tube upto 1 metre long of quality and make as approved by Engineer - in - charge. |
| 326 | Providing and fixing mirror of superior glass (of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing : |
| 327 | Rectangular shape 1500x450 mm |
| 328 | Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour, weighing not less than 105 gms. |
| 329 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. |
| 330 | 600 mm long towel rail with total length of 645 mm, width 78mm and effective height of 88 mm, weighing not less than 190gms. |
| 331 | Providing and fixing P.V.C. waste pipe for sink, wash basin, urinal including P.V.C. waste fittings complete as per the sample approval & under the directions of Engineer-in-charge |
| 332 | Flexible Pipe |
| 333 | 40 mm dia |
| 334 | Providing and fixing 100 mm sand cast Iron grating as per the sample approval & under the directions of Engineer-in-charge |
| 335 | Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 em deep and 1.8 em thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1 :2:4 (1 cement: 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per the sample approval & under the directions of Engineer-in-charge |
| 336 | White Agaria Marble Stone |
| 337 | Providing and fixing C.P. brass Sink Taps of approved quality conforming to IS:8931 as per the sample approval & under the directions of Engineer-in-charge : |
| 338 | 15 mm nominal bore |
| 339 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 as per the sample approval & under the directions of Engineer-in-charge |
| 340 | 15 mm nominal bore |
| 341 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank as per the sample approval & under the directions of Engineer-in-charge |
| 342 | SOIL , WASTE, VENT PIPES AND FITTINGS |
| 343 | Providing and fixing on wall face unplasticised Rigid PVC pipes confonning to IS : 13592 Type A, including jointing with seal ring confonning to IS : 5382, leaving 10 mm gap for thennal expansion, (i) Single socketed pipes. |
| 344 | 75 mm diameter |
| 345 | 110 mm diameter |
| 346 | Providing and fixing M.S. holder bat clamps of approved design to C.l. or S.C.I. rain water pipes embedded in and including cement concrete blocks 10x10x10 em of 1:2:4 mix (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) and cost of cutting holes andmaking good the walls etc. : |
| 347 | 75 mm diameter |
| 348 | 110 mm diameter |
| 349 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS: 13592 Type A, including jointing with seal ring conforming to IS : 5382,leaving 10 mm gap for thennal expansion. |
| 350 | Single tee with door |
| 351 | 75x75x75 mm |
| 352 | 110x110x110 mm |
| 353 | Single tee without door |
| 354 | 75x75x75 mm |
| 355 | 110x110x110 mm |
| 356 | Bend 87.5° |
| 357 | 75 mm bend |
| 358 | 110 mm bend |
| 359 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 em diameter and weighing not less than 440 grams. |
| 360 | Cutting holes up to 15x15 cm in R.C.C. floors and roofs for passing drain pipe etc. and repairing the hole after insertion of drain pipe etc. with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including finishing complete so as tomake it leak proof. |
| 361 | Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : |
| 362 | 100 mm inlet and 100 mm outlet |
| 363 | Sand cast iron S&S as per IS: 3989 |
| 364 | WATER SUPPLY PIPES AND FITTINGS |
| 365 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply and all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer inCharge. |
| 366 | Internal work - Exposed on wall |
| 367 | 25 mm nominal dia Pipes |
| 368 | 32 mm nominal dia Pipes |
| 369 | 40 mm nominal dia Pipes |
| 370 | 50 mm nominal dia Pipes |
| 371 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings and fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. |
| 372 | Concealed work - including cutting chases and making good the walls etc. |
| 373 | 15 mm nominal dia Pipes |
| 374 | 20 mm nominal dia Pipes |
| 375 | 25 mm nominal dia Pipes |
| 376 | 32 mm nominal dia Pipes |
| 377 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. |
| 378 | External work |
| 379 | 65 mm nominal dia Pipes |
| 380 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : |
| 381 | 32 mm nominal bore |
| 382 | 40 mm nominal bore |
| 383 | 50 mm nominal bore |
| 384 | 65 mm nominal bore |
| 385 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete |
| 386 | 15 mm nominal bore |
| 387 | 20 mm nominal bore |
| 388 | 25 mm nominal bore |
| 389 | Providing and fixing gun metal non- return valve of approved quality (screwed end) : |
| 390 | 32 mm nominal bore |
| 391 | Horizontal |
| 392 | 40 mm nominal bore |
| 393 | Horizontal |
| 394 | 50 mm nominal bore |
| 395 | Horizontal |
| 396 | 65 mm nominal bore |
| 397 | Horizontal |
| 398 | Providing and fixing uplasticised PVC connection pipe with brass unions : |
| 399 | 30 cm length |
| 400 | 15 mm nominal bore |
| 401 | INTERNAL RAIN WATER DRAINAGE WORK |
| 402 | Making khurras 45x45 cm with average minimum thickness of 5 em cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1 :3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete. |
| 403 | Providing and fixing 100 mm diameter and 60 em long rain water spout in cement mortar 1 :4 (1 cement : 4 fine sand). |
| 404 | Stone ware spout |
| 405 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes confonning to IS : 13592 Type A, including jointing with seal ring confonning to IS : 5382, leaving 10 mm gap for thennal expansion, (i) Single socketed pipes. |
| 406 | 75 mm diameter |
| 407 | 110 mm diameter |
| 408 | 160 mm diameter |
| 409 | Providing and fixing M.S. holder bat clamps of approved design to C.l. or S.C.I. rain water pipes embedded in and including cement concrete blocks 10x10x10 em of 1:2:4 mix (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) and cost of cutting holes and making good the walls etc. : |
| 410 | 75 mm diameter |
| 411 | 110 mm diameter |
| 412 | 160 mm diameter |
| 413 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS: 13592 Type A, including jointing with seal ring conforming to IS : 5382,leaving 10 mm gap for thennal expansion. |
| 414 | Coupler |
| 415 | 75 mm |
| 416 | 110 mm |
| 417 | 160 mm |
| 418 | Single tee with door |
| 419 | 75x75x75 mm |
| 420 | 110x110x110 mm |
| 421 | 160x160x160 mm |
| 422 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 em diameter and weighing not less than 440 grams. |
| 423 | SUB HEAD - X- INTERNAL ELECTRICAL WORKS |
| 424 | POINT WIRING : |
| 425 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed mild mild steel conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 426 | Group C |
| 427 | Group B |
| 428 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed mild mild steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 429 | Group C |
| 430 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed mild mild steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. |
| 431 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed mild mild steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 432 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed mild mild steel conduit as required. |
| 433 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 434 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 435 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 436 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 437 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 438 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 439 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 440 | 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 441 | Supplying and drawingCo axial TV cable, RG-6 grade, 0.7 mm solid copper conductor, shieldedwith fine tinned copper braid and protected with PVCsheathin the existing surface/recessed mild steel/PVC conduit as required. |
| 442 | Supplying and Installation of following sizes of mild mild steel conduit alongwith accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 443 | 20 mm |
| 444 | 25 mm |
| 445 | 32 mm |
| 446 | Supplying and Installation of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 447 | 20 mm |
| 448 | 25 mm |
| 449 | 32 mm |
| 450 | 40 mm |
| 451 | Supplying and Installation following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 452 | 5/6 A switch |
| 453 | 3 pin 5/6 A socket outlet |
| 454 | Telephone socket outlet |
| 455 | TV antenna socket outlet |
| 456 | Supplying and Installation two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 457 | Supplying and Installation modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 458 | Supplying and Installation following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 459 | 1 or 2 Module (75mmX75mm) |
| 460 | Supplying and Installation following Modular base & cover plate on existing modular metal boxes etc. as required. |
| 461 | 1 or 2 Module |
| 462 | Supplying and Installation suitable size GI box with modular plate and cover in front on surface or in recess, including providing and Installation 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 463 | Supplying and Installation suitable size GI box with modular plate and cover in front on surface or in recess, including providing and Installation 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 464 | Supplying and Installation 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 465 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. |
| 466 | Upto 450 mm sweep |
| 467 | Supplying & Installation suitable size GI box wih modular plate and cover in front on surface or in recess including providing and Installation 25 A modular socket outlet and 25 A modular SP MCB, \"C\" curve including connections, painting etc. as required. |
| 468 | MCB\"s & DB’s : |
| 469 | Providing and Installation following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 470 | 100 A, 30 KA,FPMCCB |
| 471 | 125 A, 30 KA,FPMCCB |
| 472 | Supplying and Installation following way, single pole and neutral (SPN), sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 473 | 8 way , Double door |
| 474 | 12 way , Double door |
| 475 | Supplying and Installation following way, horizontal type three pole and neutral (TPN), sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 476 | 4 way (4 + 12), Double door |
| 477 | 6 way (4 + 18), Double door |
| 478 | 8 way (4 + 24), Double door |
| 479 | Supplying and Installation of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 480 | 4 way (4 + 12), Double door |
| 481 | 8 way (4 + 24), Double door |
| 482 | 12 way (4 + 36), Double door |
| 483 | Supplying and Installation 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 484 | Single pole |
| 485 | Double pole |
| 486 | Triple pole (40A & 63A) |
| 487 | Supplying and Installation single pole blanking plate in the existing MCB DB complete etc. as required. |
| 488 | Supplying and Installation following rating, four pole (FP), 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 489 | 40 A |
| 490 | 63 A |
| 491 | 100 A |
| 492 | Supplying and Installation Cable End Box (Loose Wire Box) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc.as required. |
| 493 | For 6 way, Double door TPN MCBDB |
| 494 | For 8 way, Double door TPN MCBDB |
| 495 | ELCB/RCCB SWITCHES : |
| 496 | Supplying and Installation following rating, four pole, (three phase and neutral) SPN, 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 497 | 40 A |
| 498 | 63 A |
| 499 | FIXTURES : |
| 500 | Supplying, installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round/square/Rectangular) COB Type of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K / 6000°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). |
| 501 | Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C) |
| 502 | Powder coated die cast /Extruded aluminum Body including trim with Aluminum Reflector |
| 503 | 8 - 10 watt |
| 504 | 12 -15 watt |
| 505 | Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends, CCT 3000°K/4000°K/5700°K/ 6000°K/ 6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). |
| 506 | Manufactures Word Mark/Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 507 | Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm) |
| 508 | 40 watt |
| 509 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends,CCT 3000°K / 4000°K / 5700°K /6000°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. |
| 510 | Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 511 | Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm) |
| 512 | 18- 22 watt |
| 513 | Supplying and Installation PVC batten/angle holder including connections etc. as required. |
| 514 | Supply and Installation LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete. |
| 515 | Supply and Installation of single unit LED aviation obstruction light complete with transformer and LED spiral etc. complete in all respect. |
| 516 | Supply and Installation of water tight oblong 10 Watt LEDbulk head luminaire having die cast housing with driver set confirming to IP 65 and above Protection.Complete in all respect. (1100 systemlumens 110 lm/W, PF>0.95, THD<20% at full load) |
| 517 | Supply and Installation of 120 watt IP66& IK10 high efficancy highbay fitting with arrangement of hanging hook along with Installation and providing of mounting arrangement at slab and hanging rodcomplete in all respect including connection with 2.5 sqmm FRLS PVC insulated copper conductor |
| 518 | Supply and Installation of 60 watt IP66& IK10 high efficancy highbay fitting with arrangement of hanging hook along with Installation and providing of mounting arrangement at slab and hanging rodcomplete in all respect including connection with 2.5 sqmm FRLS PVC insulated copper conductor |
| 519 | Supply, installation, connecting, testing and commissioning of illuminated exit sign with 1 x 6 watt LED lamp including providing maintenance free batteries & charger capable of working for 2 hr duration mounted on ceiling/wall complete with the approved EXIT self adhesive labels as per site requirement as required including connection with 1.5 sqmm FRLS PVC insulated copper conductor |
| 520 | Supply & Installation of 12 Watt LED Bulb - B22 / E27 (Colour Temp.- 6500K / Lumens - 900 lm) cool day light, Input Volts (AC 90V-260V), 3-Star rating suitable for Batten/Angle holder including making connection.Complete in all respect. |
| 521 | Supply & Installation of 400mm sweep wall mounted (Light Duty) fan complete with Plastic Blade & Pull Cord (Adjustable upward and downward tilt mechanism /motor /capacitor etc.) Oscillation degree - 90, Power consumption : 60 W, Rated voltage : 230 V, Rated frequency : 50 Hz, Speed : 1350 RPM. Complete in all respect. |
| 522 | Supply & Installation of 450mm sweep wall mounted (Heavy Duty) fan complete with Double ball bearings ZZ (Permanent lubricated) /Sturdy close-mesh guards with powder coating /Aerodynamically designed & Balanced Blade /Precision built oscillating mechanism with indexing option and Oscillation degree - 90, Power consumption : 100 W, Rated voltage : 230 V, Rated frequency : 50 Hz, Speed : 1440 RPM. Complete in all respect. |
| 523 | Supply & Installation of 225/230mm sweep ventilating (Light Duty) exhaust fan complete with Metallic Blade (Steel bird guard protector /Copper motor for high air suction performance /Capacitor etc.), Noise level : (45 - 50) dB, Power consumption : 45 W, Rated voltage : 230 V, Rated frequency : 50 Hz, Motor type : Normal Speed. Complete in all respect. |
| 524 | Supply & Installation of 300mm sweep ventilating (Medium Heavy Duty) exhaust fan complete with Metallic Blade (Steel bird guard protector /Double ball bearing /Copper motor /Capacitor etc.), Noise level : (45 - 50) dB, Power consumption : 70/85 W, Rated voltage : 230 V, Rated frequency : 50 Hz, Speed : 900/1400 RPM. Complete in all respect. |
| 525 | Supply & Installation of 450mm sweep ventilating (Industrial Heavy Duty) exhaust fan complete with Metallic Blade (Dynamically balanced impellers for smooth and vibration-free operation /Pre-lubricated double ball bearing /Copper motor /Capacitor etc.), Noise level : 55 dB - 60 dB; Power consumption : 140 W ; Rated voltage : 220-240 V ; Rated frequency : 50 Hz, Speed : 900 RPM. Complete in all respect. |
| 526 | Brush Less Direct Current (BLDC) Fan without RemoteSupply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 °C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 527 | 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 528 | S/F of hexagonal fan box with hexagonal side of approx 80mm in length fabricated from 16SWGM.S. sheet incorporating 10mm dia, M.S. round barduly bent for supporting fan hanger dully painted withred oxide and screwing arrangement with wiring conduit laid in the R.C.C. roof before concreting along with supply of all materials, labour T & P etc., for proper completion of work. |
| 529 | MISCELLANEOUS ITEMS |
| 530 | Supply and Installation of perforated 2mm thick CRCA sheet steel power coated cable tray of following sizes complete with bend/tee joints, coupling plate & nuts bolts etc. including providing and Installation of M.S. painted hanger etc. as required. |
| 531 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 532 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 533 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 534 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 535 | Supply and Installationof cable tray/steel work in position including clamps, frame work of flats, angle iron, channel with fabrication work including cutting, bending, welding, drilling bolting etc. as per design as required.One coat of primer and 2 coats of enamel paint of approved shade shall be provided. |
| 536 | SUB HEAD -X I -AIR CONDITIONING |
| 537 | VRF/VRV OUTDOOR AC UNIT |
| 538 | Supply, Installation, Testing & Commissioning of Modular type VariableRefrigerant Flow/Variable Refrigerant Volume air cooled Outdoor unitssuitable for cooling/heating having 100% hermetically sealed inverter type twin Rotary/Scroll Compressor(s), minimum two compressors (withindividual seperate PCB) for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condensor fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. |
| 539 | The system shall be able to deliver 100% of the rated capacity upto 39Degree Celcius. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as per Energy Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete as per CPWD specification, connections, inter connections etc. as required. (For capacity <40 kWr ISEER 6.4, Capacity > 40 and <70 ISEER 6.5, Capacity > 70 ISEER 6.6 for ECSBC Building + Building) |
| 540 | 566HP |
| 541 | VRF/VRV INDOOR UNIT (CASSETTE TYPE) |
| 542 | Supply, Installation, Testing and Commissioning of following minimumcapacity 4 way Cassette Type Indoor ceiling mounted unit equipped withsynthetic washable media pre-filter, fan section with low noise fan / dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration Isolation, Corded remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Signals. The system shall be capable to adjust air flow as per room requirement in auto mode. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor) |
| 543 | 3.6 TR /3.18 TR |
| 544 | 2.6 TR / 2.56 TR |
| 545 | 2.0 TR / 2.02 TR |
| 546 | 1.6 TR / 1.59 TR |
| 547 | 1.2 TR / 1.28 TR |
| 548 | Double SkinnedCeiling Susprnded DX TYPE Air Handling Units with Inbuilt Starter Panel |
| 549 | Supply, Installation Testing & Commissioning of factory assembled/ modular EUROVENT certified Double skin-floor mounted / Ceiling Suspended Air handling Units (AHU) complete with double skin 50mm thick insulated with Rockwool panel of 38±2 kg/cum density sandwiched between 0.8mm thick Alu Zinc inner & 0.8mm precoated GI outer sheets. The AHU casing shall comply to Eurovent standard EN 1886 for casing strength D1, casing Air leakage L1, Thermal Bridging factor TB2, Thermal Transmittance T2 & filter bypass leakage F9. The control wiring and power wiring shall be in the scope of OEM AHU manufacture and to be carried out at factory with terminations to Marshalling box. |
| 550 | Food grade self adhesive coated EPDM gasket to be provided between panels and structure of the AHU to ensure the entire housing is airtight. 10mm heavy duty GSS base frame shall be powder coated for better aesthetics, cleaning and maintenance. |
| 551 | The AHU shall be supplied with AHU blower fans with wall mounted EC PLUG fan (EBM / Ziehl-abegg) complete with external rotor BLDC motor & integrated electronic controller, potentiometer for speed control. The fan shall be suitable for BMS connectivity. Series of multiple fans shall be considered depending upon capacity of AHU’s (as mentioned below) AHU manufacture should supply cover plate for fans in sufficient quantity for maintenance purpose. EC fan incoming supply to be terminated. |
| 552 | With MCB and shall be included in the power terminal box for electrical connection of EC fans and should be factory fitted on the AHU’s potentiometer shall be provided in the marshalling box for manual operation of EC fans. Relay for AUTO/MANUAL operation should be a part of marshaling box supplied by the AHU manufacture |
| 553 | DX Type coils 6 Row deep suitable for connecting with VRV/VRF . Face velocity across the coils should not exceed 500 FPM. Cooling coils shall be constructed from premium quality seamless copper tubes 12.5mm thickness dia and aluminum fins of 0.21mm thickness of 12FPI, AS PER SPECS, UV Emitters with reflectors to be fixed on the coil surface with removable extruded aluminum frames. |
| 554 | Filters section should be consisting of pre filterin aluminium casing. Pre filter shall be with non woven sysnthetic media of 10 micron article size with an efficiency of 90 % . |
| 555 | AHU should have marine lamp including adequately rated LED light fitting inside the AHU cabinet. AHU inspection door should have view window with perfectly sealed gaskets on either side to ensure air tightness. All AHUs shall be provided with door limit switch and also door safety GI guard. All internals shall be powder coated for corrosion resistance. |
| 556 | Control panel to be provided with a rotary switch to ON/OFF the fan through manual by override. Apart from that there will be an option to ON/OFF AHU by controller keypad and also from BMS. A potentiometer with auto/manual switch to be provided so an override of fan speed through manual should be possible Main incoming MCB, Individual MCB for each fan, busbar, 1 no. Contactor to distribute power to individual fan should be provided. A SMPS with terminal fuse protected will be used powering up the controller. All Common alarms will be displayed on controller |
| 557 | Isolators Vibration isolators shall be provided to all air handling units. The fan and motor framework shall be isolated from the AHU framework by means of spring type vibration isolators. The AHU shall be mounted on 6-inch-high PCC block suitable for weight of the AHU. The platform shall be 4 inch bigger than the AHU frame size from all sides. The framework of the AHU and the P.C.C. block shall be isolated by means of neoprene mats of size 150mmx150mm in two layers with 16g G.S.S. sheet sandwiched in between. |
| 558 | Note: Units Shall be including expansion AHU Kit to connect with VRV / VRF System. |
| 559 | Note: PVC ports for DPS tube connections in Fine filter shall be provided and rates will be included in AHU. |
| 560 | 6000 CFM, ( 65 mm St. Pr, 6 Row CC )CEILING SUSPENDED TYPE |
| 561 | 5000 CFM, ( 40 mm St. Pr, 6 Row CC ) CEILING SUSPENDED TYPE |
| 562 | 4000 CFM, ( 40 mm St. Pr, 6 Row CC ) CEILING SUSPENDED TYPE |
| 563 | 3000 CFM, ( 40 mm St. Pr, 6 Row CC ) CEILING SUSPENDED TYPE |
| 564 | COPPER REFRIGERANT PIPING |
| 565 | Supply, Installation, testing and commissioning including vaccumiazationand Nitrogen testing of following nominal sizes of soft/hard drawn copperrefrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories,insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : |
| 566 | 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 567 | 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 568 | 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 569 | 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 570 | 19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm |
| 571 | 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm |
| 572 | 25.4 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm |
| 573 | 28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm |
| 574 | 31.8 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm |
| 575 | 34.9 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm |
| 576 | 38.1 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm |
| 577 | 41.27 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm |
| 578 | Y- JOINTS |
| 579 | Supply, Installation, Testing and Commissioning of Y/T/Multi Joints. Joints shall be of same Original Equipment Manufacturer (OEM) make as of ODUs and IDUs |
| 580 | Anticorrosive Coating on VRV-IDU, Brazing Joints of Cooling Coil |
| 581 | Anticorrosive Coating on VRV-ODU, Brazing Joints of Cooling Coil |
| 582 | OUTDOOR STAND FABRICATION |
| 583 | Supply,fabrication and erection of Angle/Channel/Flat iron stand ,hanging arrangement for air conditioning machines & ducts etc.Back /Support clamps or other similar work etc.including nuts ,bolts of required size,making holes,fabrication,welding,cutting,etc.and painting with one coat of red oxide paint & two coat of enamel paint as required as per specification. |
| 584 | Central Controller forIndoor & Outdoor Units |
| 585 | Supply, installation, testing & commissioning of Central Controller capable of controlling of all IDUs, ODUscomplete with necessary hardware, accessories etc. to perform the following functions: |
| 586 | Controlof IDUs, ODUs Units as above with monitoringof vital parameterssuch as temperaturesensing & setting, ON/OFF, status etc. |
| 587 | Permit / prohibit function of each remote controlled unit. |
| 588 | Operation of units in individually or in group. |
| 589 | Fault indication with Alarm. |
| 590 | The central controller will be complete including all hardware & software (including wiring) suitable to perform above function. |
| 591 | CONTROL & TRANSMISSION WIRING |
| 592 | Supply,installation,testing and commissioning of 2core X 1.5 mm² copper wire in PVC conduit as per specifications ( for transmission) |
| 593 | CABLING FOR REMOTE CONTROL |
| 594 | Supply,installation,testing and commissioning of 2core X 1.5 mm2 copper wire in PVC conduitas per specifications ( for remotes) |
| 595 | CABLE TRAY: |
| 596 | Supply and installingfollowing size of perforated painted with powder coating M.S Cable trays with perforation not more than 17.5% , in convinient sections , joined with connectors, suspended from the ceiling with M.S suspenders including bolts & nuts , painting suspenders etc as required. |
| 597 | 150mm x 50mm x 1.6 mm thick |
| 598 | Isolator |
| 599 | Providing & fixing weather proof isolator near each outdoor unit. |
| 600 | Propellar Fan |
| 601 | For Ventilation (Wall mounted Fans)Supply,installation,testing and commissioning of Wall mounted fans with motor complete in all electrical fitting all respect& offollowing capacities. |
| 602 | 250 CFM ( 5 mm static pressure) |
| 603 | 200 CFM ( 5 mm static pressure) |
| 604 | Factory Fabricated Ducting |
| 605 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete withRTV sealant & neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. |
| 606 | Thickness 0.63 mm sheet |
| 607 | Thickness 0.80 mm sheet |
| 608 | Thickness 1.00 mm sheet |
| 609 | Thickness 1.25 mm sheet |
| 610 | Site Fabricated Ducting |
| 611 | Supply, installation, balancing and commissioning of site fabricated GSS sheet metal rectangular/round ducting complete withRTV sealant & neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. |
| 612 | Thickness 0.63 mm sheet 120 GSM |
| 613 | Thickness 0.80 mm sheet120 GSM |
| 614 | Thickness 1.00 mm sheet120 GSM |
| 615 | Thickness 1.25 mm sheet120 GSM |
| 616 | G.I Volume Control Dampers (VCD) |
| 617 | Supply, installation, balancing and commissioning of G.I Volume control duct damper complete with neoprene rubber gaskets, nuts , bolts , screws linkages , flanges etc,as required. |
| 618 | Fire Dampers |
| 619 | Supply, installation, testing and commissioning of Fire Dampers in supply / main branch and return air path as andwhere required od required sizes i/c control wiring , the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored.The spring return action shall be inbuilt mechanism and not externally mounted.The damper shall also be closed in the event of fire signal complete as required and as per specifications. |
| 620 | Fire Damper |
| 621 | Actuator |
| 622 | Grilles / Diffusers |
| 623 | Supply & fixing of powder coated extruded aluminium Supply Air Grills withvolume control dampers as per specifications. |
| 624 | Supply & fixing of powder coated extruded aluminium Return Air Grills with louvers but withoutvolume control dampers as per specifications. |
| 625 | Supply , fixing , testing and commissioning ofSupply Air diffusers of powder coated aluminiumwithvolume control dampers with anti smudge ring & removable core as per specifications. |
| 626 | Supply , fixing , testing and commissioning ofReturn Air diffusers of powder coated aluminiumwithoutvolume control dampers with anti smudge ring & removable core as per specifications. |
| 627 | Supply & fixing of powder coated extruded aluminium Fresh Air / Exhasut louvers and bird screen with dampers as per specifications. |
| 628 | Duct Insulation |
| 629 | Supply & fixing of following thickness duly laminated aluminium foil of mat finish closed cell Nitrilerubber (Class \"O\") insulation on existing duct after applying suitable adhesive for Nitrile rubber.The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation, complete as per specifications and as required. |
| 630 | 19 mm |
| 631 | 25 mm |
| 632 | Duct Acoustic Lining |
| 633 | Supply & fixing of acoustic lining of supply / return air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 Kg/m³ , with 25 mm X 25 mm X 25 mm GI section of 1.25 mm thick , 600 mm centrer to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminium sheet fixed to inside surface of ducts with cadmium plated nuts ,bolts,stick pins , CPRX compound etc.complete as requiredas per specifications. |
| 634 | Canvass Connection |
| 635 | Supply & fixing of fire retardent Double canvass connection.complete in all respect including all necessary accessaries and fittings as requiredas per specifications. |
| 636 | PLUMBING |
| 637 | G.I Condensate Drain Piping |
| 638 | Supplying, fixing, testing and commissioning of condensate drain water piping of GI \"Medium\" Class complete with fittings like elbows, tees, reducers, bends, MS Flanges, supports, welding, painting etc. as required & conforming to tender specifications and of following sizes, Drain pipe shall be duly insulated with 15 mm thick polyurethen foam insulation at the joints etc. as per specifications & as required |
| 639 | 40 mm dia NB |
| 640 | 50 mm dia NB |
| 641 | UPVC Condensate Drain Piping |
| 642 | Supply, installation, testing and commissioning of drain piping of hard UPVC pipe and fittings, insulated with 12 mm thick nitrile rubber. |
| 643 | 25mm |
| 644 | 32mm |
| 645 | 40mm |
| 646 | POWER & CONTROL CABLING |
| 647 | Supplying, laying, effecting proper termination, testing & commissioning of the following POWER CABLE sizes of 1.1 KV - PVC inner sheated,extruded PVC type ST2 sheathed & Galvanised steel strips/wire as per IS 7908 (Part-I) armoured aluminium conductor cables conforming to relevant latest amended Indian Standardsas per specification standard. |
| 648 | 4 C - 10 sqmm (COPPER - PVC - UNARMOURED) |
| 649 | 4 C - 16 sqmm (COPPER - PVC - UNARMOURED) |
| 650 | 4 C - 25 sqmm (COPPER - PVC - ARMOURED) |
| 651 | 4 C - 35 sqmm(COPPER - PVC - ARMOURED) |
| 652 | 3C x 10 Sq. mm (COPPER - PVC - ARMOURED) |
| 653 | 3C x 6 Sq. mm (COPPER - PVC - ARMOURED) |
| 654 | 3C x 4 Sq. mm (COPPER - PVC - ARMOURED) |
| 655 | Earthing Strip / Wires. |
| 656 | Providing and fixing 8 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring / cable as required |
| 657 | Providing and fixing 10 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring / cable as required |
| 658 | Cable Tray |
| 659 | Supply and installingfollowing size of perforated painted with powder coating G.I Cable trays with perforation not more than 17.5% , in convinient sections , joined with connectors, suspended from the ceiling with M.S suspenders including bolts & nuts , painting suspenders etc as required. |
| 660 | 150mm x 50mm x 1.6 mm thick |
| 661 | 300 mm x 50 mm x 1.6 mm thick |
| 662 | 450 mm x 62.5 mm x 2.0 mm thick |
| 663 | 600 mm x 62.5 mm x 2.0 mm thick |
| 664 | CASSETTE SPLIT UNIT (Server / UPS Room) |
| 665 | Supply, Installation, Testing and Commissioning of Air Cooled Cassette type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), R-32/R410A/R-407 Green Refrigerant, wireless Remote, inbuilt drain pump,suitable for 400/230V, 50 Hz ,1 /3 phase AC supply, including surface /concealed copper Refrigerant piping with insulation (closed cell elastomericnitrile rubber tubular pipe section) upto 5.5 Mtr (IDU to ODU), copper power and control cable upto 5.5 Mtr (IDU to ODU) including drain pipe, the system shall be capable of performing cooling, dehumidification, Air circulation,filtration & ventilation of following capacity with Scroll/rotary compressor with min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB) as specified. The system shall be able to deliver 100% of the rated capacity as per relevant IS Code. The lab testing reports as per IS: 1391 shall be submitted from National Accreditation Board for Testing and Calibration Laboratories (NABL) accredited as per International Electro technical Commission (IEC) 17025 standards / Central Power Research Institute (CPRI)/Electrical Research and Development Association (ERDA)with Original Equipment Manufacturer (OEM) etc. complete as per CPWD specification and as per IS:1391 as required. |
| 666 | 4.0 TR star rating 5 star |
| 667 | SUB HEAD -X I I -POWER WIRING |
| 668 | INDUSTRIAL SOCKETS |
| 669 | Supplying & Installation suitable size GI box wih modular plate and cover in front on surface or in recess including providing and Installation 25 A modular socket outlet and 25 A modular SP MCB, \"C\" curve including connections, painting etc. as required. |
| 670 | Supplying and Installation 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 20 A \"C\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 671 | Supplying and Installation 32 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 32 A \"C\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 672 | Supplying and Installation 63 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 63 A \"C\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 673 | Supplying and Installation 100 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 100 A \"C\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 674 | Supplying and Installation 200 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 200 A TPMCCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 675 | Supplying and Installation 315 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 315 A TPMCCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 676 | Supplying and Installation 400 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 400 A TPMCCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 677 | Supplying and Installation 630 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 630 A TPMCCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 678 | MISCELLANEOUS ITEMS |
| 679 | Providing, laying and Installation following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. |
| 680 | 150 mm dia |
| 681 | 300 mm dia |
| 682 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 683 | 90 mm dia (OD-90 mm & ID-76 mm nominal) |
| 684 | 160 mm dia (OD-160 mm & ID-135 mm nominal) |
| 685 | Supplying and embedding following dia G.I. pipe (medium class) in pole collar/ foundation (during casting) for cable entry including bending the pipe to the required shape complete as required. |
| 686 | 40 mm dia |
| 687 | Providing, laying and Installation following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required. |
| 688 | 100 mm dia |
| 689 | 150 mm dia |
| 690 | Providing and Installation following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 691 | 100 A, 30 KA,TPMCCB |
| 692 | 125 A, 36 KA,TPMCCB |
| 693 | 200 A, 36 KA,TPMCCB |
| 694 | 315 A, 36 KA,TPMCCB |
| 695 | 630 A, 36 KA,TPMCCB |
| 696 | Supplying ofcopper conductor PVC insulated unarmoured served sheathed cable 1100 volts grade. Following size : |
| 697 | size 16 sq mm x 1 core |
| 698 | size 25 sq mm x 1 core |
| 699 | size 35 sq mm x 1 core |
| 700 | size 50 sq mm x 1 core |
| 701 | SUB HEAD -X I I I -SHOP ELECTRICAL |
| 702 | PANELS |
| 703 | AC Panel - |
| 704 | Supply, Installation, Testing & commissioning of of LT Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. Main LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar - 1600A, TPN electrolytic grade E91-E AL bus bar, 50 kA for 1 sec. |
| 705 | INCOMER - 2 Nos |
| 706 | 1250A 4P 50kA EDO ACB WITH MICROPROCESSOR RELEASE & LSING Protection - 1 Nos |
| 707 | Each incomer ACB should have below mentioned accessories as per proposed scheme |
| 708 | Under Voltage Release for ACB |
| 709 | Shunt Release for ACB |
| 710 | Mechanical Interlock using Key & Lock |
| 711 | Locking arrangement for OFF button with R - Lock (on breaker) |
| 712 | Digital Multifuncation Meter, 96Sq.mm., Class-1 with RS485 |
| 713 | Breaker Control Switch (TNC) |
| 714 | CTs - 1250/5A , 15VA , Class -1 Tape Wound for Metering |
| 715 | AUX CONTACTOR 2NO+2NC |
| 716 | 220V AC Indication LED Type (R/Y/B Phase On) |
| 717 | 240V AC Indication LED Type ( Breaker On/Off/Trip) |
| 718 | Type 2 SPD with AU MCB as Backup Protection |
| 719 | 6A DP MCB, 10kA, C-Curve |
| 720 | SP MCB, 10kA, C-Curve |
| 721 | CT Shorting Link |
| 722 | OUTGOING 315A MCCB FEEDER - 8 Nos |
| 723 | 315A 4P 36kA MCCB WITH TM RELEASE & LSI Protection |
| 724 | EXTENDED ROTARY HANDLE for 315A MCCB |
| 725 | 315A 4P SPREADER LINK |
| 726 | UPS Panel (Input Side) |
| 727 | Supply, Installation, Testing & commissioning of of UPS Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar - 630A, TPN electrolytic grade E91- E AL bus bar, 36 kA for 1 sec. |
| 728 | INCOMER from Main LT Panel - 1 Nos |
| 729 | 400A 4P 36kA MCCB WITH MICROPROCESSOR RELEASE & LSING Protection |
| 730 | EXTENDED ROTARY HANDLE for 400A MCCB |
| 731 | 400A 4P SPREADER LINK |
| 732 | MCCB AUX & TAC CONTACT |
| 733 | MFM WITH RS 485 PORT |
| 734 | 400/5A 15VA CL1 CT |
| 735 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 736 | 6A SP 10KA MCB |
| 737 | Type 2 SPD with AU MCB as Backup Protection |
| 738 | 6A DP MCB, 10kA, C-Curve |
| 739 | SP MCB, 10kA, C-Curve |
| 740 | CT Shorting Link |
| 741 | OUTGOING 400A MCCB FEEDER - 2 Nos (200KVA) |
| 742 | 400A 4P 36kA MCCB WITH MICROPROCESSOR RELEASE & LSING Protection |
| 743 | EXTENDED ROTARY HANDLE for 400A MCCB |
| 744 | 400A 4P SPREADER LINK |
| 745 | UPS Panel (Output Side-Incoming from UPS Module) |
| 746 | Supply, Installation, Testing & commissioning of of UPS Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar - 630A, TPN electrolytic grade E91- E AL bus bar, 36 kA for 1 sec. |
| 747 | INCOMER from UPS (N+1 Configuration) - 2 Nos |
| 748 | 400A 4P 36kA MCCB WITH MICROPROCESSOR RELEASE & LSING Protection |
| 749 | EXTENDED ROTARY HANDLE for 400A MCCB |
| 750 | 400A 4P SPREADER LINK |
| 751 | MCCB AUX & TAC CONTACT |
| 752 | MFM WITH RS 485 PORT |
| 753 | 400/5A 15VA CL1 CT |
| 754 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 755 | 6A SP 10KA MCB |
| 756 | Type 2 SPD with AU MCB as Backup Protection |
| 757 | 6A DP MCB, 10kA, C-Curve |
| 758 | SP MCB, 10kA, C-Curve |
| 759 | CT Shorting Link |
| 760 | OUTGOING 63A MCCB FEEDER - 10 Nos |
| 761 | 63A 4P 18kA MCCB WITH MICROPROCESSOR RELEASE & LSING Protection |
| 762 | EXTENDED ROTARY HANDLE for 18A MCCB |
| 763 | 63A 4P SPREADER LINK |
| 764 | UPS Panel - |
| 765 | Supply, Installation, Testing & commissioning of of LT Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar - 125A, TPN electrolytic grade E91- E AL bus bar, 25 kA for 1 sec. |
| 766 | INCOMER from Main LT Panel - 1 Nos |
| 767 | 100A 4P 25kA MCCB WITH WITH TM RELEASE & LSI Protection |
| 768 | EXTENDED ROTARY HANDLE for 100A MCCB |
| 769 | 100A 4P SPREADER LINK |
| 770 | MCCB AUX & TAC CONTACT |
| 771 | MFM WITH RS 485 PORT |
| 772 | 100A/5A 15VA CL1 CT |
| 773 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 774 | 6A SP 10KA MCB |
| 775 | Type 2 SPD with AU MCB as Backup Protection |
| 776 | 6A DP MCB, 10kA, C-Curve |
| 777 | SP MCB, 10kA, C-Curve |
| 778 | CT Shorting Link |
| 779 | OUTGOING 100A MCCB FEEDER - 2 Nos (40KVA) |
| 780 | 100A 4P 25 kA MCCB WITH TM RELEASE & LSI Protection |
| 781 | EXTENDED ROTARY HANDLE for 100A MCCB |
| 782 | 100A 4P SPREADER LINK |
| 783 | Ventilation Panel - (Basement) |
| 784 | Supply, Installation, Testing & commissioning of of LT Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar - 630 A, TPN electrolytic grade E91- E AL bus bar, 35 kA for 1 sec. |
| 785 | INCOMER from Main LT Panel ESS - 1 Nos |
| 786 | 400A 4P 36kA MCCB WITH TM RELEASE & LSI Protection |
| 787 | EXTENDED ROTARY HANDLE for 400A MCCB |
| 788 | 400A 4P SPREADER LINK |
| 789 | MCCB AUX & TAC CONTACT |
| 790 | MFM WITH RS 485 PORT |
| 791 | 400A/5A 15VA CL1 CT |
| 792 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 793 | 6A SP 10KA MCB |
| 794 | Type 2 SPD with AU MCB as Backup Protection |
| 795 | 6A DP MCB, 10kA, C-Curve |
| 796 | SP MCB, 10kA, C-Curve |
| 797 | CT Shorting Link |
| 798 | OUTGOING 150A MCCB FEEDER - 1 Nos |
| 799 | 150A 4P 25 kA MCCB WITH TM RELEASE & LSI Protection |
| 800 | EXTENDED ROTARY HANDLE for 150A MCCB |
| 801 | 150A 4P SPREADER LINK |
| 802 | OUTGOING 125A MCCB FEEDER - 2 Nos |
| 803 | 125A 4P 25 kA MCCB WITH TM RELEASE & LSI Protection |
| 804 | EXTENDED ROTARY HANDLE for 125A MCCB |
| 805 | 125A 4P SPREADER LINK |
| 806 | OUTGOING 63A MCCB FEEDER - 2 Nos |
| 807 | 63A 4P 18 kA MCCB WITH TM RELEASE & LSI Protection |
| 808 | EXTENDED ROTARY HANDLE for 63A MCCB |
| 809 | 63A 4P SPREADER LINK |
| 810 | Sub-Panel AC & Pressurization - (Terrace) |
| 811 | Supply, Installation, Testing & commissioning of of LT Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar - 500A, TPN electrolytic grade E91-E AL bus bar, 36 kA for 1 sec. ( each panel per Floor) |
| 812 | INCOMER from Main LT Panel ESS - 1 Nos |
| 813 | 315A 4P 36kA MCCB WITH TM RELEASE & LSI Protection |
| 814 | EXTENDED ROTARY HANDLE for 315A MCCB |
| 815 | 315A 4P SPREADER LINK |
| 816 | MCCB AUX & TAC CONTACT |
| 817 | MFM WITH RS 485 PORT |
| 818 | 315A/5A 15VA CL1 CT |
| 819 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 820 | 6A SP 10KA MCB |
| 821 | Type 2 SPD with AU MCB as Backup Protection |
| 822 | 6A DP MCB, 10kA, C-Curve |
| 823 | SP MCB, 10kA, C-Curve |
| 824 | CT Shorting Link |
| 825 | OUTGOING 150A MCCB FEEDER - 1 Nos |
| 826 | 150 A 4P 25kA MCCB WITH TM RELEASE & LSI Protection |
| 827 | EXTENDED ROTARY HANDLE for 150A MCCB |
| 828 | 150A 4P SPREADER LINK |
| 829 | OUTGOING 125A MCCB FEEDER - 2 Nos |
| 830 | 100A 4P 25kA MCCB WITH TM RELEASE & LSI Protection |
| 831 | EXTENDED ROTARY HANDLE for 100A MCCB |
| 832 | 100A 4P SPREADER LINK |
| 833 | OUTGOING 63A MCCB FEEDER - 3 Nos |
| 834 | 63A 4P 18kA MCCB WITH TM RELEASE & LSI Protection |
| 835 | EXTENDED ROTARY HANDLE for 63A MCCB |
| 836 | 63A 4P SPREADER LINK |
| 837 | Equipment Power Panel - |
| 838 | Supply, Installation, Testing & commissioning of of LT Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar -1250A, TPN electrolytic grade E91-E AL bus bar, 50 kA for 1 sec. |
| 839 | INCOMER from Main LT Panel ESS - 1 Nos |
| 840 | 1000A 4P 50kA EDO ACB WITH MICROPROCESSOR RELEASE & LSING Protection |
| 841 | Under Voltage Release for ACB |
| 842 | Shunt Release for ACB |
| 843 | Breaker Control Switch (TNC) |
| 844 | 220V AC Indication LED Type (R/Y/B Phase On) |
| 845 | 240V AC Indication LED Type ( Breaker On/Off/Trip) |
| 846 | 6A DP MCB, 10kA, C-Curve |
| 847 | SP MCB, 10kA, C-Curve |
| 848 | Neutral Shorting Link |
| 849 | Digital MFM WITH RS 485 PORT |
| 850 | 1000/5A 15VA CL1 CT |
| 851 | OUTGOING 630A MCCB FEEDER - 1 Nos |
| 852 | 200A 4P 25 kA MCCB WITH TM RELEASE & LSI Protection |
| 853 | EXTENDED ROTARY HANDLE for 200A MCCB |
| 854 | 200A 4P SPREADER LINK |
| 855 | OUTGOING 400A MCCB FEEDER - 2 Nos |
| 856 | 200A 4P 25 kA MCCB WITH TM RELEASE & LSI Protection |
| 857 | EXTENDED ROTARY HANDLE for 200A MCCB |
| 858 | 200A 4P SPREADER LINK |
| 859 | OUTGOING 315A MCCB FEEDER - 2 Nos |
| 860 | 200A 4P 25 kA MCCB WITH TM RELEASE & LSI Protection |
| 861 | EXTENDED ROTARY HANDLE for 200A MCCB |
| 862 | 200A 4P SPREADER LINK |
| 863 | OUTGOING 200A MCCB FEEDER - 3 Nos |
| 864 | 200A 4P 25 kA MCCB WITH TM RELEASE & LSI Protection |
| 865 | EXTENDED ROTARY HANDLE for 200A MCCB |
| 866 | 200A 4P SPREADER LINK |
| 867 | OUTGOING 125A MCCB FEEDER - 2 Nos |
| 868 | 125A 4P 25 kA MCCB WITH TM RELEASE & LSI Protection |
| 869 | EXTENDED ROTARY HANDLE for 125A MCCB |
| 870 | 125A 4P SPREADER LINK |
| 871 | OUTGOING 100A MCCB FEEDER - 2 Nos |
| 872 | 100A 4P 25 kA MCCB WITH TM RELEASE & LSI Protection |
| 873 | EXTENDED ROTARY HANDLE for 100A MCCB |
| 874 | 100A 4P SPREADER LINK |
| 875 | OUTGOING 63A MCCB FEEDER - 4 Nos |
| 876 | 63A 4P 18 kA MCCB WITH TM RELEASE & LSI Protection |
| 877 | EXTENDED ROTARY HANDLE for 63A MCCB |
| 878 | 63A 4P SPREADER LINK |
| 879 | Main Lighting Panel |
| 880 | Supply, Installation, Testing & commissioning of of LT Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar - 630A, TPN electrolytic grade E91-E AL bus bar, 36 kA for 1 sec. |
| 881 | INCOMER from Main LT Panel ESS - 1 Nos |
| 882 | 400A 4P 36kA MCCB WITH TM RELEASE & LSI Protection |
| 883 | EXTENDED ROTARY HANDLE for 400A MCCB |
| 884 | 400A 4P SPREADER LINK |
| 885 | MCCB AUX & TAC CONTACT |
| 886 | MFM WITH RS 485 PORT |
| 887 | 400A/5A 15VA CL1 CT |
| 888 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 889 | 6A SP 10KA MCB |
| 890 | Type 2 SPD with AU MCB as Backup Protection |
| 891 | 6A DP MCB, 10kA, C-Curve |
| 892 | SP MCB, 10kA, C-Curve |
| 893 | CT Shorting Link |
| 894 | OUTGOING 100A MCCB FEEDER - 2 Nos |
| 895 | 100A 4P 25 kA MCCB WITH TM RELEASE & LSI Protection |
| 896 | EXTENDED ROTARY HANDLE for 100A MCCB |
| 897 | 100A 4P SPREADER LINK |
| 898 | OUTGOING 63A MCCB FEEDER - 6 Nos |
| 899 | 63A 4P 18 kA MCCB WITH TM RELEASE & LSI Protection |
| 900 | EXTENDED ROTARY HANDLE for 63A MCCB |
| 901 | 63A 4P SPREADER LINK |
| 902 | Lighting Floor Sub-Panel - 1 |
| 903 | Supply, Installation, Testing & commissioning of of LT Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar - 150A, TPN electrolytic grade E91-E AL bus bar, 25 kA for 1 sec. |
| 904 | INCOMER from Main Lighting Panel - 1 Nos |
| 905 | 100A 4P 25kA MCCB WITH TM RELEASE & LSI Protection |
| 906 | EXTENDED ROTARY HANDLE for 100A MCCB |
| 907 | 100A 4P SPREADER LINK |
| 908 | MCCB AUX & TAC CONTACT |
| 909 | MFM WITH RS 485 PORT |
| 910 | 100A/5A 15VA CL1 CT |
| 911 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 912 | 6A SP 10KA MCB |
| 913 | Type 2 SPD with AU MCB as Backup Protection |
| 914 | 6A DP MCB, 10kA, C-Curve |
| 915 | SP MCB, 10kA, C-Curve |
| 916 | CT Shorting Link |
| 917 | OUTGOING 40A MCB FEEDER - 5 Nos |
| 918 | 40A 4P 10 kA MCB with Mechanical Shortcircuit Flag Indication |
| 919 | Lighting Floor Sub-Panel - 2 |
| 920 | Supply, Installation, Testing & commissioning of of LT Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar - 100A, TPN electrolytic grade E91-E AL bus bar, 25 kA for 1 sec. |
| 921 | INCOMER from Main Lighting Panel - 1 Nos |
| 922 | 63A 4P 18kA MCCB WITH TM RELEASE & LSI Protection |
| 923 | EXTENDED ROTARY HANDLE for 63A MCCB |
| 924 | 63A 4P SPREADER LINK |
| 925 | MCCB AUX & TAC CONTACT |
| 926 | MFM WITH RS 485 PORT |
| 927 | 63A/5A 15VA CL1 CT |
| 928 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 929 | 6A SP 10KA MCB |
| 930 | Type 2 SPD with AU MCB as Backup Protection |
| 931 | 6A DP MCB, 10kA, C-Curve |
| 932 | SP MCB, 10kA, C-Curve |
| 933 | CT Shorting Link |
| 934 | OUTGOING 40A MCB FEEDER - 4 Nos |
| 935 | 40A 4P 10 kA MCB with Mechanical Shortcircuit Flag Indication |
| 936 | Power Floor Panel |
| 937 | Supply, Installation, Testing & commissioning of of LT Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar - 400A, TPN electrolytic grade E91-E AL bus bar, 36 kA for 1 sec. |
| 938 | INCOMER from Main Lighting Panel - 1 Nos |
| 939 | 250A 4P 36kA MCCB WITH TM RELEASE & LSI Protection |
| 940 | EXTENDED ROTARY HANDLE for 250A MCCB |
| 941 | 250A 4P SPREADER LINK |
| 942 | MCCB AUX & TAC CONTACT |
| 943 | MFM WITH RS 485 PORT |
| 944 | 250A/5A 15VA CL1 CT |
| 945 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 946 | 6A SP 10KA MCB |
| 947 | Type 2 SPD with AU MCB as Backup Protection |
| 948 | 6A DP MCB, 10kA, C-Curve |
| 949 | SP MCB, 10kA, C-Curve |
| 950 | CT Shorting Link |
| 951 | OUTGOING 125A MCCB FEEDER - 2 Nos |
| 952 | 125A 4P 25 kA MCCB WITH TM RELEASE & LSI Protection |
| 953 | EXTENDED ROTARY HANDLE for 125A MCCB |
| 954 | 125A 4P SPREADER LINK |
| 955 | OUTGOING 63A MCB FEEDER - 8 Nos |
| 956 | 63A 4P 10 kA MCB with Mechanical Shortcircuit Flag Indication |
| 957 | Lift Panel (G+P-1) |
| 958 | Supply, Installation, Testing & commissioning of of LT Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar - 200A, TPN electrolytic grade E91-E AL bus bar, 25 kA for 1 sec. |
| 959 | INCOMER from Main LT Panel ESS - 1 Nos |
| 960 | 150A 4P 25kA MCCB WITH TM RELEASE & LSI Protection |
| 961 | EXTENDED ROTARY HANDLE for 150A MCCB |
| 962 | 150A 4P SPREADER LINK |
| 963 | MCCB AUX & TAC CONTACT |
| 964 | MFM WITH RS 485 PORT |
| 965 | 150A/5A 15VA CL1 CT |
| 966 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 967 | 6A SP 10KA MCB |
| 968 | Type 2 SPD with AU MCB as Backup Protection |
| 969 | 6A DP MCB, 10kA, C-Curve |
| 970 | SP MCB, 10kA, C-Curve |
| 971 | CT Shorting Link |
| 972 | OUTGOING 100A MCCB FEEDER - 1 Nos |
| 973 | 100A 4P 25 kA MCCB WITH TM RELEASE & LSI Protection |
| 974 | EXTENDED ROTARY HANDLE for 100A MCCB |
| 975 | 100A 4P SPREADER LINK |
| 976 | OUTGOING 63A MCCB FEEDER - 1 Nos |
| 977 | 63A 4P 18 kA MCCB WITH TM RELEASE & LSI Protection |
| 978 | EXTENDED ROTARY HANDLE for 63A MCCB |
| 979 | 63A 4P SPREADER LINK |
| 980 | Lift Panel (G+P-2) |
| 981 | Supply, Installation, Testing & commissioning of of LT Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar - 250A, TPN electrolytic grade E91-E AL bus bar, 25 kA for 1 sec. |
| 982 | INCOMER from Main LT Panel ESS - 1 Nos |
| 983 | 200A 4P 25kA MCCB WITH TM RELEASE & LSI Protection |
| 984 | EXTENDED ROTARY HANDLE for 200A MCCB |
| 985 | 200A 4P SPREADER LINK |
| 986 | MCCB AUX & TAC CONTACT |
| 987 | MFM WITH RS 485 PORT |
| 988 | 200A/5A 15VA CL1 CT |
| 989 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 990 | 6A SP 10KA MCB |
| 991 | Type 2 SPD with AU MCB as Backup Protection |
| 992 | 6A DP MCB, 10kA, C-Curve |
| 993 | SP MCB, 10kA, C-Curve |
| 994 | CT Shorting Link |
| 995 | OUTGOING 100A MCCB FEEDER - 1 Nos |
| 996 | 100A 4P 25 kA MCCB WITH TM RELEASE & LSI Protection |
| 997 | EXTENDED ROTARY HANDLE for 100A MCCB |
| 998 | 100A 4P SPREADER LINK |
| 999 | OUTGOING 63A MCCB FEEDER - 2 Nos |
| 1000 | 63A 4P 18 kA MCCB WITH TM RELEASE & LSI Protection |
| 1001 | EXTENDED ROTARY HANDLE for 63A MCCB |
| 1002 | 63A 4P SPREADER LINK |
| 1003 | Lift Panel (P+P-1) |
| 1004 | Supply, Installation, Testing & commissioning of of LT Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar - 125A, TPN electrolytic grade E91-E AL bus bar, 25 kA for 1 sec. |
| 1005 | INCOMER from Main LT Panel ESS - 1 Nos |
| 1006 | 100A 4P 25kA MCCB WITH TM RELEASE & LSI Protection |
| 1007 | EXTENDED ROTARY HANDLE for 100A MCCB |
| 1008 | 100A 4P SPREADER LINK |
| 1009 | MCCB AUX & TAC CONTACT |
| 1010 | MFM WITH RS 485 PORT |
| 1011 | 100A/5A 15VA CL1 CT |
| 1012 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 1013 | 6A SP 10KA MCB |
| 1014 | Type 2 SPD with AU MCB as Backup Protection |
| 1015 | 6A DP MCB, 10kA, C-Curve |
| 1016 | SP MCB, 10kA, C-Curve |
| 1017 | CT Shorting Link |
| 1018 | OUTGOING 63A MCCB FEEDER - 2 Nos |
| 1019 | 63A 4P 18 kA MCCB WITH TM RELEASE & LSI Protection |
| 1020 | EXTENDED ROTARY HANDLE for 63A MCCB |
| 1021 | 63A 4P SPREADER LINK |
| 1022 | Outdoor Feeder Panel - |
| 1023 | Supply, Installation, Testing & commissioning of of LT Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar - 200A, TPN electrolytic grade E91-E AL bus bar, 25 kA for 1 sec. |
| 1024 | INCOMER from Main LT Panel ESS - 1 Nos |
| 1025 | 150A 4P 25kA MCCB WITH TM RELEASE & LSI Protection |
| 1026 | EXTENDED ROTARY HANDLE for 150A MCCB |
| 1027 | 150A 4P SPREADER LINK |
| 1028 | MCCB AUX & TAC CONTACT |
| 1029 | MFM WITH RS 485 PORT |
| 1030 | 150A/5A 15VA CL1 CT |
| 1031 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 1032 | 6A SP 10KA MCB |
| 1033 | Type 2 SPD with AU MCB as Backup Protection |
| 1034 | 6A DP MCB, 10kA, C-Curve |
| 1035 | SP MCB, 10kA, C-Curve |
| 1036 | CT Shorting Link |
| 1037 | OUTGOING 63A MCB FEEDER - 2 Nos |
| 1038 | 63A 4P 10 kA MCB with Mechanical Shortcircuit Flag Indication |
| 1039 | OUTGOING 40A MCB FEEDER - 6 Nos |
| 1040 | 40A 4P 10 kA MCB with Mechanical Shortcircuit Flag Indication |
| 1041 | ARMOURED CABLES : |
| 1042 | Supplying ofaluminium conductor PVC insulated and PVC sheathed / XLPE aluminium armoured served conductor cable of 1.1 KV grade as required. Following size : |
| 1043 | size 6 sq mm x 2 core |
| 1044 | size 10 sq mm x 2 core |
| 1045 | size 6 sq mm x 4 core |
| 1046 | size 10 sq mm x 4 core |
| 1047 | size 16 sq mm x 4 core |
| 1048 | size 25 sq mm x 3-1/2core |
| 1049 | size 35 sq mm x 3-1/2core |
| 1050 | size 50 sq mm x 3-1/2core |
| 1051 | size 70 sq mm x 3-1/2core |
| 1052 | size 95sq mm x 3-1/2core |
| 1053 | size 120 sq mm x 3-1/2core |
| 1054 | size 150 sq mm x 3-1/2core |
| 1055 | size 185 sq mm x 3-1/2core |
| 1056 | size 240 sq mm x 3-1/2core |
| 1057 | size 300 sq mm x 3-1/2core |
| 1058 | size 400 sq mm x 3-1/2core |
| 1059 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 1060 | 2 X 6 sq. mm (19mm) |
| 1061 | 2 X 10 sq. mm (19mm) |
| 1062 | 4 X 6 sq. mm (22mm) |
| 1063 | 4 X 10 sq. mm (25mm) |
| 1064 | 4 X 16 sq. mm (28mm) |
| 1065 | 3½ X 25 sq. mm (28mm) |
| 1066 | 3½ X 35 sq. mm (32mm) |
| 1067 | 3½ X 50 sq. mm (35mm) |
| 1068 | 3½ X 70 sq. mm (38mm) |
| 1069 | 3½ X 95 sq. mm (45mm) |
| 1070 | 3½ X 120 sq. mm (45mm) |
| 1071 | 3½ X 150 sq. mm (50mm) |
| 1072 | 3½ X 185 sq. mm (57mm) |
| 1073 | 3½ X 240 sq. mm (62mm) |
| 1074 | 3½ X 300 sq. mm (70mm) |
| 1075 | 3½ X 400 sq. mm (82mm) |
| 1076 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 1077 | Above 95 sq. mm and upto 185 sq. mm |
| 1078 | Above 185 sq. mm and upto 400 sq. mm |
| 1079 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 1080 | Above 95 sq. mm and upto 185 sq. mm |
| 1081 | Above 185 sq. mm and upto 400 sq. mm |
| 1082 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. |
| 1083 | Above 95 sq. mm and upto 185 sq. mm |
| 1084 | Above 185 sq. mm and upto 400 sq. mm |
| 1085 | Laying and Installation of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 1086 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 1087 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 1088 | Laying and Installation of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 1089 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 1090 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 1091 | Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
| 1092 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 1093 | Supplying and Installation cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and Installation the same in ground as required. |
| 1094 | Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 1095 | 3½ X 25 sq. mm |
| 1096 | 3½ X 35 sq. mm |
| 1097 | 3½ X 50 sq. mm |
| 1098 | 4 X 16 sq. mm |
| 1099 | Supply & Installation of aluminium base mount trefoil cable cleats two bolts (SS 304) are extensively used in electrical installations to securely fasten and support cables. These cleats are specifically designed for use with aluminium cables, offering reliable and robust cable management solutions. (Suitable for use with cable diameters 15 to 130 mm.) In accordance with BS EN 61914:2009. Operating temperature -60°C to +105°C |
| 1100 | 15-30mm |
| 1101 | 45-60mm |
| 1102 | 105-130mm |
| 1103 | SUB HEAD -X I V -SPECIAL EARTHING |
| 1104 | Earthing Work : |
| 1105 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 1106 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 1107 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. |
| 1108 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 1109 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 1110 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 1111 | Providing and Installation 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 1112 | Providing and Installation 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 1113 | Providing and Installation 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 1114 | Providing and Installation earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required. |
| 1115 | Supply, Installation, Testing and Commisioning of 12 terminal positions copper earth bus bar including mounting accessories complete in all respet. |
| 1116 | Supply, Installation, Testing and Commisioning of 12 terminal positions GI earth bus bar including mounting accessories complete in all respet. |
| 1117 | SUB HEAD -X V-U.P.S WIRING |
| 1118 | Online UPS- Input Supply: Industrial Type |
| 1119 | Supplying, installation, Testing & Commissioning of of following capacity at full load (Unity Power Factor) at operating temperature 0 to 40 deg C, Relative humidity 0 to 95%, Online double conversion true sine wave Uninterrupted hot swappable (allow for the replacement or addition of battery modules without shutting down the entire system) modular Power Supply (UPS) system with N+1 modules (N denotes total number of moduels requird for rated capacity). The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch alongwith provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. UPS shall have inbuilt phase sequence correction. The UPS systems offered are to be of the latest technology with Digital Control Microprocessor based for reliable operation using Insulated Gate Bipolar Transistor (IGBT)\"s both for the rectifier & inverter (3 Level) with PWM (Pulse Width Modulation). The quality of design, manufacturing and inspection process should confirm to the relevant International standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >96% while operating on battery mode and delivering quality power to the 100% non-linear loads. |
| 1120 | Current total harmonic effect(ITHD) on the input grid shall be < 5% at 50 %load. (The required LC (inductor (L) and a capacitor (C)) filters shall be included in UPS cost), extreme power factor kit to be included to limit the input power factor (PF) to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ), however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC : 3Phase 400V +/-20%, 50 Hz +/-5 Hz, AC Output voltage: 3Phase 415 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins, Sine wave output. Non condensing, noise level less than 60db at 1 meter distance, protections: Input Under voltage over voltage, abnormal out voltage, battery over charging, output over current, short circuit protection, battery deep discharge protection, 10KV surge. UPS must comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI)-type UPS. Communication RS232/RS485/SNMP port open protocol for BMS integration, all hardware & software for iOT Communication as per approved by Engineering in charge. Required battery racks and interconnecting copper conductor cables of suitable size and connectors and all required accoseries are inclusive of the cost). This system must provide a means for logging and alarming of all monitored points plus email notification. Forced air-cooling with integral inbuilt fans with redundancy (if one fan fail UPS should be able to handle at least 80% of the load, Noise Level 65 DB at 1 meter distance. The system shall be in compliance IEC 62040- 1,2 & 3, IS:16242 and CPWD Specification. |
| 1121 | Display Panel (minimum) (In-build 5 inch or more LC Display / LED ) to display : a) Input: Voltage, current, Frequency. b) Bypass: Voltage, Frequency. c) Output: Voltage, frequency, Current.d) Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage. f)Temperature: STS, Inverter, PFC. g) Event Logging & Statistical Data (On LCD/LED): UPS should capture and display up to 3000 events like: Over temperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-circuit / Device Fail / Inverter Fail / Rectifier Fail / Bypass Fail, etc. h) Statistical Data: No. of power failures / Transfers to Bypass / Total Running time, etc. i) Mains Mode of Operation /Battery Mode of Operation / Bypass feeding the load /UPS Fault /Battery charging and discharging, overload, battery voltage and battery capacity. j) Audible Alarms : Mains Failure, Battery Low Alarm, UPS Overload, Fault, Shutdown, Input Over, Under Voltage, Output Over, Under Voltage, Battery Over, Under Voltage, Over Load and short circuit, Over Temperature. The UPS should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location etc. |
| 1122 | 40KVA/384V 3Phase Input and 3Phase output with isolation transformer based industrial online UPS for 15 Min Battery Backup with 12V-65Ah SMF Battery, Battery Stand, Interlinks & Battery Breaker etc. |
| 1123 | 200KVA/384V 3Phase Input and 3Phase output with isolation transformer based industrial online UPS for 15 Min Battery Backup with 12V-200Ah SMF Battery, Battery Stand, Interlinks & Battery Breaker etc. |
| 1124 | SUB HEAD -X V I -LIGHTING PROTECTION |
| 1125 | Lighting Conductor : |
| 1126 | Providing and Installation of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. Complete as required. |
| 1127 | Installation &supply of lightning conductor finial (single prong) with base plate including holes etc. complete as required. |
| 1128 | Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. |
| 1129 | Providing and Installation 8mm dia solid round aluminium conductor on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) including clamp ,screws,coupler and all required accessories. complying IEC :62561 |
| 1130 | Providing and Installation 8mm dia solid round aluminium conductor on parapet or on surface of wall for lightning conductor complete as required. (For vertical run) including clamp ,screws,coupler and all required accessories. |
| 1131 | Providing and Installation testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. |
| 1132 | Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required. |
| 1133 | SUB HEAD -X V I I -TELEPHONE & LAN |
| 1134 | DATA & LAN NETWORKING (I/N CCTV WIRING) |
| 1135 | Supplying, installation, Testing and commissioning of following capacity 8 port PoE Layer 2 Industrial Grade outdoor Network Switch having features and specifications etc. as mentioned here under: At least 8 X RJ-45 PoE/PoE+ Gigabit Ethernet Ports and additional 4 X 1G SFP Ports with non-blocking architecture by having Switching capacity of min. 24Gbps and packet forwarding rate of 17Mpps or higher, console port, 16K MAC table, IPv4 and IPv6 ready, IGMP snooping v1, v2, v3, DHCP,DHCP Relay, NTP/SNTP, SNMPv1, v2 C v3, TELNET/ SSH, LACP, STP, RSTP, MSTP, ERPS. VLAN: Port based, Mac based, IP subnet based, tag based, protocol based. Ǫ-in Ǫ, L2/L3 ACL, 1588v2 Precision Time Protocol HWBased E2E Transparent clock, SNTP, TFTP, SNMP, Radius, Syslog. Dual DC Power input, IP30 rated, DIN Rail, -40° to 70° C operating temperature. Certificate: UL, CE, FCC, NEMA-TS2, IEC/MIL-STD for Shock, Vibration & Drop Certificate. OEM Should have Certificate for Industrial Cyber Security Capability IEC-62443-4-1:2018, ISO 45001, ISO 27001 and ISO 14001 Certified or Equivelent Indian Certificate. OEM/Product must be on Trusted Telecom Portal of Department of Telecommunication, Government of India. |
| 1136 | Supplying, installation, Testing and commissioning of following capacity 24 port Layer 2 indoor Network Switch having features and specifications etc. as mentioned here under: At least 24 X RJ-45 Gigabit Ethernet Ports and additional 2 X 10G Base -T with 4 X SFP Ports with non-blocking architecture by having Switching capacity of min. 168Gbps and packet forwarding rate of 125Mpps or higher, 16K MAC table. Console Port, USB port, Stacking support of min. 9 units per stack. Internal dual AC Power supply, STP, RSTP, MSTP, BPDU Filter, BPDU Restriction, Min. 9K Jumbo Frame, LBD, IGMP Snooping V1/V2/V3, MLD Snopping V1/V2. IGMP /MLD Groups 1K or more, IPv4/IPv6 Loopback Interface, 16 L3 IP Interface, Ipv6 ND, VRRPv3, UDP Helper, ECMP. VLAN: 802.1Ǫ, Port based, Ǫ-in-Ǫ, Multicast VLAN, Protocol VLAN, VLAN Trunking, DHCP Snopping, Server, server Screening. RADIUS , TACACS+ Authentication, ǪoS: 802.1P, 8 queues per port, ǪoS : WRR, Strict+WRR, WRED, 802.1p. ACL: MAC based, IPv4C IPv6, TCP/UDP Port number, time based ACL, TFTP Client, SNMP V1, v2c, v3, SNMP traps, RMON, DHCP server, relay, client, LLDP, LLDP-MED, OAM, Dying Gasp, 802.3ah, sflow, RIP, OSPF v2/v3, policy based route, SSL, SSH. 6 kV surge protection on all Gigabit Ethernet ports and on all GE RJ-45 access ports. Certifications: UL, CE, FCC, RoHS, MTCTE, OEM/Product must be on Trusted Telecom Portal of Department of Telecommunication, Government of India. |
| 1137 | Supplying Installation Testing and Commissioning of 24 port Cat6 Patch Panel loaded. Must be of 1U height with clear label holders and white label with the panel. 24 Ports Cat-6 Patch Panel should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required. |
| 1138 | Supplying, Installation, Testing and commissioning of following CAT6A Patch Cord should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D |
| 1139 | Copper Patch Cords of length 1m (3ft) |
| 1140 | Copper Patch Cords of length 3m (10ft) |
| 1141 | Supplying, Installation, Testing and commissioning of CAT6A Copper Information Outlet (IO) with face plate of color as per site requirement, should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D. All copper Cable and Components should be from same OEM to maintain compatibility and interopertability. |
| 1142 | Supplying, Installation, Testing and commissioning of RJ45 Connector for CAT 6/6A Cables. RJ45 modular plug supports 4 twisted pairs, 8 positions, 8 connectors. Housing: PC, UL94V-2, transparent color. Use for 24- 26 AWG stranded wires. |
| 1143 | Supplying, drawing, Testing and commissioning of Cat6A UTP 4 pair, 23 AWG solid copper cable in existing conduit/ on surface, U/FTP, LSZH, Non-Plenum, Horizontal (solid) Cable suitable for high speed data networking application supporting upto 10Gbps over a 100 meter channel. The 4 Unshielded Twisted Pairs (UTP) cable with color coded insulation for easy indentification should have FLAME PROPERTIES i.e. Flammability Test - IEC 60332-1, Smoke Density - IEC 61034, LSZH standards compliance: ANSI/TIA-568 C.2, ISO/IEC 11801, IEEE 802.3an, RoHS. Delay Skew should be < 45NS. The outer Cable Diameter should be 7.5 + 2 mm. Cable should have been tested and verified by UL/ ETL etc. complete as required. |
| 1144 | Supplying and Installation of following size Wall Mount Rack having Fixed Structure with 0.8mm CRCA Sheet, completely knockeddown condition (CKD) Shape, Vertical Mounting Rail 1.6 mm with \"U\"Marking, Minimum 2 cable entry/exit provision at Top and bottom with rubber protection, Front 5mm Toughened Glass with lock, wall mounting kit, Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required. |
| 1145 | 6U Rack |
| 1146 | 15U Rack |
| 1147 | Supplying and Installation of 25mm dia of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 1148 | TELEPHONE NETWORKING |
| 1149 | Supply, Installation, Testing & Commissioning of 20 Pair Krone Box Module. |
| 1150 | Supply, Installation, Testing & Commissioning of 100 Pair Krone Box Module. |
| 1151 | Supplying and laying of FRLS PVC Insulated annealed copper conductor 20 pair Armoured Telephone cable etc. complete as reqd. |
| 1152 | Supplying and laying of FRLS PVC Insulated annealed copper conductor 100 pair Armoured Telephone cable etc. complete as reqd. |
| 1153 | Supplyinganddrawing2 pair0.5 mmdia FRLS PVCinsulated annealed copperconductor, unarmoredtelephonecableintheexistingsurface/recessed steel/ PVC conduit as required. |
| 1154 | Supplying and Installation of 25mm dia of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 1155 | SUB HEAD -X V I I I-FIRE ALARM SYSTEM |
| 1156 | Intelligent (Addressable) Fire Alarm System : |
| 1157 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System)and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
| 1158 | Ten Loop |
| 1159 | Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required. |
| 1160 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reSet, acknowledge and silence switches complete as required. |
| 1161 | Supplying, installation, testing & commissioningof intelligent analog addressable photothermal (Smoke) detector complete with mounting base complete as required. |
| 1162 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
| 1163 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 1164 | Supplying, installation, testing & commissioning of intelligent addressable thermal detectorwith rate of rise cum fixed tempreature thermistor complete with base as required. |
| 1165 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
| 1166 | Supplying, installation, testing & commissioning of addressable phone control module complete as required. |
| 1167 | Supplying, installation, testing & commissioning of addressable beam detector with short circuit isolator (inbuilt or seperate) complete with emitter and receiver including connections with remote test features etc complete as required. |
| 1168 | Supplying, installation, testing & commissioning of intelligent addressable duct detector including suitable Photo detector complete with base as required. |
| 1169 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 1170 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
| 1171 | Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required. |
| 1172 | Supplying, installation, testing & commissioning of fire fighter phone jack complete as required. |
| 1173 | SUB HEAD -X I X -FIRE FIGHTING SYSTEM |
| 1174 | FIRE BUCKET & ESTINGUISHERS |
| 1175 | Supply & fixing of 4 nos. G.I.round bottom fire buckets of 9 liters capacity filled with sand including proper supporting / mounting arrangements in MS angle iron frame, painted by fire red colour over two coats of red oxide paint and written with white paint \"FIRE\" complete in all respects as per the directions ofEngineer-in-charge. |
| 1176 | Supply & erection of ISI marked portable fire extinguishers, confirming to IS:15683, wall mounted type, wall brackets complete in all respect as per standard item with all accessories, delivery hose & nozzle whereever required, including fixing on walls as per the directions ofEngineer-in-charge. |
| 1177 | CO2 gas type. 4.5 kg. capacity |
| 1178 | ABC dry powder Type 6 kg. capacity |
| 1179 | Supply & erection of ISI marked portable Fire Ball, wall mounted type, wall brackets complete in all respect as per standard item with all accessories, including fixing on walls as per the directions of Engineer-in-charge. |
| 1180 | PIPES & ACCESSORIES |
| 1181 | Providing, laying, testing & commissioning of \"C\" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 1182 | 25 mm dia |
| 1183 | 32 mm dia |
| 1184 | 40 mm dia |
| 1185 | 50 mm dia |
| 1186 | 65 mm dia |
| 1187 | 80 mm dia |
| 1188 | 100 mm dia |
| 1189 | 150 mm dia |
| 1190 | 200 mm dia |
| 1191 | Providing, fixing, testing & commissioning of 15 mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories. |
| 1192 | Pendent Sprinkler |
| 1193 | Upright Sprinkler |
| 1194 | Horizontal Size Wall Sprinkler |
| 1195 | FIRE HYDRANTS & ACCESSORIES |
| 1196 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling & Cast Iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : |
| 1197 | Single Headed Gunmetal |
| 1198 | Supplying and fixing single headed external yard hydrant valve with instantaneous Gunmetal/Stainless Steel coupling & Cast Iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : |
| 1199 | Single Headed Gunmetal |
| 1200 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : |
| 1201 | 80 mm dia |
| 1202 | 100 mm dia |
| 1203 | 150 mm dia |
| 1204 | 200 mm dia |
| 1205 | 250 mm dia |
| 1206 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 1207 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : |
| 1208 | 80 mm dia |
| 1209 | 100 mm dia |
| 1210 | 150 mm dia |
| 1211 | 200 mm dia |
| 1212 | 250 mm dia |
| 1213 | Providing, installation, testing and commissioning of Stainless Steel Y-Strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia hole flange. |
| 1214 | 80 mm dia |
| 1215 | 100 mm dia |
| 1216 | 150 mm dia |
| 1217 | 200 mm dia |
| 1218 | 250 mm dia |
| 1219 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : |
| 1220 | Gun Metal |
| 1221 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle.Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. |
| 1222 | 30 m |
| 1223 | Supplying & fixing 63 mm dia Gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnected hose pipe coupling as required. |
| 1224 | Gun Metal |
| 1225 | Supplying & Fixing of Fire Brigade connection of Cast Iron body with gun metal male instanteneous inlet couplings complete with cap & chain as required for suitable diameter MS pipe connection conforming to IS 904 as required: |
| 1226 | 2 Way - 100 mm dia MS Pipe |
| 1227 | 4 Way - 150 mm dia MS Pipe |
| 1228 | Supplying & fixing air vessel made of 250 mm dia, 8 mm thick MS Sheet, 1200 mm in height with air release valve on top & flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge & painting with synthetic enamel paint of approved shade as required. |
| 1229 | Providing & fixing of pressure switch in MS pipe line including connection etc. as required. |
| 1230 | Providing & fixing of flow switch in MS pipe line including connection etc. as required. |
| 1231 | 100 mm dia |
| 1232 | Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm & hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure guages, strainer, pressure switch, test control box, ball valve, MS pipe, orifice plate etc of following sizes as required. |
| 1233 | 80 mm dia |
| 1234 | 100 mm dia |
| 1235 | 150 mm dia |
| 1236 | Providing & fixing of Fireman Axe-made of carbon steel with rubber insulated handle tested to 20,000 Volts as per IS:926 |
| 1237 | Providing & fixing of Fire shaft door fabricated out of M.S. sheet and frame, door size of 1200 (W) x 2100 (h)with 4 mm thick glass, suitable Rubber beading and Locking arrangement and complete door shall be powder coated with red color powder coating |
| 1238 | FIRE PUMPS & PANEL |
| 1239 | (A) Supplying, Installing, Testing & commissioning of Electrical Driven Main Fire Pump suitable for automatic operation & consisting of following, complete in all respect, as required: (B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. (C) Suitable HP squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class - F insulation, conforming to IS - 325. (D) MS fabricated common base plate, coupling, coupling guard, foundation boults, etc as required.(E) Suitable cement concrete foundation duly plastered with anti viberation pads. |
| 1240 | 2280 lpm at 56 meters head |
| 1241 | (A) Supplying, Installing, Testing & commissioning of Diesel Engine Driven Main Fire Pump suitable for automatic operation & consisting of following, complete in all respect, as required:(B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.(C) Suitable HP, 1500 RPM water cooled with radiator, diesel engineconforming to relevant IS standard complete with auto starting mechanism, 12/24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments & protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required.(D) MS fabricated common base plate, coupling, coupling guard, foundation boults, etc as required.(E) Suitable cement concrete foundation duly plastered with anti viberation pads. |
| 1242 | 2280 lpm at 56 meters head |
| 1243 | (A) Supplying, Installing, Testing & commissioning of Electrical driven Pressurisation Pump suitable for automatic operation & consisting of following, complete in all respect, as required: (Jockey Pump)(B) Horizontal type, multistage, centrifugal pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.(C) Suitable HP squirrel cage induction motor, TEFC type, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class - F insulation, conforming to IS - 325.(D) MS fabricated common base plate, coupling, coupling guard, foundation boults, etc as required.(E) Suitable cement concrete foundation duly plastered with anti viberation pads. |
| 1244 | 180 lpm at 56 meters head |
| 1245 | INCOMING400A, 50kA 4 Pole MCCB, lcs = 100% lcu Rating Digital Voltmeter 0-500V with selector switch Ammeter (0-400 A) with selector switch & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps. Set of Copper Bus Bar 500 Amps. OUTGOING (Note: All outgoing feedres for pumps should have digital Ammeter with selector switches, & LED type ON, OFF, trip indicating lamps)MAIN FIRE PUMP125 Amp, 50kA TPN MCCB, lcs=100% lcu, with fully automatic Star/Delta starter suitable for 60 hp pump with overload protection, current sensing type single phase preventor complete with all accessories & internal wiring required for automatic operation, seletor switch for local/remote, auto/manual/OFF operation - 2 sets.JOCKEY PUMP125 Amp, 50kA TPN MCCB, lcs=100% lcu, with suitable HP fully automatic star/delta starter with overload protection, current sensing type single phase preventor complete with all accessories & internal wiring required for automatic operation, seletor switch for local/remote, auto/manual/OFF operation - 2 sets. |
| 1246 | DIESEL ENGINE CONTROL Control for diesel engine comprising - Automatic/Manual selector switch & 3 attempts starting device, timers & relays as required, push buttons, start/stop in manual mode indicating lamp for high/low Lub. Oil pressure, high water temp & engine on indication. Battery charger suitable for 12V/24 V DC with boost & trickle selector switch, 0-30 V DC volt meter & 0-20 A DC Ammeter. All standard relays & accessories for automatic operation of diesel engine. SYSTEM CONTROLLERDesigning, supply, installation, testing & commissioning of system controller to control operation of main electric fire pump, deisel pump, pressurization pump, terrace pump in sequence as per specification consisting of relays, timers, sensors, annunciation window for fault indication, complete as per specification. |
| 1247 | SUB HEAD -X X -LIFT |
| 1248 | Passenger Lift - |
| 1249 | Supplying, Installation, Testing & Commissioning of following capacity passenger Machine room less (MRL) lift with regenerative drive as per CPWD General Specification for Electrical Works (Part-III Lift & Escalator) 2003, BIS Codes, NBC 2016 as amended upto date having provision for barrier free access as per Harmonised Guidelines & Standards for Universal Accessibility in India - 2021 of MoHUA, serving different floors in the lift shaft as per detailed specifications enclosed and as under including all other equipment and accessories complete as required:- |
| 1250 | (i) Speed-1 MPS |
| 1251 | (ii) Floors-7 (B1+B2+G+M+3) |
| 1252 | (iii) Travel -20 Meters (approx.) |
| 1253 | (iv) Stops & opening- 7 stops and 7 openings |
| 1254 | (v) Controller: A.C. variable voltage & variable frequency |
| 1255 | (vi) Automatic rescue device (ARD) complete with dry maintenance free batteries as required. |
| 1256 | vii) Operation: Microprocessor based single automatic push button/simplex selective collective/duplex collective selective with/without attendant |
| 1257 | (viii) Power-415 Volts+10%, 3 phase, 50 Hz, 4 wires system |
| 1258 | (ix) Car Enclosure: Stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish) on all sides and stainless steel decorative ceiling with fans (indirect throw) and LED fitting. |
| 1259 | (x) The car flooring should be smooth and antiskid as approved by engineer-in-charge. |
| 1260 | (xi) Type of doors |
| 1261 | Car: Power operated, centre opening horizontal sliding stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish). |
| 1262 | Landing doors: stainless steel scratch proof . |
| 1263 | (xii) A hand rail not less that 600mm long at 900mm above floor level to be fixed adjacent to control panel in the lift car. |
| 1264 | (xiii)Voice announcement system in the car to announce the position of the elevator in the hoist way as the car passes or stops at floor served by the elevator. |
| 1265 | (xiv) Closed loop Control System, protection against power fluctuation, self diagnostic control, Landing doors 2 hours Fire rated, Overload detection and protection, Overspeed Governer, Dot Matrix LED D & P Indicators In Car & Landings, BMS Compatibility, tamper proof infrared curtain covering almost the entire height of the lift car door, Alarm horn, Anti Nuisance Operation, CCTV camera system with 4 MP IP camera, suitable NVR and HDD for 30 days storage backup , Firemen switch, 2/3 way intercom, Emergency Stop Switch with battery backup for fan and light fitting for 1 hour, pit ladder. |
| 1266 | (xv) The lift doors shall have a vision panel to enable persons with hearing impairment to signal for help or assistance in the event of an emergency. |
| 1267 | (xvi) An appropriate technological support be provided (Through emergency messaging |services or alarms etc.) to respond to the emergency requirements of person with hearing impairment or deafness. |
| 1268 | (xvii) In case of failure of ARD or other electronic devices, a provision of manual rescue be provided. |
| 1269 | 13 passenger (884kg) |
| 1270 | Good Lift - |
| 1271 | Supplying, Installation, Testing & Commissioning of 5000kg Machine room less (MRL) goods lift with regenerative drive as per CPWD General Specification for Electrical Works (Part-III Lift & Escalator) 2003, BIS Codes, NBC 2016 as amended upto date, serving different floors in the lift shaft as per detailed specifications enclosed and as under including all other equipment and accessories complete as required :- |
| 1272 | (i) Speed-0.5 MPS |
| 1273 | (ii) Floors-7 (B1+B2+G+M+3) |
| 1274 | (iii) Travel -20 Meters (approx.) |
| 1275 | (iv) Stops & opening- 7 stops and 7 openings |
| 1276 | (v) Controller: A.C. variable voltage & variable frequency |
| 1277 | (vi) Automatic rescue device (ARD) complete with dry maintenance free batteries as required. |
| 1278 | vii) Operation: Microprocessor based single automatic push button/simplex selective collective/duplex collective selective with/without attendant |
| 1279 | (viii) Power-415 Volts+10%, 3 phase, 50 Hz, 4 wires system |
| 1280 | (ix) Car Enclosure: Stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish) on all sides and stainless steel decorative ceiling with fans (indirect throw) and LED fitting. |
| 1281 | (x) The car flooring should be strong to take the rated load without any deformation or damage and antiskid as approved by engineer-in-charge. |
| 1282 | (xi) Type of doors |
| 1283 | Car: Power operated, centre opening horizontal sliding stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish). |
| 1284 | Landing doors: stainless steel scratch proof . |
| 1285 | (xii) A hand rail not less that 600mm long at 900mm above floor level to be fixed adjacent to control panel in the lift car. |
| 1286 | (xiii) Voice announcement system in the car to announce the position of the elevator in the hoist way as the car passes or stops at floor served by the elevator. |
| 1287 | (xiv) Closed loop Control System, protection against power fluctuation, self diagnostic control, Landing doors 2 hours Fire rated, Overload detection and protection, Overspeed Governer, Dot Matrix LED D & P Indicators In Car & Landings, BMS Compatibility, tamper proof infrared curtain covering almost the entire height of the lift car door, Alarm horn, Anti Nuisance Operation, CCTV camera system with 4 MP IP camera, suitable NVR and HDD for 30 days storage backup , Firemen switch, 2/3 way intercom, Emergency Stop Switch with battery backup for fan and light fitting for 1 hour, pit ladder. |
| 1288 | (xv) In case of failure of ARD or other electronic devices, a provision of manual rescue be provided. |
| 1289 | 5000 kg |
| 1290 | SUB HEAD -X X I -EOT CRANES |
| 1291 | Design,Manufacture& Supplyof 10T DGEOT Crane withCabinoperatedandwithfollowingspecifications as per IS: 807 & S 177.Span — 20.5 mtrs Lift — 11 mtrsBay Length — 160 mtrsLocation : Above Tank |
| 1292 | Erection, Testing & Commissioning ofthe above Crane. |
| 1293 | Supply of 60 Lb/yd Rail |
| 1294 | Erection of6O Lb/yd Rail |
| 1295 | Supply of Pestoon type current collection system |
| 1296 | érection of Festoon type current collection system |
| 1297 | Design,Manufacture& Supplyof 10T DGEOT Crane withPendantControlledOperationandwithfollowing specificBtions asper IS: 807 & 3177.Span — 10 mtrs Lits — 5.3 mtrsBay Length — 90 mtrsLocation : Assemblé Area(GFloor) |
| 1298 | Erection. Testing & Commissioning of the above Crane. |
| 1299 | Supply of 60 Lb/yd Rail |
| 1300 | Erection of 60 Rb/yd Rail |
| 1301 | Supply of Festoon type current collection system |
| 1302 | Erection of Festoontype current collection system |
| 1303 | Design,Manufacture& Supplyof 5TDGEOTCrane witiiPendantContmtledOperationandwithfollowing specifications aS per IS: 807 & 3177.Span — 18.5 mtrsLift — 5.5 mtrsBay Length — 20 mtrsLocation : Dispateh Bay |
| 1304 | Erection, Testing & Commissioning of the above Crane. |
| 1305 | Supply of60 Lb/ydRail |
| 1306 | Etection of 60 Lb/yd Rail |
| 1307 | Supply of Festoon type current collection system |
| 1308 | Erection of Pestoon type current collection system |
| 1309 | Design,Manufacture& Supplyof 5TDGEOTCrane witiiPendantContmtledOperationandwithfollowing specifications aS per IS: 807 & 3177.Span — 10.0 mtrsLift — 4.0 mtrsBay Length — 90.0 mtrsLocation : Assembly area (Basement0 |
| 1310 | Erection,Testing & Commissioningof the above Crane. |
| 1311 | Supplyof 60 Lb yd Rail |
| 1312 | Erection of 60 1.b/yd Rail |
| 1313 | Supply ofFestoontype current collection system |
| 1314 | Erection of Festoontype currenttollectionsystem |
| 1315 | Design,Manufacture&Suppl yof3TDGFOTCranewithPendantControlledOperationaridwithfollowingspecifications as per IS:807 &3177.Span - 10 mtrs Lift — 5 .5 mtrsBay Length — 90 mtrslocation : Test FacidityArea(GFloor) |
| 1316 | Erection,Testing & Commissioningof the above Crane. |
| 1317 | Supplyof 60 Lb yd Rail |
| 1318 | Erection of 60 1.b/yd Rail |
| 1319 | Supply ofFestoontype current collection system |
| 1320 | Erection of Festoontype currenttollectionsystem |
| 1321 | Design,Manufacture&Suppl yof3TDGFOTCranewithPendantControlledOperationaridwithfollowingspecifications as per IS:807 &3177.Span - 10 mtrs Lift — 4.0 mtrsBay Length — 90 mtrslocation : Test FacidityArea (Basement) |
| 1322 | Erection, Testing & Commissioningofthe above CraCe. |
| 1323 | Supply of 60 Lb\"yd Rail |
| 1324 | Erection nf 60 Lb/jdRail |
| 1325 | Supply ofFestoontype current collection system |
| 1326 | Erection of Festoontype currentcollectionsystem |
| 1327 | Design,Manufacture&Supply of’ 2TDGEOTCrancwithCabinoperated andwithfollowingspecificat iotasas per IS: 807 & 3177.Span— 20.5 mirsLift — 10 mirsBay cength — 160 mtrsLocation : Above Tank |
| 1328 | Erection, Testing & Commissioningol\"the above Crane. |
| 1329 | Supply of 60 Lb/ydRail |
| 1330 | Erection of 60 Lb/yd Rail |
| 1331 | Supply ofFestoon type current collection system |
| 1332 | Erection of Festoontype current collectionsystem |
| 1333 | Design,Manufacture&Supplyof2TDGEOTCrane withPen‹1antCoritrolledOperalionandwithfollowing specifications as per 1S: 807 &3177.Span — 18.5mtrs Lift — 5.5 mtrsBaylength — 20 mtsLocation : Dispatch Bay(GFloor) |
| 1334 | Erection, Testing & Commissioningol\"the above Crane. |
| 1335 | Supply of 60 Lb/ydRail |
| 1336 | Erection of 60 Lb/yd Rail |
| 1337 | Supply ofFestoon type current collection system |
| 1338 | Erection of Festoontype current collectionsystem |
| 1339 | Design,Manufacture& Supplypf2TMonomilCmne withPendantContmlledOperationandwithfollowing specifications as per IS: 807 & 3177.Span — 18.5 mtrsLift -4 mtrsBay Length — 20 mtrsLocation : Dispatch BBy(Basement) |
| 1340 | Erection, Testing & Commissioningol\"the above Crane. |
| 1341 | Supply of 60 Lb/ydRail |
| 1342 | Erection of 60 Lb/yd Rail |
| 1343 | Supply ofFestoon type current collection system |
| 1344 | Erection of Festoontype current collectionsystem |
| 1345 | SUB HEAD -X X I I -WATER COOLERS |
| 1346 | Drinking Water Fountain |
| 1347 | Providing and fixing Drinking Water Fountain with inbuild water treatment unit of approved quality & sample approved under the directions of engineer-in-charge. |
| 1348 | SUB HEAD -X X I I I -PRESSURISED VENTILLATION SYSTEM |
| 1349 | LIFT WELL / LIFT LOBBY & STAIR CASE PRESSURIZATION |
| 1350 | Supply, erection,testing andcommissioning of ceiling hunged Tube / VaneAxial flow fans with adjustable pitch blade , MS casing, castaluminiumalloyimpeller completewith TEFC Sq. Cage Inductionmotor suitable for 415 volts ± 10%,50Hz ± 3 %, 6 / 4 pole, three phase A.Csupply of Class \"H\" insulationand shall IE -3 with support,mountings with vibration isolator spring and fire rated canvas flexible connection etc. & of following capacity as per approved tender drawings.(Noise Level shall not be more than 90 DB at a distance of 3 metres).Note Fan shall be AMCA Certified. |
| 1351 | In Normal / Emergency Mode: (LIFT WELL) |
| 1352 | Air Qty.=14000 CFM |
| 1353 | Static Pressure = 30 mm Wg |
| 1354 | Motor = Not exceed 5.5Kw. |
| 1355 | FRESH AIR |
| 1356 | Supply, erection,testing andcommissioning of ceiling hunged Tube / VaneAxial flow fans with adjustable pitch blade , MS casing, castaluminiumalloyimpeller completewith TEFC Sq. Cage Inductionmotor suitable for 415 volts ± 10%,50Hz ± 3 %, 6 / 4 pole, three phase A.Csupply of Class \"H\" insulationand shall IE -3 with support,mountings with vibration isolator spring and fire rated canvas flexible connection etc. & of following capacity as per approved tender drawings.(Noise Level shall not be more than 90 DB at a distance of 3 metres).Note Fan shall be AMCA Certified. |
| 1357 | InEmergency Mode: |
| 1358 | Air Qty.= 11000 CFM |
| 1359 | Static Pressure = 30 mm Wg |
| 1360 | Motor = Not exceed 5.5 Kw. |
| 1361 | InEmergency Mode: (FORSIMULATION TANK) |
| 1362 | Air Qty.= 15000 CFM |
| 1363 | Static Pressure = 30 mm Wg |
| 1364 | Motor = Not exceed 7.5 Kw. |
| 1365 | InEmergency Mode: |
| 1366 | Air Qty.= 16000 CFM |
| 1367 | Static Pressure = 30 mm Wg |
| 1368 | Motor = Not exceed 7.5 Kw. |
| 1369 | InEmergency Mode: |
| 1370 | Air Qty.= 4000 CFM |
| 1371 | Static Pressure = 30 mm Wg |
| 1372 | Motor = Not exceed 2.2 Kw. |
| 1373 | EXHAUST AIR |
| 1374 | Supply, erection,testing andcommissioning of ceiling hunged Tube / VaneAxial flow fans with adjustable pitch blade , MS casing, castaluminiumalloyimpeller completewith TEFC Sq. Cage Inductionmotor suitable for 415 volts ± 10%,50Hz ± 3 %, 6 / 4 pole, three phase A.Csupply of Class \"H\" insulationand shall IE -3 with support,mountings with vibration isolator spring and fire rated canvas flexible connection etc. & of following capacity as per approved tender drawings.(Noise Level shall not be more than 90 DB at a distance of 3 metres).Note Fan shall be AMCA Certified. |
| 1375 | InEmergency Mode: |
| 1376 | Air Qty.= 11000 CFM |
| 1377 | Static Pressure = 30 mm Wg |
| 1378 | Motor = Not exceed 5.5 Kw. |
| 1379 | InEmergency Mode: |
| 1380 | Air Qty.= 16000 CFM |
| 1381 | Static Pressure = 30 mm Wg |
| 1382 | Motor = Not exceed 7.5 Kw. |
| 1383 | InEmergency Mode: |
| 1384 | Air Qty.= 4000 CFM |
| 1385 | Static Pressure = 30 mm Wg |
| 1386 | Motor = Not exceed 2.2 Kw. |
| 1387 | SUB - PANELS FORVENTILATION |
| 1388 | Supply ,installation,testing and commissioning of Cubical wall mounted type switch board made of 2mm thick CRCA sheet as detailed below & conforming to the specifications. |
| 1389 | Note: The HVAC contractor shall provide fire shunt relay contact in his panel wherever necessary along with auto/manual mode selector switch in the outgoingfeeder forAXIAL FLOW Fan to take fire input signal (Potential Free Contact).Cost shall be included in the panel price quoted by him. |
| 1390 | For VENTILATION FAN |
| 1391 | 16A TPN MCB for 16 Awith DOL Starter, overload relay, start / stop push buttons, phase indication lights with protection fuse,on / off / tripindicationlightswith protection fuse,ammeter ( 0-16 A) with single CT, single phase preventer. Auto Manual Selector switch. MCB shall be of 10 KA. |
| 1392 | Controls & interlocking accessories as required. |
| 1393 | For VENTILATION & PRESSURIZATION FAN |
| 1394 | 32A TPN MCB for 32 Awith Star Delta Starter, overload relay, start / stop push buttons, phase indication lights with protection fuse,on / off / tripindicationlightswith protection fuse,ammeter ( 0-32 A) with single CT, single phase preventer. Auto Manual Selector switch. MCB shall be of 25KA. |
| 1395 | Controls & interlocking accessories as required. |
| 1396 | POWER & CONTROL CABLING |
| 1397 | Supplying, laying, effecting proper termination, testing & commissioning of the following POWER CABLE sizes of 1.1 KV - PVC inner sheated,extruded PVC type ST2 sheathed & Galvanised steel strips/wire as per IS 7908 (Part-I) armoured aluminium conductor cables conforming to relevant latest amended Indian Standardsas per specification standard. |
| 1398 | 3C x 4 Sq. mm |
| 1399 | 3C x 6 Sq. mm |
| 1400 | Earthing Strip / Wires. |
| 1401 | Providing and fixing 10 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring / cable as required |
| 1402 | Providing and fixing 8 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring / cable as required |
| 1403 | Cable Tray |
| 1404 | Supply and installingfollowing size of perforated painted with powder coating M.S Cable trays with perforation not more than 17.5% , in convinient sections , joined with connectors, suspended from the ceiling with M.S suspenders including bolts & nuts , painting suspenders etc as required. |
| 1405 | 150mm x 50mm x 1.6 mm thick |
| 1406 | SUB HEAD -X X I V -D.G SET |
| 1407 | DG Set - |
| 1408 | Supply, installation, Testing & Commissioning of \"Silent Type Diesel Generating set as per CPCB IV + or better norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should contain drawing, test report OEM manual,Geo-Tag of manufacturing location, rating plate as per relevant IS Code etc. and consisting of the followings: |
| 1409 | (A) Diesel Engine: |
| 1410 | Turbocharged Diesel engine 4 stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 40 Degree C, 50% RH & at 1000 Meter MSL , capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor shall be as per ISO 8528.The engine shall comply to the latest CPCB norms (CPCB IV + or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018 and as per CPWD specifications. |
| 1411 | (B) Engine mounted Instrument Panel fitted with and having digital display for following: |
| 1412 | (i) Start-stop switch with key |
| 1413 | (ii) Water temperature indication |
| 1414 | (iii) Lubrication oil pressure indication |
| 1415 | (iv) Lubrication oil temperature indication |
| 1416 | (v) Battery charging indication and Voltage indication |
| 1417 | (vi) RPM indication |
| 1418 | (vii) Over speed indication |
| 1419 | (viii) Low lubricantion Oil trip indication |
| 1420 | (ix) Engine Running Hours indication |
| 1421 | (x) Fuel Level |
| 1422 | (C) Alternator: |
| 1423 | Synchronous alternator rated of appropriate KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C, 50% RH & at 1000 Meter MSL. The alternator shall be having Screen Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamically balanced rotor, capable of taking 10% over loading for one hour after 12 hours of continuous operation, self cooled,self-excited and self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613 suitable for tropical conditions and with class- H insulation. |
| 1424 | (D) Base Frame & Foundation: |
| 1425 | Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. |
| 1426 | (E) FUEL TANK: |
| 1427 | Daily service fuel tank of suitable liters capacity as per CPWD Specifications, fabricated out of 3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class \"C\" pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications. |
| 1428 | (F) Exhaust System: |
| 1429 | Dry exhaust manifold with hospital type exhaust silencer and catalytic convertor. |
| 1430 | (G) Starting System: |
| 1431 | 12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries (180 AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG Set. |
| 1432 | (H) Acoustic and weather proof enclosure |
| 1433 | with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air into the atmosphere and the temperature rise inside the enclosure, noise level outside enclosure. The acoustic enclosure should be suitable for cable connection/connection through bus-trunking. Such arrangements on acoustic enclosure should be water proof & dust-proof conforming to IP-65 protection. The enclosure shall be as per CPCB IV + or better norms etc. and as per CPWD specifications. |
| 1434 | (I) AMF Panel: |
| 1435 | Free standing floor mounted IP 42 automatic mains failure control panel including auto by-pass, suitable for KVA as below for silent type DG set complete with relays, timers, set of CTs for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase & Total), KW & provision for overload, short circuit, restricted earth fault, under frequency, power (aluminum) and control (copper) cabling of suitable size upto 15 meter between AMF panel, LT Panel and DG Set including connection interconnection etc. as required, all complete and inter locking and communication/ Ethernet/RS485/SNMP port open protocol for BMS integration including suitable software, the panel shall be of DG Set OEM make etc. as per approved by Engineering in charge and including the following: |
| 1436 | Suitable numbers and appropriate capacity 4 pole motorised electrically operated draw out with cradle type 3 position ACB/ MCCB with electronic release for O/C & E/F and shunt trip. |
| 1437 | Auto/Manual/Test/Off selector switch |
| 1438 | Protection for under and over voltage phase reversal (2 nos Over voltage relay, 2 Nos. reverse power relay and 2 Nos. under voltage relay). |
| 1439 | 3 Sets of current transformers 15 P 10 accuracy for protection and 15 VA class-I for metering |
| 1440 | Energy analyser unit to indicate current, Voltage( L-N & L-L), kW, kVA (Phase & Total), Frequency, KWH, PF. |
| 1441 | LED Indicating lamps for load on mains and load on set. |
| 1442 | Fuse/ MCB for instruments. |
| 1443 | Battery charger, complete with transformer/ rectifier, D.C. voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment. |
| 1444 | Main supply failure monitor. |
| 1445 | Supply failure timer. |
| 1446 | Restoration timer |
| 1447 | Control unit with three impulse automatic engine start/stop and failure to start lockout. |
| 1448 | Impulse counter with locking and reset facility. |
| 1449 | ON/OFF/Control circuit switch with indicator |
| 1450 | Audio/Video annunciation for(i) High water temperature(ii) Low lubricating oil pressure(iii) Engine over speed(iv) Engine fails to start(v) Full load/maximum load warning |
| 1451 | Protection for over/under Frequency, Loss of AC sensing, Over Current, Unbalancing load with suitable number of relays and accessories |
| 1452 | Maintenance notification based on Engine Run Hour & due date. |
| 1453 | Load Management through PLC to achieve auto opening and closing of incomer breakers, bus coupler switching of essential panel, interlocking providing signal to AMF Panel for load status and AMF shall give command to DG Set to auto start / auto stop depending upon load status and requirement etc. and necessary hardware and software required to perform the operation shall be provided by the contractor including all control wiring. |
| 1454 | 1250 KVA (As per latest CPCB Norms) |
| 1455 | EXHAUST SYSTEM FOR DG |
| 1456 | Supply of exhaust piping of following sizes MS B Class exhaust pipes conforming to IS:3589 with welding joint including bends, clamps, dash fastener, flanges, nuts, bolts etc. completeas requiredand asper specifications detailed below. |
| 1457 | 10\" dia. (250 mm NB), MS, 4.85 mm thick plate, Exhaust pipe |
| 1458 | 14\" dia. (350 mm NB), MS, 4.85 mm thick plate, Exhaust pipe |
| 1459 | Supply of 50mm thick glasswool /mineral wool, wire chicken mesh over insulation and 26 gauge aluminium sheet cladding over the following sizes exhaust pipes from silencer to atmosphere. |
| 1460 | 10\" dia. (250 mm NB), MS, 4.85 mm thick plate, Exhaust pipe |
| 1461 | 14\" dia. (350 mm NB), MS, 4.85 mm thick plate, Exhaust pipe |
| 1462 | Supply and installation of MS Support structure The MS Structure. will be duly coated with two coats of red-oxide primer and two coats of enamel paint. The colour shade of final paint will be as decided by the client. |
| 1463 | Supply and installation of Aluminium cladding for residencial silencers with Mineral Wool 50mm Thick, density 64 Kg/cu.mtr., wire mesh and 24 gauge aluminium cladding. |
| 1464 | Supply and installation of SS Flexible Bellows, 10\" dia. (250 mm NB), complete with counter flanges, heat resitant gaskets, nuts-bolts-washers etc., complete as required. |
| 1465 | Supply and installation of Lightening Arrestors Non Seamer Type with GI Strip upto Earth Pit |
| 1466 | Supply and installation of Aviation light with UPS and Cable upto light |
| 1467 | FUEL SYSTEM |
| 1468 | Supply and Installation of MS Class C Pipe 25 mm(Considering DG set to be placed at a distance of 5-6 mtr) |
| 1469 | Supply and Installation of set of Fuel Pipe fittings like bends, flanges, valves, tee, elbows etc. |
| 1470 | HSD STORAGE AND SUPPLY SYSTEM 25KL FOR 3X1250 KVA DG SETS |
| 1471 | Supply of HSD storage tanks 25 KL capacity (6 mm thick flat end) as per 10987 - 1992 and approved for construction, shop drawings duly approved by “CCOE” suitable for under ground installation including the following: |
| 1472 | a. Inlet and outlet connections |
| 1473 | b. Vent pipe. |
| 1474 | c. Dip pipe assembly with calibration chart |
| 1475 | d. 550 mm dia manhole with cover. |
| 1476 | e. Lifting lugs |
| 1477 | f. MS ladder |
| 1478 | g. Providing Anti corrosive Pypcoat (AW4) treatment. |
| 1479 | HSD storage tank as described above |
| 1480 | Supply of electrical driven rotary gear-pumps suitable for pumping of HSD |
| 1481 | Supply ofM.S. class ‘C’ (heavy duty) pipe |
| 1482 | 25 mm dia |
| 1483 | 50 mm dia |
| 1484 | 80 mm dia |
| 1485 | Supply of 80 Nb Flexible Hose pipe with AL Adopter for filling of HSD in BOT |
| 1486 | Supply of Pot-Strainer |
| 1487 | 80 mm dia |
| 1488 | Supply ofoil flow meter 80 nb with flanged end for HSD service. |
| 1489 | Supply of cast steel ball valves |
| 1490 | 80 mm dia |
| 1491 | 50 mm dia |
| 1492 | 25 mm dia |
| 1493 | Supply ofcast steel non return valves |
| 1494 | 50 mm dia |
| 1495 | Supply ofY Strainer |
| 1496 | 50 mm dia |
| 1497 | Supply of 990 litres capacity buffer oil storage tank fabricated from 2 mm thick MS plates. Tank shall include 450 mm ID manhole cover, level indicator and flanged connection for inlet, outlet, overflow drainand probe provision for level controller. Tank shall be mounted on 2 m high structure support with access ladder (painted with 2 coats of red oxide primer). |
| 1498 | Supplyof gunmetalfootvalvewithnecessaryfittingscompleteas required. |
| 1499 | 50 mm dia |
| 1500 | Supply of level switch High & Low for storage Tank & Buffer tank |
| 1501 | Supply ofWeather proof (IP-55) remote pushbutton anchoring on floor including supporting arrangement. |
| 1502 | SUB HEAD - X X VROAD ,HARD STANDING & DRAINS |
| 1503 | Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earth with lead upto 50 Metre. |
| 1504 | Construction of granular sub-base by providing close graded material, Spreading in uniform layers with motor grader on prepared sueface, mixing by mix in place method with front end loader at OMC,and compacting with vibratory roller to achieve the desired density ,complete as per clause 401 |
| 1505 | With material conforming to Grade-I (size range 75 mm to 0.075 mm) having CBRValue-30 |
| 1506 | With material conforming to Grade-III (size range 26.5 mm to 0.075 mm) having CBRValue-20 |
| 1507 | Construction of dry lean cement concrete sub base over a prepared sub-grade with coarse and fine aggregate conforming to IS:383, thesize of coarse aggregate not exceeding 25 mm, aggregate cement ratio not toexceed 15:1, aggregate gradation after blending to be asper specifications, cement content not to be less than 150 Kg/cum,optimum moisture content to be determined during trial lengthconstruction, concrete strength not to be less than 10 Mpa at 7days, mixed in a batching plant, transported to site, for all leads &lifts, laid with a mechanical paver, compacting with 8-10 tonne vibratoryroller, finishing and curing etc. complete as per direction of Engineer-in- charge. |
| 1508 | Providing and laying 1000 Micron Low-Density Polyethylene LDPE Sheets with aminimum Density of 925 kg/cum having Low crystalline and high amorphous (less than 50-60% crystalline). LDPE sheets can hold their shape in extremely high or low-temperature environments, ranging from -40 ℃ to 90 ℃. complete as per direction of Engineer- in-charge. |
| 1509 | Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to 0.075 mm ) to wet mix macadam (WMM) specification including premixing the material with water at OMC in for all leads & lifts, laying in uniform layers with mechanical paver finisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achievethe desired density, complete as per specifications and directions of Engineer-in-Charge. |
| 1510 | Providing and laying C.C. pavement of mix M-30 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator , vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-in-charge. (The panel shuttering work shall be paid for separately). |
| 1511 | (Note:- Cement content considered in this item is @ 350 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately). |
| 1512 | Providing and applying 2.5 mm thick road marking strips (retroreflective) of specified shade/ colour using hot thermoplastic material by fully/ semi automatic thermoplastic paint applicator machine fitted with profile shoe, glass beads dispenser, propane tank heater and profile shoe heater, driven by experienced operator on road surface including cost of material, labour, T&P, cleaning the road surface of all dirt, seals, oil, grease and foreign material etc. complete as per direction of Engineer-in-charge and accordance with applicablespecifications. |
| 1513 | Providing and fixing Glow studs of size 100x20 mm made of heavy duty body shall be moulded ASA (Acrylic styrene Acryloretrite ) or HIP (High impact polystyrene) or ABS having electronically welded micro- prismatic lens with abrasion resistant coating as approved by Engineer in charge. The glow stud shall support a load of 13635 kg tested in accordance with ASTM D4280. The slope of retro- reflective surface shall be 35 (+/-5) degress to base .The reflective panels on both sides with at least 12 cm of reflective area up each side. The luminance intensity should be as per the specification and shall be tested as described in ASTM I: 809 as recommended in BS: 873 part 4 : 1973. The studs shall be fixed to the Road surface using the adhesive conforming to IS, as per procedure recommended by the manufacturer complete and as per direction of Engineer-in-charge. |
| 1514 | Providing and fixing pre-moulded joint filler in expansion joints of RCC roads / CC pavements after making the joints dust free with high pressure air jet cleaners, all complete as per direction of the Engineer-in-Charge. (Pre-moulded joint fillers shall be made of bitumen hot sealing compound impregnated fibre board having impregnation more than 35%, conforming to IS:1838 for fibre board and IS: 1834for hot sealing bitumen compound grade A.) |
| 1515 | SUB HEAD - X X V ISTORM WATER DRAIN |
| 1516 | EXTERNAL DRAINAGE SYSTEM |
| 1517 | Constructing RCC precast perforated RCC. slab covered Drain with 150mm thick RCC 1.1.5.3 ( 1 cement : 1.5 fine sand : 3 graded stone aggregate 20mm nominal size) wallincluding earth excavation, 75mm thick bed concrete 1:4:8 (1 cement : 4 fine sand : 8 graded stone aggregate 40mm nominal size) and 100mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5mm nominal size) for filling haunches including 12mm cement plaster 1:4 (1 cement : 4 coarse sand ) with a floating coat of neat cement inside the drain, its top and exposed side including disposal of surplus earth complete as per standard design: |
| 1518 | Drain 600 wide average. Depth 1200 cm with R.C.C. Slab |
| 1519 | SUB HEAD -X X V I I -EXTERNAL WATER SUPPLY |
| 1520 | EXTERNAL WATER SUPPLY WORK |
| 1521 | Excavating trenches by mechinical/ manual means of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, for all depth, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m : |
| 1522 | All kinds of soil |
| 1523 | Pipes, cables etc, not exceeding 80 mm dia. |
| 1524 | Pipes, cables etc. exceeding 80 mm dia. butnot exceeding 300 mm dia |
| 1525 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. |
| 1526 | External work |
| 1527 | 25 mm nominal dia Pipes |
| 1528 | 32 mm nominal dia Pipes |
| 1529 | 40 mm nominal dia Pipes |
| 1530 | 50 mm nominal dia Pipes |
| 1531 | 65 mm nominal dia Pipes |
| 1532 | 80 mm nominal dia Pipes |
| 1533 | 100 mm nominal dia Pipes |
| 1534 | 150 mm nominal dia Pipes |
| 1535 | Providing and fixing C.I. sluice valves (with cap) complete with bolts, nuts, rubber insertions etc. (the tail pieces if required will be paid separately) : |
| 1536 | 100 mm diameter |
| 1537 | Class II |
| 1538 | 150 mm diameter |
| 1539 | Class II |
| 1540 | 200 mm diameter |
| 1541 | Class II |
| 1542 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : |
| 1543 | 80 mm nominal bore |
| 1544 | 65 mm nominal bore |
| 1545 | 50 mm nominal bore |
| 1546 | 40 mm nominal bore |
| 1547 | 32 mm nominal bore |
| 1548 | Constructing masonry Chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice / gate valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:1.5:3 mix (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size), including necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plasteringwith cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : |
| 1549 | With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 |
| 1550 | Providing and fixing C.I. double acting air valve of approved quality with bolts, nuts, rubber insertions etc. complete (The tail pieces, tapers etc if required will be paid separately) : |
| 1551 | 80 mm dia |
| 1552 | WATER TREATMENT PLANT |
| 1553 | Planing, Design, Construction, Supplying, Installing, Testing & Commissioning of Water Treatment Plant capacity 50 KLD. The plant is proposed to be installed as per site condition .The opening shall be provided on above for this purpose, for the following the shop drawings & design of WTP shall also be prepared in such a way that it comprise of the following units of required size as per detail design requirements. The work has to be carried through authorised vendor, dealer/representative of approved make. |
| 1554 | Planing, Design, Construction, Supplying, Installing, Testing & Commissioning of Water Treatment Plant (Pump Room) for stimulation channel. The plant is proposed to be installed as per site condition .The opening shall be provided on above for this purpose, for the following the shop drawings & design of Pump Room shall also be prepared in such a way that it comprise of the following units of required size as per detail design requirements. The work has to be carried through authorised vendor, dealer/representative of approved make. |
| 1555 | RAIN WATER HARVESTING |
| 1556 | RECHARGE PITS |
| 1557 | Providing M.S. foot rests including fixing in manoholes with 20x20x10 cm cement concrete blocks 1:3:6 (1cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) as per standard design: |
| 1558 | With 20x20mm square bar |
| 1559 | Providing and fixing in position precast RCC manhole cover and frame of required shape and approved quality. |
| 1560 | M.D. -10- Circular shape 500mm internal diameter |
| 1561 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer -in-charge, beyond 90 metre & upto 150 metre depth below ground level. |
| 1562 | Drilling of 300mm dia bore hole manually. |
| 1563 | 400 mm dia |
| 1564 | Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. |
| 1565 | 150 mm nominal size dia |
| 1566 | Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 1567 | Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 1568 | Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer -incharge. |
| 1569 | Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge. |
| 1570 | BOREWELL |
| 1571 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, upto 90 metre depth below ground level. |
| 1572 | All kinds of soil |
| 1573 | 400 mm dia |
| 1574 | Supplying, assembling, lowering and fixing in vertical position in borewell, ERW (Electric Resistance Welded) FE 410 mild steel screwed and socketed/plain ended casing pipes of required dia, conforming to IS: 4270, of reputed & approved make, including painted with outside surface with two coats of anticorrosive paint of approved brand and manufacture, including required hire & labour charges, fittings & accessories, all complete, for all depths, as per direction of Engineer-in charge. |
| 1575 | 200 mm nominal size dia having minimum wall thickness 5.40 mm |
| 1576 | Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric Resistance Welded) FE 410 plain slotted (having slot of size 1.6/3.2 mm) mild steel threaded and socketed/ plain bevel ended pipe (type A) of required dia, conforming to IS: 8110, of reputed and approved make, having wall thickness not less than 5.40 mm, including painted with outside surface with two coats of anticorrosive bitumestic paint of approved brand and manufacture, including hire & labour charges, fittings & accessories, all complete, for all depths, as per direction of Engineer-in-charge. |
| 1577 | 150 mm nominal size dia |
| 1578 | Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of useable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by “V” notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, including disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge. |
| 1579 | Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for borewell of: |
| 1580 | 200 mm dia |
| 1581 | Providing and fixing M.S. clamp of required dia to the top of casing/housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts & nuts of required size complete. |
| 1582 | 150 mm clamp |
| 1583 | 200 mm clamp |
| 1584 | Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tubewell as per IS:2800 (part I). |
| 1585 | 150 mm dia |
| 1586 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. |
| 1587 | 80 mm dia nominal bore |
| 1588 | Providing and fixing gun metal non- return valve of approved quality (screwed end) : |
| 1589 | 80 mm nominal bore |
| 1590 | Vertical |
| 1591 | Providing and fixing C.I. double acting air valve of approved quality with bolts, nuts, rubber insertions etc. complete (The tail pieces, tapers etc if required will be paid separately) : |
| 1592 | 80 mm dia |
| 1593 | Providing and fixing enclosed type water meter (bulk type) conforming to IS : 2373 and tested by Municipal Board complete with bolts, nuts, rubber insertions etc. (The tail pieces if required will be paid separately) : |
| 1594 | 80 mm dia nominal bore |
| 1595 | Submersible Pump include the rate of electrical control panels complete with all accessories & controls, all Electrical/Mechanical items as required to operate the system automatic/manual. Level Controller with sufficient nos. of low / high level alarms, contacts with electrodes and control wiring for the automatic operation of water supply pumps, Submersible Sump Pumps, to achieve the functional requirement shall be provided. Control wiring between these pumps and water tanks shall be provided.Domestic water pumps must start at low water level inunder grounddomestic water tank & stop at high level in that water tank. Dry running protection shall be provided for all the pumps. Sequencing shall be provided for each set of pumps. |
| 1596 | Supplying & Installation of(400 lpm and 75 mtr head) submersible starter and cable (L&T or BCH make) etc of approved make, and all accessories complete as per requirement of site. |
| 1597 | SUB HEAD -X X V I I I -EXTERNAL ELECTRIFICATION |
| 1598 | HT PANEL - |
| 1599 | Supply, Installation, Testing & commissioning of indoor type floor mounted metal clad, 11 KV VCB panel drawout Indoor type fabricated from 2mm thick CRCA Sheet steel complete with totally enclosed & fully interlocked, horizontal drawout, horizontal / vertical isolation type breaker as per IEC 62271-100/200, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, Manually spring charged breaker and manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C. supply with short circuit fault level of maximum 500 MVA as per IS 2026, complete with self contained, fully interlocked, rack in and rack out mechanism, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO + 4 NC and equipped with following switchgears and accessories as required and instruction of Engineer InchargeMake: OEM or their Licensee partner complying with the specifications. Type test certificate issued by CPRI/ ERDA or any other NABL accredited agency. |
| 1600 | INCOMER: 2 nos |
| 1601 | Each incomer VCB should be as below. |
| 1602 | 1 No. 800 Amp 11KV 26.3 kA VCB with Closing coil to be operated with 230V AC & Tripping Coil operated with 24V DC auxiliary, supply TNC Switchand comprising of following items: |
| 1603 | 1 No. 11 KV/ 110 V/110V PT Class 0.5 accuracy for metering & Class 3P for Protection and 100 VA burden |
| 1604 | 1 set 11kV, 4 ampere 25kA PT Fuse |
| 1605 | Digital Voltmeter & Ammeter with inbuilt Selector Switch |
| 1606 | Phase indication lamps protected through 3 nos. 2A SP MCBs |
| 1607 | Under Voltage & Over voltage protection device protected through 3 Nos. 2A SP MCBs. |
| 1608 | 1 set of dual core dual ratio 3 CTs of 150A-75A/5A of 15VA burden and accuracy class 0.5 for metering and class 5P10 for protection. |
| 1609 | 1 No. Microprocessor based numerical relay (IDMT relay) with 2 levels of over current and earth fault protection, 3 O/C and 2 E/F element with LED’s for fault indication. Trip records must be with date & time stamping |
| 1610 | 1 No. Anti Pumping device. |
| 1611 | 1 No. trip Circuit Supervision Relay |
| 1612 | 1 No. Master Trip Relay |
| 1613 | 2 Nos. Transformer Supervision Relays |
| 1614 | 1 Set of multifuction meter with basic parameters like frequency, KW, KVA, KVAR, Power Factor, total harmonic distortion etc. shall be suitable for EMS function with RS 485 port for communication. |
| 1615 | 1 Set of following indicating lamps. |
| 1616 | Amber for Trip indication. |
| 1617 | Red \"ON\" Green \"OFF\" Spring charge indication. Trip Circuit Healthy indication. |
| 1618 | Breaker positioning lamps & DC Circuit Healthy indicaton lamp. |
| 1619 | 8-Window Annunciator |
| 1620 | 1 No. Hooter with Accept/Reset & Test Push Button |
| 1621 | Local/remote Selector Switch & Emergency Push Button with necessary NO/NC Contacts. |
| 1622 | 1 No. Power Pack Unit for providing auxiliary power to Trip Coil and other necessary equipments as required. |
| 1623 | Provision for installation of meter from electricity board |
| 1624 | Bus Coupler : 1 nos |
| 1625 | Similar as incomer vcb but without protection relay. |
| 1626 | Out going: 3 nos |
| 1627 | 1 No. 630 Amp 11KV 26.3 kA VCB with Closing coil to be operated with 230V AC & Tripping Coil operated with 24V DC auxiliary, supply TNC Switch and comprising of following items: |
| 1628 | Ammeter with inbuilt Selector Switch |
| 1629 | 1 set of dual core dual ratio 3 CTs of 100A-50A/5A of 15VA burden and accuracy class 0.5 for metering and class 5P10 for protection. |
| 1630 | 1 No. Microprocessor based numerical relay (IDMT relay) with 2 levels of over current and earth fault protection, 3 O/C and 2 E/F element with LED’s for fault indication and at least 15 trip records for over current & 15 for earth fault. Trip records must be with date & time stamping. ANSI : 50, 50N,51,51N |
| 1631 | 1 No. Anti Pumping device. |
| 1632 | 1 No. trip Circuit Supervision Relay |
| 1633 | 1 No. Master Trip Relay |
| 1634 | 2 Nos. Transformer Supervision Relays |
| 1635 | 1 Set of multifuction meter with basic parameters like frequency, KW, KVA, KVAR, Power Factor, total harmonic distortion etc. shall be suitable for EMS function with RS 485 port for communication. |
| 1636 | 1 Set of following indicating lamps. |
| 1637 | Amber for Trip indication. |
| 1638 | Red \"ON\" Green \"OFF\" Spring charge indication. Trip Circuit Healthy indication. |
| 1639 | Breaker positioning lamps & DC Circuit Healthy indicaton lamp. |
| 1640 | BUS BAR: 630 A TP CU Bus Bar |
| 1641 | it shall be single bus bar pattern with air insulated encapsulated bus bars housed in a separate compartment, segregated from other compartments. The Bus bar material shall be high conductivity Copper rated as specified. Max. Bus Bar temp shall not exceed 90 degree C in any conditions viz. rated and short circuit current. |
| 1642 | Short time current rating : 26.3 kA Duration of Short circuit withstand : 3 Sec |
| 1643 | Transformer - |
| 1644 | Supply, installation, testing and commissioning of following capacity (continuous loading) 11/0.433 KV Delta/Star,step down, 3 Phase, 50 Hz, Dyn 11 vector group, Cast Resin/VPI (vacuum pressure impregnated) Dry Type, copper wound transformer (Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH or better) AN (air natural) cooled transformer suitable for indoor applications with Off Circuit Tap Link (OCTL), insulation class F (minimum), suitable for environment conditions class E4, suitable for fire behaviour class F1,climate class-C1, having cable end boxes on HV side suitable for 3x300 sqmm XLPE cable of 11 KV grade with necessary hardware, clamps, lugs etc. for termination on HV/MV etc. for all transformers. Bus trunking arrangement on LV side complete with all accessories and safety provisions as per relevant IS Code, The transformer shall be provided with standard fittings/accessories as per relevant IS and mentioned below, protection alarm/trip protection, 3 nos. of Polymeric Zinc Oxide surge Arrestors on HV Side. |
| 1645 | Winding Temperature scanner (Digital) with alarm/Trip contacts with RTD Sensors per LV winding and space for mounting differential protection CT\"s in LV chamber with neutral brought out separately including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/HT Panel for safety tripping, complete as confirming to IS-2026 Part-11, i/c supplying and grouting of suitable M.S. Channel with all accessories ,complete in all respects as required at site as per specifications.Design ambient condition :a) air temperature 50 0Cb) Relative Humidity 90 % Maxc) Seismic Zone as per location of sited) Altitude as per location/site. The transformer should have QR code which should contain drawing, test report OEM manual, Geo-Tag of manufacturing location, rating plate as per relevant IS Code etc. All testing shall as per relevant IS Code. |
| 1646 | Noise level Shall not exceed limits as per NEMA TR-1 with all accessories running measured as per IEC 551/NEMA Standard. Fitting and Accessories :The following fittings shall be provided :- a) Two earthing terminals with the earthing symbolb) Rating and terminal marking platesc) Thermometer pocket with capd) Lifting lugs for the complete transformer as well as for core and winding assemblye) Bi-directional flat rollers (for transformers above 200 kVA)f) HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth)g) Arcing horns or suitable rating lightning arrestors for HT side – 3 Nos. for transformers up to 200 kVAh) Bird guardi) Jacking pads (for transformer above 1600 kVA)j) Name Rating & Diagram Platek) Monogram Platei) Additional neutral separately brought out on bushing for earthing. |
| 1647 | 1250 KVA (losses at 50% loading < 3600watt, losses at 100% loading < 10750watt) Level 2/3 (As per latest ECBCS Norms) |
| 1648 | Main LT Panel - |
| 1649 | Supply, Installation, Testing & commissioning of of Main LT Panel, suitable for 415 volts 4 pole, 50 Hz, A.C. Supply. Main LT Panel shall be single font/double font, totally enclosed compartmentalized type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet steel for load bearing member and 1.6mm for non load bearing members and complete with Aluminum bus bars, multifunction meter, indicating lamps, protection relays, CT\"s protection mcb, interconnections with suitable size of solid aluminum strips/power cables & control circuit including breaker control switch, etc as required and as per instruction and approval of Engineer In charge. Bus Bar - 3200A, TPN electrolytic grade E91-E AL bus bar, 50 kA for 1 sec. |
| 1650 | INCOMER from 1250 KVA TRANSFORMER Sets - 3 Nos |
| 1651 | 2000A 4P 50kA EDO ACB WITH MICROPROCESSOR RELEASE & LSING Protection - 3 Nos |
| 1652 | Each incomer ACB should have below mentioned accessories as per proposed scheme |
| 1653 | Under Voltage Release for ACB |
| 1654 | Shunt Release for ACB |
| 1655 | Mechanical Interlock using Key & Lock |
| 1656 | Locking arrangement for OFF button with R - Lock (on breaker) |
| 1657 | Digital Multifuncation Meter, Class-1 with RS485 |
| 1658 | Breaker Control Switch (TNC) |
| 1659 | CTs - 2000/5A , 15VA , Class -1 Tape Wound for Metering |
| 1660 | 2000/5A 15VA CL1 CT FOR APFCR |
| 1661 | AUX CONTACTOR 2NO+2NC |
| 1662 | 220V AC Indication LED Type (R/Y/B Phase On) |
| 1663 | 240V AC Indication LED Type ( Breaker On/Off/Trip) |
| 1664 | Type 1+2 SPD with AU MCB as Backup Protection |
| 1665 | 6A DP MCB, 10kA, C-Curve |
| 1666 | SP MCB, 10kA, C-Curve |
| 1667 | CT Shorting Link |
| 1668 | Bus Coupler - 2 Nos |
| 1669 | 2000A 4P 50kA EDO ACB - 2 Nos |
| 1670 | Under Voltage Release for ACB |
| 1671 | Mechanical Interlock using Key & Lock |
| 1672 | Locking arrangement for OFF button with R - Lock (on breaker) |
| 1673 | On delay timer |
| 1674 | Breaker Control Switch (TNC) |
| 1675 | AUX CONTACTOR 2NO+2NC |
| 1676 | 220V AC Indication LED Type (R/Y/B Phase On) |
| 1677 | 240V AC Indication LED Type ( Breaker On/Off/Trip) |
| 1678 | 6A 4P 10KA MCB FOR SECONDARY PROTECTION OF PT |
| 1679 | 6A DP MCB, 10kA, C-Curve |
| 1680 | SP MCB, 10kA, C-Curve |
| 1681 | Neutral Link |
| 1682 | Electrical Interlocking arrangement for Main ACBs & Buscoupler ACBs |
| 1683 | INCOMER from 1250 KVA DG Sets - 3 Nos |
| 1684 | 2000 A 4P 50kA EDO ACB WITH MICROPROCESSOR RELEASE & LSING Protection- 3 Nos |
| 1685 | Under Voltage Release for ACB |
| 1686 | Shunt Release for ACB |
| 1687 | Mechanical Interlock using Key & Lock |
| 1688 | Locking arrangement for OFF button with R - Lock (on breaker) |
| 1689 | Digital Multifuncation Meter, Class-1 with RS485 |
| 1690 | Breaker Control Switch (TNC) |
| 1691 | CTs - 2000/5A , 15VA , Class -1 Tape Wound for Metering |
| 1692 | AUX CONTACTOR 2NO+2NC |
| 1693 | 220V AC Indication LED Type (R/Y/B Phase On) |
| 1694 | 240V AC Indication LED Type ( Breaker On/Off/Trip) |
| 1695 | 6A DP MCB, 10kA, C-Curve |
| 1696 | SP MCB, 10kA, C-Curve |
| 1697 | CT Shorting Link |
| 1698 | Digital Voltmeter - 3 Phase |
| 1699 | Auto/manual Selector Switch |
| 1700 | Phase Sequence Relay |
| 1701 | EMERGENCY STOP PUSH BUTTON |
| 1702 | PLC based interlocking system for Tranformers & DG |
| 1703 | OUTGOING 1600A ACB FEEDER - 1 Nos |
| 1704 | 1600A 4P 50kA EDO ACB WITH MICROPROCESSOR RELEASE & LSING Protection |
| 1705 | Under Voltage Release for ACB |
| 1706 | Shunt Release for ACB |
| 1707 | Breaker Control Switch (TNC) |
| 1708 | 220V AC Indication LED Type (R/Y/B Phase On) |
| 1709 | 240V AC Indication LED Type ( Breaker On/Off/Trip) |
| 1710 | 6A DP MCB, 10kA, C-Curve |
| 1711 | SP MCB, 10kA, C-Curve |
| 1712 | Neutral Shorting Link |
| 1713 | Digital MFM WITH RS 485 PORT |
| 1714 | 1600/5A 15VA CL1 CT |
| 1715 | OUTGOING 1250A ACB FEEDER - 2 Nos |
| 1716 | 1250A 4P 50kA EDO ACB WITH MICROPROCESSOR RELEASE & LSING Protection |
| 1717 | Under Voltage Release for ACB |
| 1718 | Shunt Release for ACB |
| 1719 | Breaker Control Switch (TNC) |
| 1720 | 220V AC Indication LED Type (R/Y/B Phase On) |
| 1721 | 240V AC Indication LED Type ( Breaker On/Off/Trip) |
| 1722 | 6A DP MCB, 10kA, C-Curve |
| 1723 | SP MCB, 10kA, C-Curve |
| 1724 | Neutral Shorting Link |
| 1725 | Digital MFM WITH RS 485 PORT |
| 1726 | 1250/5A 15VA CL1 CT |
| 1727 | OUTGOING 1000A ACB FEEDER - 3 Nos |
| 1728 | 1000A 4P 50kA EDO ACB WITH MICROPROCESSOR RELEASE & LSING Protection |
| 1729 | Under Voltage Release for ACB |
| 1730 | Shunt Release for ACB |
| 1731 | Breaker Control Switch (TNC) |
| 1732 | 220V AC Indication LED Type (R/Y/B Phase On) |
| 1733 | 240V AC Indication LED Type ( Breaker On/Off/Trip) |
| 1734 | 6A DP MCB, 10kA, C-Curve |
| 1735 | SP MCB, 10kA, C-Curve |
| 1736 | Neutral Shorting Link |
| 1737 | Digital MFM WITH RS 485 PORT |
| 1738 | 1000/5A 15VA CL1 CT |
| 1739 | OUTGOING 800A ACB FEEDER (Capacitor Bank) - 3 Nos |
| 1740 | 800A 4P 50kA EDO ACB WITH MICROPROCESSOR RELEASE & LSING Protection |
| 1741 | Under Voltage Release for ACB |
| 1742 | Shunt Release for ACB |
| 1743 | Breaker Control Switch (TNC) |
| 1744 | 220V AC Indication LED Type (R/Y/B Phase On) |
| 1745 | 240V AC Indication LED Type ( Breaker On/Off/Trip) |
| 1746 | 6A DP MCB, 10kA, C-Curve |
| 1747 | SP MCB, 10kA, C-Curve |
| 1748 | Neutral Shorting Link |
| 1749 | Digital MFM WITH RS 485 PORT |
| 1750 | 800/5A 15VA CL1 CT |
| 1751 | OUTGOING 630A MCCB FEEDER - 3 Nos |
| 1752 | 630A 4P 36kA MCCB WITH MICROPROCESSOR RELEASE & LSING Protection |
| 1753 | EXTENDED ROTARY HANDLE for 630A MCCB |
| 1754 | 630A 4P SPREADER LINK |
| 1755 | MCCB AUX & TAC CONTACT |
| 1756 | Digital MFM WITH RS 485 PORT |
| 1757 | 630/5A 15VA CL1 CT |
| 1758 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 1759 | 6A SP 10KA MCB |
| 1760 | OUTGOING 400A MCCB FEEDER - 6 Nos |
| 1761 | 400A 4P 36kA MCCB WITH MICROPROCESSOR RELEASE & LSING Protection |
| 1762 | EXTENDED ROTARY HANDLE for 400A MCCB |
| 1763 | 400A 4P SPREADER LINK |
| 1764 | MCCB AUX & TAC CONTACT |
| 1765 | Digital MFM WITH RS 485 PORT |
| 1766 | 400/5A 15VA CL1 CT |
| 1767 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 1768 | 6A SP 10KA MCB |
| 1769 | OUTGOING 250A MCCB FEEDER - 6 Nos |
| 1770 | 250A 4P 36kA MCCB WITH TM RELEASE & LSI Protection |
| 1771 | EXTENDED ROTARY HANDLE for 250A MCCB |
| 1772 | 250A 4P SPREADER LINK |
| 1773 | MCCB AUX & TAC CONTACT |
| 1774 | Digital MFM WITH RS 485 PORT |
| 1775 | 250/5A 15VA CL1 CT |
| 1776 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 1777 | 6A SP 10KA MCB |
| 1778 | OUTGOING 200A MCCB FEEDER - 3 Nos |
| 1779 | 200A 4P 25kA MCCB WITH TM RELEASE & LSI Protection |
| 1780 | EXTENDED ROTARY HANDLE for 200A MCCB |
| 1781 | 200A 4P SPREADER LINK |
| 1782 | MCCB AUX & TAC CONTACT |
| 1783 | Digital MFM WITH RS 485 PORT |
| 1784 | 200/5A 15VA CL1 CT |
| 1785 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 1786 | 6A SP 10KA MCB |
| 1787 | OUTGOING 150A MCCB FEEDER - 3 Nos |
| 1788 | 150 A 4P 25kA MCCB WITH TM RELEASE & LSI Protection |
| 1789 | EXTENDED ROTARY HANDLE for 150A MCCB |
| 1790 | 150A 4P SPREADER LINK |
| 1791 | MCCB AUX & TAC CONTACT |
| 1792 | Digital MFM WITH RS 485 PORT |
| 1793 | 150/5A 15VA CL1 CT |
| 1794 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 1795 | 6A SP 10KA MCB |
| 1796 | OUTGOING 100A MCCB FEEDER - 5 Nos |
| 1797 | 100A 4P 25 kA MCCB WITH TM RELEASE & LSI Protection |
| 1798 | EXTENDED ROTARY HANDLE for 100A MCCB |
| 1799 | 100A 4P SPREADER LINK |
| 1800 | MCCB AUX & TAC CONTACT |
| 1801 | Digital MFM WITH RS 485 PORT |
| 1802 | 100/5A 15VA CL1 CT |
| 1803 | Indicating Lamp - R/Y/G and ON/OFF/Trip |
| 1804 | 6A SP 10KA MCB |
| 1805 | HYBRID Power Factor Correction System - |
| 1806 | Supply, Installation, testing and commissioning of 400KVAr + 200A AHF HYBRID APFC Panel, 3 phase 4 wire, 415 V, 50 Hz AC System for Ambient temperature -5°C to +40°C of following capacity with passive solution of 60% capacity and active solution of 40% capacity,3Phase 4 wire Hybrid Power Factor Correction Solution (with arrangement for neutral current balance) to achieve >0.99 lag and TDDI/THDV values within IEEE recommended limits. HPFC should be designed as per IS 16636 Or IEC 61921.The active section and passive section shall work in sync to give optimized output. The degree of protection of passive section should be IP 42, and of active section should be minimum IP 21.The switching device for APFC passive section should be through capacitor duty contactor and for the active compensation system shall be IGBT based with 3 level topology having 12 IGBT in inverter circuit. The active compensation system should filter harmonics from 2nd to 50th individual harmonic order and shall be selectable for the entire range. |
| 1807 | The active compensation system should have feature to improve PF correction and harmonic filtration having response time <25Micro second. The hybrid panel shall be indoor type floor mounted free standing totally enclosed, extensible, fabricated in compartmentalized designed made of CRCA sheet steel of 2.0mm thick for framework & covers, 3 mm thick for gland plate i/c cleaning & finishing complete with 9 tank process for powder coated of approved shade ( RAL 7032-Siemens gray or as approved by Engineer-in-Charge), having front section (switch gear and control accessories) and rear section (capacitor and reactor), front and rear access, having suitable current carrying capacity, extensible TPN Aluminum alloy bus bar of high conductivity, DMC/SMC bus bar supports, bottom base channel of MS Section, fabrication shall be done in transportable section, entire panel shall have common copper earth bar of minimum size of 25mm x 5mm with 2nos. earth studs, the earth terminals provided on the body of capacitor bank shall also be bonded to the main capacitor panel earth bus with 2 nos. 8 SWG or 6 SWG GI earth wires/ equivalent size of copper conductor cable, forced ventilation for maintaining temperature rise not more than 5°C from ambient, interconnections, connections with 14% detuned reactor and heavy duty 525 V ISI marked Impregnated MPP(Metalized Polypropylene) Capacitor (IS 13340 Part -1 & 2) APFC Panel shall be in compliance with IS :16636 & CPWD Specifications etc. as per below details. |
| 1808 | (A) Incomers |
| 1809 | 800A ACB (400KVAR+200A AHF) Microprocessor base with O/C, S/C, E/L release of TPN 50KA breaking capacity (Ics=Icu), ON, OFF, Trip, R, Y, B - LED Indicating Lamp set along with required Instruments and accessories with extended rotary handel and door interlocking arrangement. Current rating of the Incomer in ampere shall be APFC Panel rating in KVAR x 1.4 x 1.5 or Nearest higher standards rating.+ |
| 1810 | (B) Instruments & Indications |
| 1811 | a) For Passive Section : |
| 1812 | i) 3-Phase current sensing APFC microprocessor relay/controller, advance 12/16 stages (12 stages for over all capacity of panel (active + passive) below 500 KVAR and 16 stages 500 KVAR & above) and having display of Phase wise V, A, PF, Cos-Phi, KW, KVA, KVAR, THD-V , THD-I, harmonics up to 31 level. |
| 1813 | ii) Auto Manual Selector switch, auxiliary contactors with timer for delay in manual mode. |
| 1814 | iii) Digital Multi function meter with LED Display for V, A, PF, KW, KVA, KVAR, THD-V & I, Frequency. |
| 1815 | iv) Suitable rating control transformer shall be provided for control and indication circuit. |
| 1816 | v) All components like control transformer, meter, relay and indicating lamp shall be protected by using suitable rating individual MCB\"s. |
| 1817 | vi) Wiring of the control circuit shall be done by using 2.5 sq mm, FRLS 1100V grade, PVC insulated multi stranded copper control wire. |
| 1818 | vii) Communication Ethernet/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge. |
| 1819 | b) For Active Section : Dedicated HMI (Human Machine Interface) (Minimum 7 inch display) for controlling and communication and having display of Phase wise V, A, PF, Cos-Phi, KW, KVA, KVAR, THD-V , THD-I, harmonics up to 50th level. Communication Ethernet/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge. |
| 1820 | BUS DUCT (FOR ESS) |
| 1821 | Supply and fix sandwich type bus bar trunking system with aluminium busbar 2000 Amps, 50 KA breaking capacity, IP 54 protection, include with separators, flexible joints, tap off boxes, end feed units, earthing etc. |
| 1822 | 11 KV Cabel & Termination : |
| 1823 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : |
| 1824 | 300 sq. mm |
| 1825 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : |
| 1826 | 300 sq. mm |
| 1827 | Supply and laying of 3 core standered aluminium conductor XLPE (Cross linked polyethylene) insulated PVC bedded, Galvanised flat steel strip armoured cables confirming to I.S. 7098 (Part-II with latest amendments) 11KV grade at a depth of 900 mm below ground level over a cushion of 100 mm thick fine river sand all around and protected with well burnt bricks on sides and on top put across. The armouring of cable shall be properly connected with earth conductor by clamps etc. |
| 1828 | 300 sq. mm 3 core |
| 1829 | MISCELLANEOUS ITEMS |
| 1830 | Rubber mat of 1 meter x 2 meter x 10 mm |
| 1831 | Rubber mat of 1 meter x 2 meter x 19 mm |
| 1832 | Electric rubber hand gloves 11 KV |
| 1833 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 1834 | Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 1835 | Supply & Installation of D.P. Structure With AIR BREAK SWITCH having following specifications A, B, C, D, E. All as per pre approved by Engineer in charge. |
| 1836 | A) Double pole structure on 2 no ISMB ( I beam ) of size 150 x 75 mm,10 mtr length using 7 no MS channel each of size 100 mm x 50 mm x 2500 mm complete in all respect with nuts, springs washers, clamps as required. |
| 1837 | B) Off load type gang operated 3-pole vertical flute type switch suitable for 11KV ; 630A ,3-ø, central post rotating double break isolator complete with MS hardware , copper moving & fixed contact ,assembly of 9 nos pin insulator ,GI pipe of suitable length for operation. |
| 1838 | C) 3nos Vertical / Horizontal mounted 11kv horn gap fuse set /drop out 11kv barrel fuses mounted on 6no pin insulators |
| 1839 | D) 3 piece non linear resistor type. lighting arrestor of approved make suitable for 3 wire, 11kv Overheadline with rated voltage of 9kv rms & nominal discharge current rating of 5 ka & complete with galvanized clamping arrangement GI bolts, nuts, washer etc as required. |
| 1840 | E) 3 no 11kv ACSR conductors mounted on pin type insularors as required. GENERAL:The go shall be operated by hand operated liver properly earthed with provision for locking mounted at 3’ |
| 1841 | F) All design must be inline with SEB requirements no additional will be paid. |
| 1842 | Supply and installation of HT 11 KV, 3 phase, 50 cycles totally enclosed metal clad switchgearcomplete with Vacuum circuit breaker havingrupturing capacity upto 350 MVA, overload and earth fault protection, ammeter, voltmeter and of rating upto 630 Amp. |
| 1843 | SUB HEAD - X X I X SEWAGE DISPOSAL |
| 1844 | Providing, laying and jointing glazed DWC pipes IS 16098 Part - 2 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete : |
| 1845 | 160 mm dia |
| 1846 | 200 mm dia |
| 1847 | 250 mm dia |
| 1848 | Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand: 10 graded stone aggregate 40 mm nominal size) all-round pipes including bed concrete as per standard design : |
| 1849 | 160 mm dia pipe |
| 1850 | 200 mm dia pipe |
| 1851 | 250 mm dia pipe |
| 1852 | Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) up to haunches of pipes including bed concrete as per standard design : |
| 1853 | 160 mm dia pipe |
| 1854 | 200 mm dia pipe |
| 1855 | 250 mm dia pipe |
| 1856 | Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x 300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design: |
| 1857 | 150x100 mm size P type |
| 1858 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 1859 | Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement: 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone-III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design : |
| 1860 | Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) : |
| 1861 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 1862 | Extra for depth for manholes : |
| 1863 | Size 90x80 cm |
| 1864 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 1865 | Constructing brick masonry circular type manhole 0.91 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement : 4 coarse sand), inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size), and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design : |
| 1866 | 0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-20 grade designation) 560 mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182 kg., fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately) : |
| 1867 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 1868 | Extra depth for circular type manhole 0.91m internal dia (at bottom) beyond 0.91 m to 1.67 m |
| 1869 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 1870 | Constructing brick masonry circular manhole 1.22 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement :4 coarse sand) inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement foundation concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design : |
| 1871 | 1.68 m deep with SFRC Cover and frame (heavy duty HD-20 grade designation) 560 mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182 kg. fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately) : |
| 1872 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 1873 | Extra depth for circular type manhole 1.22 m internal dia (at bottom) beyond 1.68 m to 2.29 m : |
| 1874 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 1875 | Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : 10910, on 12 mm dia steel bar conforming to IS: 1786, having minimum cross section as 23 mmx25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture’s permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design. |
| 1876 | SEPTIC TANK |
| 1877 | Supplying, Installing, Testing & Commissioning ofReadymade polyethelene Septic Tank of capacity 28.5 KLD of size 2.0 dia x 9.25 m length x 16 mm thick with sufficient nos. of chambers and manhole of size 550 mm dia with provision in and out pipe of 160 mm dia of United /Supremeor equivalent approved make |
| 1878 | Making soak pit 2.5 m diameter 3.0 metre deep with 45 x 45 cm dry brick honey comb shaft with bricks and S.W. drain pipe 100 mm diameter, 1.8 m long complete as per standard design. |
| 1879 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 1880 | SUB HEAD -X X X -EXTERNAL LIGHTING |
| 1881 | Street Pole with LED Lamp : |
| 1882 | Supply & Installation of 9 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 155 mm and base plate 12mm thik) having 3mm thikness with Single Arm bracket (1 Mtr length) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and Required T&P completee in all respect. |
| 1883 | Supplying, installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >80, under voltage and over voltage protection, EMIEMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K /4000°K /5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. |
| 1884 | System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). |
| 1885 | 150 watt |
| 1886 | Supply and Installation of 240 volts C Curve 6-32 amp SP miniature circuit breaker (10 KA) in existing MCB, DB complete with connections as required. |
| 1887 | supply and Installation following capacity of automatic street light cubicle control pannel with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 seeries with contactors, HRC fuse, isolating switch, metering instrument and instrument box with CTs etc.complete in all respect. |
| 1888 | 40 A TPN |
| 1889 | Supply & Installation of anticlimbing device fabricated from G.I.(flat) of 25 mm x 6mm size in a shape of ring of the pole size, having G.I. flat pointed fins of length 225 mm in 8 nos. including all the materials, labour, T&P and other material required for proper completion for work and to the satisfaction of Engineer-in-Charge. |
| 1890 | High Mast Pole : |
| 1891 | Supply & Installation of 20 mtr High mast shaft of approved make with rising system hot dip glavanized inside & out side dip,heaving pole sheet thickness 4 mm. Top dia minium 150 mm, Bottom dia 410 mm base plate 32 mm thick suitable for wind velocity as per IS 875 part 3 & having no circumferential weld, with accessories for high mast such as head frame suitable for 6 to 12 luminaries & its control gear boxes 1.5 HP power tool moter, 3 point suspension system with steel wire rope 8 mm dia, double drum winch, including making suitable foundation as per manufature drawing/ site reuiment along with foundation bolts nuts, washers, anchor plates etc completee in all respect. |
| 1892 | Supply and Installation of factory wired integral LED flood light luminaires with die cast aluminium housing built with dirver set suitable for 170 to 200 Watt. Confirming to IP 66 protection complete in all respect. |
| 1893 | Earthing Work : |
| 1894 | Supply and burying of 40mm dia x 4.5 metres long G.I. Pipe vertically for earthing having 12mm dia. Holes spaced 75mm apart drilled up to 2 metre from the bottom complete with earthing lead of No. 6 to 8 SWG GI wire in G.I. Pipe up to appron (and from appron to switch board the cost of G.I. wire and pipe will be extra) upto switch board, 30cm square C.I. box with hinged cover masonary enclosure, funnel at top, alternate layers of charcoal/coke and salt at least 150mm thick alround etc. as per directions of Engineer-in-charge complete in all respects as per drawing. (Pole Earthing common for 3 to 4 Poles at every interval distance) |
| 1895 | Supply and laying of 25mm x 3 mm G.I. strip from earth electrode directly in the ground as required complete in all respects. |
| 1896 | Supply and Installation of two number 8 SWG G.I. wire in 15mm dia. G.I. pipe for earthing, laid in ground or in wall duly concealed including the cost of cement, sand, labour, T&P other material required for proper completion of work as directed at side. |
| 1897 | Providing, laying and Installation following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required. |
| 1898 | 50 mm dia |
| 1899 | Supplying & erecting water tight terminal box of cast iron of size 200 x 150 x 150 mm complete on pole. |
| 1900 | Supply & Installation of 3 meter long GI Decorative pole for below post top fitting with inbuilt junction box,MCB,sleeve in foundation and required wiring till fixture in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. |
| 1901 | Supply and Installation of decorative 35 Watt LED Post top indirect light luminaire having Pressure die cast aluminium body and Clear glass with driver set confirming to IP 65 and above protection complete in all respect including connecting copper wiring. |
| 1902 | SUB HEAD -X X X IBOUNDARY WALL |
| 1903 | Fencingwithangleironpostplacedatrequireddistanceembeddedin cement concrete blocks, every 15th post, last but one end post and corner post shall be strutted on both sides and end post on one side only and provided with horizontal lines and two diagonals interwoven with horizontal wires, of barbed wire weighing 9.38 kg per 100 m (minimum), between the two posts fitted and fixed with G.I. staples, turn buckles etc. complete. (Cost of posts, struts, earth work and concrete work to be paid for separately). Payment to be made per metre cost of total length of barbed wire used. |
| 1904 | With G.I. barbed wire |
| 1905 | Providing and fixing concertina coil fencing with punched tape concertina coil 600 mm dia 10 metre openable length ( total length 90 m), having 50 nos rounds per 6 metre length, upto 3 m height of wall with existing angle iron ‘Y’ shaped placed 2.4m or 3.00 m apart and with 9 horizontal R.B.T. reinforced barbed wire, stud tied with G.I. staples and G.I. clips to retain horizontal, including necessary bolts or G.I. barbed wire tied to angle iron, all complete as per direction of Engineer-in-charge, with reinforced barbed tape(R.B.T.) / Spring core (2.5 mm thick) wire of high tensile strength of 165 kg/ sq. mm with tape (0.52 mm thick) and weight 43.478 gm/ metre (cost of M.S. angle, C.C. blocks shall be paid separately) |
| 1906 | SUB HEAD -X X X I I -P.A.SYSTEM |
| 1907 | Public Addressable System : |
| 1908 | Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required. |
| 1909 | Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required. |
| 1910 | Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required. |
| 1911 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required. |
| 1912 | Supplying & laying of 2x1.5 Sqmtm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required. |
| 1913 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed mild steel conduit of following pairs, cores and size including connections and interconnections etc. as required. |
| 1914 | speaker cable Single pair, 2-core, 1.5 Sqmtm |
| 1915 | speaker cable Two pair, 2-core, 1.5 Sqmtm |
| 1916 | speaker cable Four pair, 2-core, 1.5 Sqmtm |
| 1917 | Supplying and Installation 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required. |
| 1918 | SUB HEAD -X X X I I I -GAS SUPPRESSION SYSTEM |
| 1919 | FIRE SUPPRESSION FOR ROOM : |
| 1920 | CLEAN GAS FIRE SUPPRESSION SYSTEMS : 34/80/120/140/180 Itr completele CCOE approved high pressure seamless BIS 7285 approved Cylinders having34/80/120/140/180 ltr capacity, UL/FM approved basedNovec 1230 clean agent stored pressurized system with PESO approved valve assembly . The system also to be fitted with digital pressure gauge to monitor pressure and temperature with safety burst disc safety cap, elbow and other accessories, mounting bracket, container straps, NRV , Pressure operated control head which shall allow for pressure actuation of gas mounted, manually operated actuator to actuate the gas flooding process with the help of a lever, flexible rubber hose with wire bralded enforcment to route the gas from the storage cyinder to the discharge piping, to be connected to the discharge outlet of gas cylinder valve & to be terminated at the system piping or discharge manifold, Flexible actuation hose complete as required. Designated to provide proper flow rate & distribution Novec 1230 gas to flood the hazard area as per latest NFPA 2001. |
| 1921 | The system shall sustain upto65oC operating temperature. filling facility shall be in India and shall be UL approved.The complete gas suppression system shall be UL/FM approved. As system is UL/FM approved , the software for calculation used to be UL/FM approved. The documentary evidence to pe provided for all approval during the time of bidding. |
| 1922 | 34/80 Itr complete PESO approved high pressure seamless BIS 7285 approved Cylinders with contact pressure guage and Pesoapproved valve, respective size mounting bracket |
| 1923 | Novec 1230 manufactured by 3M, with Zero Ozone Depeltion Potential and Very Low Global Warming Potential of 1 with 20 Years Blue Sky Warantee against any regulatory Bans and Restrictions. UL Listed & FM approved |
| 1924 | Master Cylinder Kit complete comprises of Electric Control Head operated electrically from the detection and control systemwith a manual actuator and Wire Braided Flexible Rubber Hose with Elbow and connectors complete assembly to Connect Novec 1230 Cylinder Assembly Discharge outlet with Discharge Pipe or Discharge Manifold.On any displacement of solenoid valve, master cylinder kit shall be able to notify the fault by audio/visual mean. UL Listed / FM approved |
| 1925 | Warning Signs and Plates for Inside Room and Outside Room application. |
| 1926 | Discharge Nozzles to Discharge Novec 1230 Gas in the Hazard Area as hydraulic calculation and flow rate required in 180 Deg/360 Deg Discharge Pattern. UL Listed / FM approved |
| 1927 | Discharge pressure switch with actuation hose and fittings to connect- standard (UL/FM) |
| 1928 | Discharge Pipe with Support and Fittings, CS Seamless to ASTM A-106 Schedule 40. |
| 1929 | Fire Alarm System with respect to Room sizeAutomatic Gas Extinguishing Panel. 2 No’s of programmable Initiating Device Circuit and 1 No’s of Releasing Agent circuit, with the independent correlation of any no of initiating devices circuit . History event log shall be atleast of 256 events. UL Listed / FM approved/IS 2189. |
| 1930 | ConventionalMulticriteria Detector with base. |
| 1931 | Manual Release Switch & Abort Switch . The Dualaction Manual release switch to provide the signalof fire manually to Gas release panel. Abort Switch. The Dualaction Abort switch to provide the signalof fire manually to Gas release panel for abort. |
| 1932 | Audio VisualAlarm for pre alarm in case of single zone detection & discharge alarm in case of second zone detection. |
| 1933 | Response Indicator. |
| 1934 | Supplying, laying, testing and commissioning offollowing sizes ofLow Smoke Zero Halogen Silicon Insulated Fire Survival Cable with Drain Wire Armouring, solid copper conducter cable approved by LPCB as per BSEN 50200:2015 PH 120 (Fire, Mech Shock & Water 120 Minutes @ 830 deg Celcius, Fire & Mech Shock every 5 Min for 2 Hours- Both test conducted on same sample) and BS-6387 CWZ The cable shall sustain 950 deg. C. The cable shall be BS EN 60332-1-2:2004 for Bunched Flame Retardancy (installed as a single or bunched cable self extinguishes leaving the upper cable sheath unaffected showing the cable does not propagate fire). Cable shall be guaranteed for 10 years from the date of manufacture marked on the cable 2C X 1.5sqmm. |
| 1935 | Completion of Work |
| 1936 | FIRE SUPPRESSION IN PANEL : |
| 1937 | UL Certified Extinguishing agent filled in PESO Approved Filling Station: 5 Kg FK-5-1-12 Clean agent filled in PESO approved stored pressure type seamless steel cylinder as per IS 7285 with DLP Valve Assembly, Safety Burst Disc at 28 Bar and Mounting Bracketwith all necessary fittings & supportsStored Pressure type fitted with Pressure gauge, UV Resistance, Operating Pressure 15 bar, Hydraulic Pressure Tested to 250 bar, Burst Pressure at 350 bar, Red Powder coated. |
| 1938 | UL Certified Extinguishing agent filled in PESO Approved Filling Station: 10 Kg FK-5-1-12 Clean agent filled in PESO approved stored pressure type seamless steel cylinder as per IS 7285 with DLP Valve Assembly, Safety Burst Disc at 28 Bar and Mounting Bracketwith all necessary fittings & supports Stored Pressure type fitted with Pressure gauge, UV Resistance, Operating Pressure 15 bar, Hydraulic Pressure Tested to 250 bar, Burst Pressure at 350 bar, Red Powder coated. |
| 1939 | UL Certified Linear pneumatic Heat Detection Tube for automatic fire detection & supperession system made by special modified polyamaide (PA), colour red RAL300, burst temperature 1000C to 1400C, inner diameter 4mm, outer diameter 6mm. Pressurised with dry nitrogen at 15 bar pressure with all necessary fittings & supports. |
| 1940 | Master Control Unit with audio visual alarm Control Panel, 12 Volt battery, 2 NO/NC potential free relay contact for Main Fire Alarm/BMS/SCADA Integration. Gas discharge led indicator, battery led indicator, system status Led indicator , AC power ON Led indicatowith all necessary fittings & supports. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
| 7 | Click here to download tender document | Tender Documents |
| 8 | Click here to download tender document | Tender Documents |
| 9 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail